![Hirschmann RSPE30 Скачать руководство пользователя страница 61](http://html1.mh-extra.com/html/hirschmann/rspe30/rspe30_user-manual_2138135061.webp)
Installa
tio
n
RSPE30/3
2
/35
/37
Release
16
0
4/2019
61
7.3
EMC and immunity
EMC interference
emission
Standard
applications
Navy applications Railway
applications
(trackside)
Substation
applications
Radiated emission
EN 55032
Class A
Class A
Class A
Class A
GL Guidelines
—
EMC 1
—
—
FCC 47 CFR Part 15
Class A
Class A
Class A
Class A
EN 61000-6-4
Fulfilled
Fulfilled
Fulfilled
Fulfilled
Conducted emission
EN 55032
DC supply connection
Class A
Class A
Class A
Class A
GL Guidelines
DC supply connection
—
EMC 1
—
—
FCC 47 CFR Part 15
DC supply connection
Class A
Class A
Class A
Class A
EN 61000-6-4
DC supply connection
Fulfilled
Fulfilled
Fulfilled
Fulfilled
EN 55032
Telecommunication connections
Class A
Class A
Class A
Class A
EN 61000-6-4
Telecommunication connections
Fulfilled
Fulfilled
Fulfilled
Fulfilled
EMC interference
immunity
Standard
applications
Navy applications Railway
applications
(trackside)
Substation
applications
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge
±4 kV
±6 kV
±6 kV
±8 kV
EN 61000-4-2
IEEE C37.90.3
Air discharge
±8 kV
±8 kV
±8 kV
±15 kV
Electromagnetic field
EN 61000-4-3
80 MHz ... 3000 MHz
10 V/m
10 V/m
max. 20 V/m
10 V/m
IEEE 1613
80 MHz ... 1000 MHz
—
—
—
35 V/m
Fast transients (burst)