– 47 –
Notes:
1. The speed set of rotation for the fan motor in each operation mode are as shown in Table 1.
2. The set room temperatures in the diagram include the shift values in Table 2.
3. See Damper control theory for damper control and upper/lower fan operations.
¥ Same as at left.
¥ Performs the sleep operation of each operation mode.
Operating mode is judged by room temperature and outdoor temperature.
(1) Judging by outdoor temperature
¥ Operating mode is judged by outdoor temperature.
Only when the mode is not restricted by this judgment, the judgment by room temperature in the next paragraph
will be performed.
(a) Outdoor temperature
30¡C : Restricted to cooling
(b) Outdoor temperature
9¡C : Restricted to heating
(2) Judging by room temperature
Operating mode at start up is judged (initial judgment)
(a) Conditions for judgment (any of the followings)
¥ When auto operation is started after 1 hour has elapsed since the operation was stopped.
¥ When auto operation is started after the previous manual mode operation.
¥ When the operating mode is switched to auto while operating at manual mode.
(b) Judging method
¥ Room temperature
23¡C –3¡C : Cooling
¥ Room temperature < 23¡C –3¡C : Heating
–3¡C is the fine adjustment value from the remote controller.
Judging operating mode change during operation (Continuous judgment)
(a) Conditions for judgment (any of the followings)
¥ The mode is reviewed at every interval time.
¥ When auto operation is started again before 1 hour has elapsed since the operation was stopped.
(b) Judging method
¥ Judge by setting the hysteresis on the final preset temperature.
The final preset temperature is the actually targeted preset temperature which is the sum of the basic preset temperature
and each type of shift value (e.g. –3¡C by remote controller, preset temperature correction value, powerful shift value, etc.).
[Currently cooling]
¥ Room temperature
Final preset temperature —3¡C Change to heating
¥ Room temperature > Final preset temperature —3¡C Continue cooling
[Currently heating]
¥ Room temperature
Final preset tempe2¡C Change to cooling
¥ Room temperature < Final preset tempe2¡C Continue heating
Set to ultra-Lo , Lo , Med , Hi , ultra-Hi or stop depending on the room temperature,
time and heat exchange temperature. Set to stop if the room temperature is 18ßC in the
ultra-Lo mode other than during preheating (cooling is recovered at 18.33ßC).
Set to ultra-Lo , Lo , Med , Hi , ultra-Hi or stop depending on the room temperature, and
time. Set to stop if the room temperature is 18ßC in the ultra-Lo mode other than during
preheating (cooling is recovered at 18.33ßC).
Set to ultra-Hi when the compressor is running at maximum speed during hot dash or when
recovered from defrosting.
Set to ultra-Lo , Lo , Med or stop depending on the room temperature and time. Set to
stop if the room temperature is 18ßC in the ultra-Lo mode other than during preseating
(cooling is recovered at 18.33ßC).
Set to ultra-Lo , Lo , or stop depending on the room temperature and time. Set to stop if
the room temperature is 18ßC in the ultra-Lo mode other than during preseating (cooling is
recovered at 18.33ßC). The fan speed is controlled by the heat exchanger temperature; the
overload control is executed as in the following diagram:
See page 55.
¥ Same as at left
¥ See page 57.
Set to Hi in modes other than when the
compressor stops.
Set to Med in modes other than when the
compressor stops.
Set to Lo in modes other than when the
compressor stops.
See page 53.
¥ Same as at left
¥ See page 53.
Set to ultra-Hi when the
compressor runs at maximum
speed, and to Hi in other modes.
1. Runs at Hi until first thermo
off after operation is started.
2. Runs at Lo when thermo is
off.
1. The indoor fan also stops when the
compressor is in stop status.
Changes between Lo and Med
depending on the room temperature.
Changes from Hi to Med or
Lo depending on room
temperature.
Division 1
Division 2
Division 3
Division 4
Lo
Fan speed
Temperature division
Lo
Med
Med
Same as at left.
