– 106 –
HOW TO OPERATE USING THE SERVICE SWITCH THE OUTDOOR UNIT
1. Turn off the power supply to outdoor unit and then turn on again.
2. Remove the electrical box cover.
LD303 (red) will light and the unit will operate in the forced cooling mode at this time.
Never operate the unit for
more than 5 minutes.
(Cautions)
(1) If interface signal (DC 35V) terminals C and D are not connected when the outdoor unit is in forced cool mode, the outdoor
unit defect indicator (LD301) will blink 9 times during operation to indicate communication error.
(2) If checking is done with the compressor connector disconnected, the unit will continue normal operation when the
electrical parts are normal, or it will repeat operating for approx. one minute and stop due to overload power limit cut,
or it will operate in the overload status.
Be sure to push the service switch again to stop the forced cool operation.
HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY
The operation method is the same as “How to operate using the connector to servicing the outdoor unit”.
1 The charging amount of 300g is equivalent to the load in normal operation.
Charge refrigerant of 300g
after vacuuming ( 1 )
Do not operate for more than 5
minutes
Parts to be prepared
(1) Reducing union
2/8” (6.35mm)
1/2” (12.7mm)
(2) Copper pipe (2/8” and 1/2”)
1. Connect the large dia. pipe side and small dia. pipe side service valves using a pipe.
Connect the small diameter
service value and the large
diameter service valve using the
reducing union and copper pipe
as shown on the right.
Electrical Box Cover
Service switch
(forced-cooling mode is set by
pressing for 1 second or more,
and stopped by pressing again.)
Self diagnosis lamps
(LD303, 302, 301)
Large dia. service valve
Reducing union
(2/8 and 3/8 )
Copper pipe
(2/8 )
Small diameter
service valve
Reversing
valve
Compressor
Outdoor unit
Содержание RAC-50YH7
Страница 22: ... 21 SHIFT VALUE ADJUSTMENT ...
Страница 32: ... 31 Note 1 200mm or more servicing space is required above the outdoor unit ...
Страница 35: ... 34 INDOOR UNIT OUTDOOR UNIT A A A A WIRING DIAGRAM MODEL RAS 80YH5A RAC 80YH5 ...
Страница 36: ... 35 CIRCUIT DIAGRAM Remote Control ...
Страница 37: ... 37 CIRCUIT DIAGRAM MODEL RAS 80YH5A ...
Страница 38: ... 39 CIRCUIT DIAGRAM MODEL RAC 80YH5 ...
Страница 40: ... 42 MODEL RAC 80YH5 MAIN P W B ...
Страница 41: ... 43 MAIN P W B NF P W B CAPA P W B ...
Страница 46: ... 51 ...
Страница 49: ... 57 ...
Страница 83: ... 92 SELF DIAGNOSIS LIGHTING MODE DD0002204A ...
Страница 85: ... 94 2 Outdoor unit does not operate but receives remote infrared signal ...
Страница 88: ... 97 CHECKING THE REMOTE CONTROLLER ...
Страница 93: ... 102 16 ...
Страница 103: ...PM NO 0413E Printed in Malaysia RAS 80YH5A RAC 80YH5 ...