2-100
TC-12001
OUTDOOR UNIT
24
P5414950-rev.1
(2) Use the branch pipe kit surely to the distributing pipe.
Do not use the T-Joint. Fix the branch pipes horizontally to the pillar, wall or ceiling.
NOTE:
:UDSWKHEUDQFKSLSHVZLWKDQLQVXODWLRQRUDSDGDQGWKHQ¿[WKHPRQWKHZDOOZLWKWKH¿[LQJSODWHV
O
Installation Posture of Branch Pipes
(3) Ensure the branch pipes position and height
difference between indoor units according to
WKHULJKW¿JXUH
NOTE:
)L[WKHSLSLQJIURPWKH
piping insulation above by
D¿[LQJSODWHRULQVHUWLQJ
the cushioning between the
piping and the plate when
¿[LQJWKHSLSLQJE\WKHSODWH
Cooling
Heating
Check Joint of
Gas Stop Valve
A
Low Pressure
High Pressure
Check Joint of Piping
B
High Pressure
Low Pressure
Check Joint of
Liquid Stop Valve
C
([FOXVLYHIRU9DFXXP3XPSDQG
Refrigerant Charge
The gas stayed at
O-ring screw part
LVRSHQHGDQGPD\
PDNHVRXQGZKHQ
UHPRYLQJWKHFDS
However, it is not gas
leakage.
NOTE:
Pay attention not to splash the refrigerant and the oil to
WKHHOHFWULFDOER[RUWKHHOHFWULFDOSDUWVZKHQUHPRYLQJ
the charge hose.
(4)
3UHVVXUH0HDVXUHPHQWE\&KHFN-RLQW
Use the check joint (the gas stop valve “
A
” and the piping “
B
´WRPHDVXUHWKHSUHVVXUH
,QWKLVWLPHFRQQHFWDPDQLIROGJDXJHDFFRUGLQJWRWKHWDEOHEHORZEHFDXVHKLJKDQGORZSUHVVXUHV
are interchanged depending on the operation (cooling or heating).
Keep Horizontal
K
eep Hor
iz
ontal
Keep Hor
izontal
Branch Connection
To Indoor Unit
To Indoor Unit
To Outdoor Unit
Keep Vertical
Fixing the Branch Pipe to
Ceiling Surface or Beam
Fixing the Branch Pipe
to the surface of Pillar or Wall.
Main Pipe
Main Pipe
Main Pipe
Main
Pipe
Branch
Connection
Branch
Connection
Branch
Connection
Branch
Connection
Branch Pipe
Branch
Pipe
Branch Pipe
Branch Pipe
Branch Pipe
Branch Pipe
Bending
Radius
Min.
0.5m
Min.
0.5m
Min.
0.5m
CORRECT
CORRECT
INCORRECT
INCORRECT
Upper Side
Upper Side
Upper Side
Upper Side
C
B
A
Height
Difference
Max.
0.5m
Max.
0.5m
Indoor Unit
Indoor Unit
(In Case of Twin Type)