transmission wire connection
transmission wire connection
Fig. 6.2 Three phase indoor unit and outdoor unit
Fig. 6.1 Single phase indoor unit and outdoor unit
20
If connected, the printed circuit board will be damaged.
These terminals are for the Control Line.
Do not connect the Power Source Line to the terminal 1 and 2.
(3N~)
Indoor Unit
Indoor Unit
Outdoor Unit
ELB for
Outdoor Unit
ELB for
(4) Use shielded twist pair for
unit. Refer to Fig. 6.3-Fig.6.4
Refer to Fig. 6.1-Fig.6.2
6.2
Electrical Wiring Connection
(1) Connect the power supply wires to the
terminal board in the electrical control box
of both outdoor unit and indoor unit. And
connect the earth wire to the electrical
control box of outdoor unit.
In addition, connect the earth wire to earth
screw in the electrical control box of indoor
(2) Connect the wires between the outdoor
and indoor units to terminals 1 and 2 on the
terminal board.
If power supply wiring is connected to 1
and 2 of terminal board (TB1), printed
circuit board will be damaged.
Remote
Control
Switch
(Option)
Remote
Control
Switch
(Option)
(3) Do not wire in front of the fixing screw of
the service panel. Otherwise, the screw can not
be removed.
NOTES:
2. Total wiring length for remote control switch
can be extended up to 500m.
If total wiring length less than 30m, it is
possible to use the normal wiring (0.3mm
2
)
except shielded twist pair.
control between outdoor unit and indoor
unit, control wiring between indoor units,
1. In case of total wiring length at intermediate
wiring between outdoor unit and indoor unit
and between indoor units is less than 100m, it
is possible to use the normal wiring (more than
0.75mm
2
) except shielded twist pair .
ELB for
Outdoor Unit
Indoor Unit
Indoor Unit
CORRECT (1N~)
Remote
Control
Switch
(Option)
Remote
Control
Switch
(Option)
(1N~)
INCORRECT
CORRECT
INCORRECT (3N~)
Remote
Control
Switch
(Option)
Remote
Control
Switch
(Option)
Remote
Control
Switch
(Option)
Remote
Control
Switch
(Option)
ELB for
Outdoor Unit
Outdoor Unit
Indoor Unit
Indoor Unit
ELB for
ELB for
Outdoor Unit
Indoor Unit
Indoor Unit
Outdoor Unit
Indoor Unit
Outdoor Unit
ELB for
Outdoor Unit
Connect the wires between the outdoor
and indoor units to terminals 1 and 2 on
the terminal board.
220V~ 60Hz
220-240V~ 50Hz
220-240V~ 50Hz
220V~ 60Hz
220V~ 60Hz
220-240V~ 50Hz
380-415V 3N~ 50Hz
380V 3N~ 60Hz
220-240V~ 50Hz
220V~ 60Hz
380V 3N~ 60Hz
380-415V 3N~ 50Hz