CHECKING THE REFRIGERATING CYCLE
1.
Troubleshooting procedure (No operation, No heating, No cooling)
Connect U,V,W phase leads to the
power module again and operate the
air conditioner.
Gas leaks.
Repair and seal refrigerant.
Is the self-diagnosis lamp mode as
shown on the right?
YES
Gas leaking
(less than 4kg/cm
2
G)
(less than 0.39 MPaG)
Normal
(0.39-0.98 MPaG)
(4-10 kg/cm
2
G)
Perform a final check of operation.
When the
self-diagnosis lamp
lights in the same
condition as above.
The compressor is defective. Replace it
and seal refrigerant.
If the compressor checker for an
inverter type air conditioner is
available, re-check using it.
( )
(JUDGING BETWEEN GAS LEAKAGE AND
COMPRESSOR DEFECTIVE)
Blinking
off
Time until the
lamp lights
Approx. 10 seconds
Approx.
10
seconds
Approx.
10
seconds
Within
Approx.
30
seconds
Compressor
Compressor
Gas
leakage
Possible
malfunctioning
part
LD301
Self-
diagnosis lamp
Lighting mode
Blinks
2 times
Blinks
3 times
Blinks
4 times
Blinks
5 times
Blinks
6 times
Blinks
8times
Stop to operate and check the gas
pressure in balancing mode.
Checking the system power module
Содержание RAC-50YH7
Страница 22: ... 21 SHIFT VALUE ADJUSTMENT ...
Страница 32: ... 31 Note 1 200mm or more servicing space is required above the outdoor unit ...
Страница 35: ... 34 INDOOR UNIT OUTDOOR UNIT A A A A WIRING DIAGRAM MODEL RAS 80YH5A RAC 80YH5 ...
Страница 36: ... 35 CIRCUIT DIAGRAM Remote Control ...
Страница 37: ... 37 CIRCUIT DIAGRAM MODEL RAS 80YH5A ...
Страница 38: ... 39 CIRCUIT DIAGRAM MODEL RAC 80YH5 ...
Страница 40: ... 42 MODEL RAC 80YH5 MAIN P W B ...
Страница 41: ... 43 MAIN P W B NF P W B CAPA P W B ...
Страница 46: ... 51 ...
Страница 49: ... 57 ...
Страница 83: ... 92 SELF DIAGNOSIS LIGHTING MODE DD0002204A ...
Страница 85: ... 94 2 Outdoor unit does not operate but receives remote infrared signal ...
Страница 88: ... 97 CHECKING THE REMOTE CONTROLLER ...
Страница 93: ... 102 16 ...
Страница 103: ...PM NO 0413E Printed in Malaysia RAS 80YH5A RAC 80YH5 ...