5. Horizontal distance limit of remote controller:
Ceiling
Height of indoor unit
Wireless
Remote Controller
Horizontal
distance
Floor
Indoor unit (Air panel)
Receiver kit
Horizontal distance limit of remote control (in the case that height of remote controller from floor is 1 m):
RCIM
Height of indoor unit (m)
2.7
3.0
3.5
4.0
Horizontal distance (m)
2.9
3.5
4.0
4.5
RCI
Height of indoor unit (m)
2.7
3.0
3.5
4.0
4.5
5.0
Horizontal distance (m)
2.9
3.5
4.0
4.5
4.5
4.5
RCD/RPI
Height of indoor unit (m)
2.5
3.0
3.5
3.8
Horizontal distance (m)
2.5
3.5
4.0
4.0
6. Checking of command reception. Lamp (yellow) of receiver part in receiver kit blinks when receiver kit receive commands from
wireless remote controller. If lamp does not blink, commands are not sent correctly. Send commands again.
NOTE:
Beep as well as lamp blink when commands are received correctly.
The beep may not be heard due to the ambient noise.
7. Other Receiver Kit indications:
(For gas heat pump air conditioner only)
When using a gas heat pump air conditioner, “FILTER” LED (yellow) and “TIMER” LED (green) may blink at the same time. This
does not mean abnormality, but indicates the periodical checking of the engine is coming soon or has already passed.
“FILTER” (yellow) and “TIMER” (green) lamps blink slowly (every two seconds). Indicates that the periodical checking of the
engine is coming soon.
“FILTER” (yellow) and “TIMER” (green) lamps blink rapidly (every 0.5 seconds). Indicates that the timing of periodical checking
of the engine has already passed.
Ask for periodical checking when these indications appear.
8. Wall mount (RPK) Dip Switch setting:
a) The factory setting of SW1 is “Wireless”. To use with a receiver kit, slide SW1 to change to “Wired”.
b) Dip switch shall be set when both Indoor and Outdoor unit power is OFF. Setting configured with Indoor and/or Outdoor unit
power ON will be invalid.
9. The temperature setting is available from 17ºC to 30ºC by using a wireless remote control switch. The temperature range is
different depending on the indoor unit model. For the unit with the temperature setting range is 19ºC to 30ºC, 17ºC and 18ºC can
not be set by the wireless remote switch.
−
−
−