9.
FIELD
SETTING
9. Field Setting
9.1 DIP Setting
21K/AMW3-24U4RFA/42K
Dip Switch Setting of Outdoor Unit
Mark of " " indicates the position of dip switches.
Switch is valid when is ON.
39
Refrigerant collection function
By default setting is OFF.
OFF ----normal mode
ON----refrigerant collection mode
When the power is ON, the dial changed from OFF to ON, enters into refrigerant collection mode.
During refrigerant recovery mode, system low pressure protect will not occurs, and compressor
will stops after 5 minutes, and will turn to normal state when power on again.
Manual defrost function
By default setting is OFF.
By
OFF ----normal mode
ON----defrost mode
When the dial changed from OFF to ON in heating mode, enters into defrost mode, and only
valid once.
Содержание 2AMW-42U4RRA
Страница 10: ...1 GENERAL Type Capacity Btu h View 1 to 5 indoor units 42K 6 ...
Страница 15: ...3 OUTLINES AND DIMENSIONS 21K AMW3 24U4RFA Unit mm 11 ...
Страница 16: ...3 OUTLINES AND DIMENSIONS AMW3 24U4RAA Unit mm 414 380 12 ...
Страница 17: ...3 OUTLINES AND DIMENSIONS 27K Unit mm 414 380 13 ...
Страница 18: ...3 3 O OU UT TL LI IN NE ES S A AN ND D D DI IM ME EN NS SI IO ON NS S Unit mm 42K 14 ...
Страница 29: ...7 REFRIGERANT CYCLE 7 Refrigerant cycle 12K 14K 18K 21K 24K 25 ...
Страница 32: ...8 WIRING DIAGRAM Electric wiring diagram 1982504 D 21K AMW3 24U4RFA 28 ...
Страница 33: ...8 WIRING DIAGRAM AMW3 24U4RAA Electric wiring diagram 1957327 B 29 ...
Страница 34: ...8 WIRING DIAGRAM 27K 36K 30 ...
Страница 39: ...8 WIRING DIAGRAM Maintenance board Select switch signal to mainboard Communication signal to main board 35 ...
Страница 80: ...Product improvement specifications and appearance in this manual are subject to change without prior notice ...