4. Failure phenomenon: The fan motor will not stop.
>
Situation
@
I have conducted the stop operation on the product by remote control, but the indoor fan motor will not stop.
(It stopped about 10 minutes later.)
>
Estimated failure locations
@
·
Indoor fan motor
·
Fan motor drive circuit
>
Diagnosis flow
@
Initiating troubleshooting
Yes
Replace the "indoor fan motor".
No
Replace the "indoor electrical parts".
Run the product by remote control and then stop it.
(Reproduce the failure phenomenon.)
Is the voltage between pins
ĺ
and
ļ
of the fan motor
connector (CN2) below 1.5 V? (Take measurements
while the failure phenomenon is present.)
86
Содержание RAC-18WPD
Страница 2: ... DANGER 2 ...
Страница 24: ...24 ...
Страница 25: ...25 ...
Страница 26: ...26 ...
Страница 28: ...Contact your sales agent immediately if the following phenomena should occur Notes 28 ...
Страница 31: ...WIRING DIAGRAM RAK 15QPD RAK 18RPD RAK 25RPD RAK 35RPD RAK 42RPD RAK 50RPD 31 ...
Страница 33: ...CIRCUIT DIAGRAM MODEL RAK 15QPD 33 ...
Страница 34: ...CIRCUIT DIAGRAM MODEL RAK 18 25 35 42 50RPD 34 ...
Страница 57: ...10 10 10 10 10 DSW1 57 ...
Страница 61: ...RL1 RL1 RL2 61 ...
Страница 70: ...68 70 ...
Страница 73: ...37 and page 38 73 ...
Страница 74: ...Please set the DIP switch No 6 to ON accordingly Refe to page r RAR 6N1 RAR 6N2 RAR 6N3 RAR 6N4 RAR 6N5 57 74 ...
Страница 75: ...57 75 ...
Страница 76: ...76 ...
Страница 77: ... 䇭䇭 䇭䇭 䇭䇭 䇭䇭 䇭䇭 䇭䇭 B C E F 㺢 F 䌖 B GH E H C J E 77 ...
Страница 78: ... 䇭䇭 G FK 㺢 F L M C B C M C E C B H C E B M C E C B M C 78 ...
Страница 93: ...RAK 15QPD RAK 18RP RAK 25RP D D RAK 35RP RAK 42RP D D RAK RPD 50 JCH WH NO 0108E 93 ...