Delay
–1.33˚C
–0.66˚C
– 55 –
Notes:
(1) If the room temperature is (cooling preset temperature) - (1.33
°
C) or less after 30 seconds from starting the operation, the operation is done assuming
as the preset temperature = (room temperature at the time) - (2
°
C).
(2) The indoor fan is operated in the “Lo” mode. During thermo OFF indoor fan will be OFF for 5 minutes and ON for 1 minute.
(3) When the operation is started by the themostat turning ON, the start of the indoor fan is delayed 32 seconds after the start of compressor operation.
(4) The compressor is operated forcedly for 3 minutes after operation is started.
(5) The minimum ON time and OFF time of the compressor are 3 minutes.
Содержание RAC-25NH5
Страница 31: ... 29 MODEL RAK 25NH5 RAK 35NH5 ...
Страница 37: ...CIRCUIT DIAGRAM MODEL RAK 25NH5 RAK 35NH5 37 ...
Страница 38: ...CIRCUIT DIAGRAM MODEL RAC 25NH5 RAC 35NH5 39 ...
Страница 39: ... 41 PRINTED WIRING BOARD LOCATION DIAGRAM MODEL RAK 25NH5 RAK 35NH5 MAIN P W B Marking on P W B ...
Страница 40: ... 42 MODEL RAK 25NH5 RAK 35NH5 RECEIVING P W B Marking on P W B ...
Страница 41: ... 43 MODEL RAC 25NH5 RAC 35NH5 MAIN P W B Marking on P W B COMPONENT SIDE ...
Страница 53: ... 64 ...
Страница 54: ... 65 ...
Страница 55: ... 66 ...
Страница 56: ... 67 ...
Страница 90: ... 101 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 25NH5 RAC 35NH5 ...
Страница 92: ... 103 2 Outdoor unit does not operate but receives remote infrared signal ...
Страница 94: ... 105 6 Check the main P W B power circuit ...
Страница 95: ... 106 CHECKING THE REMOTE CONTROLLER ...
Страница 100: ... 111 ...
Страница 106: ... 117 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAK 25NH5 RAK 35NH5 ...
Страница 112: ...HITACHI PM NO 0324E Printed in Malaysia RAK 25NH5 RAC 25NH5 RAK 35NH5 RAC 35NH5 ...