11. INSTALLATION TOOLS AND INSTALLATION FLOW CHART
11. Installation tools and installation flow chart
11.1
Necessary tools and instrument list for installation
No.
Tool
No.
Tool
No.
Tool
No.
Tool
1
Handsaw
6
Copper Pipe Bender
11
Spanner
16
Leveler
2
Phillips
Screwdriver
7
Manual Water Pump
12
Charging Cylinder
17
Clamper for Solder-
less Terminals
3
Vacuum Pump
8
Pipe Cutter
13
Gauge Manifold
18
Hoist
(for Indoor Unit)
4
Refrigerant
Gas Hose
9
Brazing Kit
14
Cutter for Wires
19
Ammeter
5
Megohmmeter
10
Hexagon Wrench
15
Gas Leak Detector
20
Voltage Meter
Use tools and measuring instruments only for the new refrigerant which is directly touch to refrigerant.
✧
: Interchangeability is available with R410A
●
: Only for Refrigerant R32
✕
: Prohibited
✦
: Only for Refrigerant R22
Measuring Instrument and
Tool for R410A
R32
R22
Reason of Non-Interchangeability and
Attention (*: Strictly Required)
Use
Refrigerant
Pipe
Pipe Cutter
Chamfering
Reamer
✧
✧
-
Cutting Pipe
Removing Burrs
Flaring Tool
✧
✧
*
*
The flaring tools for R32 are applicable
to R22/R410A.
If using flaring tube, make dimension
of tube larger for R410A.
* In case of material 1/2H, flaring is not
available.
Flaring for Tubes
Pipe Bender
✧
✧
* In cas of material 1/2H, bending is not
available. Use elbow for bend and braze. Bending
Expanding Tool
✧
✧
* In cas of material 1/2H, expanding of
tube is not available. Use socket for
connecting tube.
Expanding Tubes
Torque Wrench
✧
×
✕
* or
φ
1/2,
φ
5/8, spanner size is up
2mm.
Connection of Flare
Nut
✧
✧
* Fo
φ
1/4,
φ
3/8,
φ
3/4, spanner size is
the same.
Brazing Tool
✧
✧
* Perform correct brazing work.
Brazing for Tubes
Nitrogen Gas
✧
✧
* Strict Control against Contamin (Blow
nitrogen during brazing.)
Prevention from
Oxidation during
Brazing
Lubrication Oil
(for Flare
Surface)
●
✦
* Use a synthetic oil which is equivalent
to the oil used in the refrigeration cycle.
* Synthetic oil absorbs moisture quickly.
Applying Oil to the
Flared Surface
Vacuum
Drying&
Refrigerant
Charge
Refrigerant
Cylinder
✕
✕
* C eck refrigerant cylinder color.
* Liquid refrigerant charging is required
regarding zeotoropic refrigerant.
* Use the weight scale.
Refrigerant Charging
Vacuum Pump
✧
✧
* The current ones are applicable.
However, it is required to mount a
vacuum pump adapter which can prevent
from reverse flow when a vacuum pump
stops, resulting in no reverse oil flow.
Vacuum Pumping
Adapter for
Vacuum Pump
✧
✦
Manifold Valve
✧
✦
* No interchangeability is available due to
higher pressures when compared with
R22.
* Do not use current ones to the different
refrigerant. If used, mineral oil will flow
into the cycle and cause sludges,
resulting in clogging or compressor
failure.
* Connection diameter is different;
R32/R410A: UNF1/2, R22: UNF7/16.
Vacuum Pumping,
Vacuum Holding,
Refrigerant Charging
and Check of
Pressures
Charging Hose
✧
✕
Weight Scale
✧
✧
Measuring Instrument
for Refrigerant
Charging
Refrigerant Gas
Leakage
Detector
✕
✕
* Th current gas leakage detector (R22)
is not applicable due to different detecting
method.
Gas Leakage Check
46
Содержание 2AMW-42U4RRA
Страница 10: ...1 GENERAL Type Capacity Btu h View 1 to 5 indoor units 42K 6 ...
Страница 15: ...3 OUTLINES AND DIMENSIONS 21K AMW3 24U4RFA Unit mm 11 ...
Страница 16: ...3 OUTLINES AND DIMENSIONS AMW3 24U4RAA Unit mm 414 380 12 ...
Страница 17: ...3 OUTLINES AND DIMENSIONS 27K Unit mm 414 380 13 ...
Страница 18: ...3 3 O OU UT TL LI IN NE ES S A AN ND D D DI IM ME EN NS SI IO ON NS S Unit mm 42K 14 ...
Страница 29: ...7 REFRIGERANT CYCLE 7 Refrigerant cycle 12K 14K 18K 21K 24K 25 ...
Страница 32: ...8 WIRING DIAGRAM Electric wiring diagram 1982504 D 21K AMW3 24U4RFA 28 ...
Страница 33: ...8 WIRING DIAGRAM AMW3 24U4RAA Electric wiring diagram 1957327 B 29 ...
Страница 34: ...8 WIRING DIAGRAM 27K 36K 30 ...
Страница 39: ...8 WIRING DIAGRAM Maintenance board Select switch signal to mainboard Communication signal to main board 35 ...
Страница 80: ...Product improvement specifications and appearance in this manual are subject to change without prior notice ...