– 89 –
1. Turn OFF the Power supply to the outdoor unit.
2. After power is turned off, wait for 10 minutes or more. Then, remove electrical parts cover and apply soldering
iron of 30 to 75W for 15 seconds or more to P2 and N1 terminals on system power module, in order to
discharge voltage in smoothing capacitor.
3. Remove receptable of red/gray lead wire connected to system power module from diode stack before
performing operation chech of each circuit.
Caution
●
Voltage of about 300-330V is charged between both ends of smoothing capacitors
●
During continuity check for each part of circuit in indoor unit electrical parts, disconnect red/gray
lead wire connected from diode stack to system power module (SPM2) to prevent secondary
trouble. (Be sure to discharge smoothing capacitor)
Do not use a soldering iron with
transformer: If one is used, thermal fuse
inside transformer will be blown
DISCHARGE PROCEDURE AND POWER SHUT OFF METHOD FOR POWER CIRCUIT
WARNING
As shown above, apply soldering iron to metal
parts (receptable) inside the sleeve
corresponding to P1 and N1 terminals of
system power module: Do this with smoothing
capacitors kept connected. By removing red/
gray lead wire from diode stack, power supply
can be shut off. (corresponding to + and –
terminals of system power module)
N1
P1
Soldering
iron
System power module
Содержание RAC-50YH7
Страница 22: ... 21 SHIFT VALUE ADJUSTMENT ...
Страница 32: ... 31 Note 1 200mm or more servicing space is required above the outdoor unit ...
Страница 35: ... 34 INDOOR UNIT OUTDOOR UNIT A A A A WIRING DIAGRAM MODEL RAS 80YH5A RAC 80YH5 ...
Страница 36: ... 35 CIRCUIT DIAGRAM Remote Control ...
Страница 37: ... 37 CIRCUIT DIAGRAM MODEL RAS 80YH5A ...
Страница 38: ... 39 CIRCUIT DIAGRAM MODEL RAC 80YH5 ...
Страница 40: ... 42 MODEL RAC 80YH5 MAIN P W B ...
Страница 41: ... 43 MAIN P W B NF P W B CAPA P W B ...
Страница 46: ... 51 ...
Страница 49: ... 57 ...
Страница 83: ... 92 SELF DIAGNOSIS LIGHTING MODE DD0002204A ...
Страница 85: ... 94 2 Outdoor unit does not operate but receives remote infrared signal ...
Страница 88: ... 97 CHECKING THE REMOTE CONTROLLER ...
Страница 93: ... 102 16 ...
Страница 103: ...PM NO 0413E Printed in Malaysia RAS 80YH5A RAC 80YH5 ...