Connection between Demand Response Enabling Device (DRED) and Outdoor Unit
This function is supported Australian Standard “Demand response capabilities and supporting
technologies for electrical products” AS 4755.3.1:2008.
AS 4755
Mode 1
Mode 2
Mode 3
When the input terminals DRM1 and SC are short-circuited, the compressor is forcibly stopped and the
indoor unit(s) is put under Thermo-OFF condition. The remote control switch display remains the running
mode with the stoppage code No. 10.
Wiring Diagram between DRED and Outdoor Unit
NOTES:
1. If the demand control (ON/OFF) with only time conditions is set, it is recommended to set the time
according to the load, not the constant setting time all through the year. The minimum set interval for
demand or forcible stoppage should be 30 minutes or more in consideration of the compressor’s
start-stop frequency and energy-saving.
2. When demand control (ON/OFF) is set, it is required to set the optional function setting. Select the
setting condition “0” to “1” at the Defrost Control in Demand Mode “
”.
Refer to item 10.3 in detail of setting.
Do not connect the power source cable or control cable to DRM1 and SC terminals.
It will cause a burnout of the printed circuit board.
(d) Connecting Remote Control Switch in Case
of Connecting between Refrigerant Cycles
O
Remote Control Switch Connecting Diagram
(a) Installing Remote Control Switch to each
Unit with Individual Operation Setting
(b) Installing One Remote Control Switch with
Individual Operation Setting
(c) Simultaneous Operation
Indoor Unit
Outdoor Unit
Remote
Control
Switch
A B
Indoor Unit
Remote
Control
Switch
A B
DSW6
ON
OFF
1 2
(Factory Setting Position)
Indoor Unit
Outdoor Unit
Remote
Control
Switch
A B
DSW6
ON
OFF
1 2
(Factory Setting Position)
Indoor Unit
A B
The remote control
switch cable is required.
O
The simultaneous
operation is available
up to 4 indoor units.
Indoor Unit
Outdoor Unit
Remote
Control
Switch
A B
DSW6
ON
OFF
1 2
Indoor Unit
A B
Change the setting
to "OFF" (DSW6-1).
Indoor Unit
Outdoor Unit
Remote Control
Switch
A B
Indoor Unit
Indoor Unit
Indoor Unit
Outdoor Unit
A B
A B
A B
Individual
Remote Control
Switch
Remote Control
Switch
Individual
Simultaneous
(Thermo ON / OFF individually)
R1
Field-Supplied
DRED
Outdoor Unit
TB2
DRM1
SC