54
Inst
allation
EAGLE20/30
Re
lease
12
03/2
021
EN 61000-4-3
80 MHz ... 800 MHz
10 V/m
—
10 V/m
10 V/m
EN 61000-4-3
800 MHz ... 1000 MHz
10 V/m
—
20 V/m
10 V/m
EN 61000-4-3
1400 MHz ... 6000 MHz
3 V/m
—
—
—
EN 61000-4-3
1400 MHz ... 3000 MHz
—
—
—
10 V/m
EN 61000-4-3
1400 MHz ... 2000 MHz
—
—
10 V/m
—
EN 61000-4-3
2000 MHz ... 2700 MHz
—
—
5 V/m
—
EN 61000-4-3
5100 MHz ... 6000 MHz
—
—
3 V/m
—
IEEE 1613
80 MHz ... 1000 MHz
—
—
—
35 V/m
Fast transients (burst)
EN 61000-4-4
IEEE C37.90.1
AC/DC supply connection
±1 kV
±1 kV
±2 kV
±4 kV
EN 61000-4-4
IEEE C37.90.1
Data line
±4 kV
±1 kV
±2 kV
±4 kV
Voltage surges - DC supply connection
EN 61000-4-5
IEEE 1613
line/ground
±2 kV
±1 kV
±2 kV
±5 kV
EN 61000-4-5
line/line
±1 kV
±0.5 kV
±1 kV
±1 kV
Voltage surges - AC supply connection
EN 61000-4-5
IEEE 1613
line/ground
±2 kV
±1 kV
±2 kV
±5 kV
EN 61000-4-5
line/line
±1 kV
±0.5 kV
±1 kV
±2 kV
Voltage surges - data line
EN 61000-4-5
line/ground
±1 kV
—
±2 kV
±4 kV
Conducted disturbances
EN 61000-4-6
150 kHz ... 80 MHz
10 V
10 V
10 V
10 V
EMC interference
immunity
Standard
applications
Navy applications Railway
applications
Substation
applications