Same as at left.
See page 49.
¥ Same as at left
¥ See page 51.
Operates at Hi regardless of the
room temperature.
Operates at Med regardless of
the room temperature.
Operates at Lo regardless of the
room temperature.
Performs only fan operation at the
set speed regardless of the room
temperature.
¥ Enters sleep operation after set
as on the left.
¥ Action during sleep operation
Lo (sleep) operation
Hi
Fan speed mode (indoor fan)
Med
Lo
Basic operation of
temperature controller
Sleep operation
(with sleep button ON)
When the compressor is running at maximum speed
during hot dash or when recovered from defrosting.
In modes other than
left
42. 66
ßC
37. 66
32. 66
29. 66
Lo
Med
Med with overload
Lo
KAFON
Heat exchanger temperature
KAFOF
Hi or ultra-HI
(fan speed set
to auto )
Heat exchanger
temperature
(Compressor stopped
forcibly for 3 minutes)
Thermo iudgment
Temperature set
for cooling
Compressor
Hi
Med
Lo
Auto
Heating
Cooling
Dehumidifying
(dehumidifying operation by the
function select button only, not including
that engaged by the dehumidify button)
Fan
Operation mode
Basic operation of
start/stop switch
Off-timer
On-timer
T
imer functions
Off -> On
On -> Off timer
Auto
Start
Stop
(Off-timer during stop)
(On-timer during operation)
ON
ON
ON
OFF
OFF
OFF
ON
OFF
(Change in reserved time)
(Change in reserved time)
(Off->On timer)
(On->Off timer) (On->Off timer)
during operation)
(Off->On timer)
during stop)
Start
Start/stop switch
Operation tamp
Start/stop switch
Operation tamp
Cancel switch
Cancel switch
Reserve switch
Srart/stop switch
Operation temp
Operation temp
Timer tamp
Timer tamp
Timer memory
Timer memory
Timer memory
Timer lamp
Operation lamp
Cancel switch
Reserve switch
Start/stop switch
Stop
Start/stop switch
Operation lamp
Hi
Hi
Med
Lo
Fan
Speed
Med
Lo
Cooling
Heating
Room
-temperature
22¡C
9¡C
30¡C
Outdoor
temperature
Cooling
Heating
final preset temperature
MODEL
RAK-25NH5, RAK-35NH5
BASIC M O D E
Содержание RAC-25NH5
Страница 31: ... 29 MODEL RAK 25NH5 RAK 35NH5 ...
Страница 37: ...CIRCUIT DIAGRAM MODEL RAK 25NH5 RAK 35NH5 37 ...
Страница 38: ...CIRCUIT DIAGRAM MODEL RAC 25NH5 RAC 35NH5 39 ...
Страница 39: ... 41 PRINTED WIRING BOARD LOCATION DIAGRAM MODEL RAK 25NH5 RAK 35NH5 MAIN P W B Marking on P W B ...
Страница 40: ... 42 MODEL RAK 25NH5 RAK 35NH5 RECEIVING P W B Marking on P W B ...
Страница 41: ... 43 MODEL RAC 25NH5 RAC 35NH5 MAIN P W B Marking on P W B COMPONENT SIDE ...
Страница 53: ... 64 ...
Страница 54: ... 65 ...
Страница 55: ... 66 ...
Страница 56: ... 67 ...
Страница 90: ... 101 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 25NH5 RAC 35NH5 ...
Страница 92: ... 103 2 Outdoor unit does not operate but receives remote infrared signal ...
Страница 94: ... 105 6 Check the main P W B power circuit ...
Страница 95: ... 106 CHECKING THE REMOTE CONTROLLER ...
Страница 100: ... 111 ...
Страница 106: ... 117 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAK 25NH5 RAK 35NH5 ...
Страница 112: ...HITACHI PM NO 0324E Printed in Malaysia RAK 25NH5 RAC 25NH5 RAK 35NH5 RAC 35NH5 ...