Hissmekano Viksam 3.0 Скачать руководство пользователя страница 8

 

 

 

www.hissmekano.se 

Manual Viksam 3.0 version 2 

 October 2022 

 

 

3.5

 

Relay contacts 

If you need to use the relay contacts, you need to remove the cover on the control and connect the 
relays according to the picture below.  

NOTE: We only use relays 1-3.

 

 
Obstruction: This contact switches/triggers when the torque limit is reached in the close/open cycle. 
Closed position: This contact switches/triggers when the door is fully closed. 
Open position: This contact switches/triggers when the door is fully open. 
 
 

 

3.6

 

Blocking 

When the door is blocked, the door must reverse. 
In case of blocking in the opening/closing phase, the door will always reverse, but the signal can be 
taken from the relay contacts on the inside of the control. After 3 attempts, the control will wait for a 
new signal. 

3.7

 

Door hanging 

For the opening and closing signals to steer the door in the right direction, the encoder cables must 
be correctly connected, see below. If it is connected correctly, the door will stop in the closed 
position after the learning trip. If the engine is on the right side seen from a floor plan, it is a right-
hanging door. 
 

NOTE. When changing direction, it is important to switch off the power and start up the steering 
learning journey mode. Otherwise, there is a risk that the door runs at full speed toward the limit 
positions when it thinks that the position is outside the doorway. 

 

Содержание Viksam 3.0

Страница 1: ...Viksam 3 0...

Страница 2: ...Voltage supply 5 3 2 Motor and encoder connection 5 3 3 Interface and settings 6 3 4 Pinch crushing protection 6 3 5 Relay contacts 7 3 6 Blocking 7 3 7 Door hanging 7 4 Commissioning 8 4 1 Learning...

Страница 3: ...rature 0 till 50 C Max voltage current for relays 230 VAC 10A Fuse 6 3A slow 5x20mm Inputs Open Signal Close signal Connections 12 x screw terminals for motor encoder signals Supply cable IEC C14 Rela...

Страница 4: ...ackside of the hanger rail Each angle needs 4x square nuts and 4x hexagonal screws Adjust the angles to approx 10mm from each pilaster Mount the idler pulley furthest into the track of the bracket to...

Страница 5: ...lley is pressed against the frame See the figure below This requires that the angle is correctly mounted on the rail and that the idler pulley has some space left in the track Belt tension adjustment...

Страница 6: ...ied with a quick connect IEC C14 cable for the power supply This is connected to 230 VAC and earth A fuse 2 5A slow is located in the connection housing 3 2 Motor and encoder connection The motor is d...

Страница 7: ...n 9 and 12 If there is no signal or if both signals are active the door will stay in its current position If the door control is connected to a common opening and closing signal 1 wire communication t...

Страница 8: ...e opening closing phase the door will always reverse but the signal can be taken from the relay contacts on the inside of the control After 3 attempts the control will wait for a new signal 3 7 Door h...

Страница 9: ...ay in the closed position NOTE If it stays in the open position the encoder may be incorrectly connected see section 3 2 When the learning journey is finished the push button must be set to the normal...

Страница 10: ...www hissmekano se Manual Viksam 3 0 version 2 October 2022 9 5 Troubleshooting...

Страница 11: ...9 Motor 3710331 Motor tension roller angle 3710298 Power supply unit 3710332 7 Maintainance 7 1 Lubrication of tension roller Push the roller down so that a small gap appears and spray some spray grea...

Отзывы: