2.3
Installing and grounding the device
2.3.1
Installing the device onto the DIN rail
Note:
Verify that there is at least 4 in (10 cm) of space above and below the
device.
Note:
The overall shield of a connected shielded twisted pair cable is
connected to the grounding connector on the front panel as a conductor.
To mount the device onto a horizontally mounted 35 mm DIN rail according
to DIN EN 60715, proceed as follows:
Slide the upper snap-in guide of the device into the DIN rail.
Press the media module downwards onto the clip-in bar.
Snap in the device.
WARNING
FIRE HAZARD
If you connect the device to a power supply that does
NOT
meet the
requirements for Limited Power Source, NEC Class 2 or PS2 according to
IEC/EN 62368-1 and is
NOT
limited to 100 W output power, the device
must be installed in either a switch cabinet or other fire enclosure.
The fire enclosure can be made of metal or plastic with fire-protection
properties of at least V-1 according to IEC 60695-11-10. Bottom openings
of the fire enclosure must
NOT
exceed 2 mm in diameter.
Failure to follow this instruction can result in death, serious injury, or
equipment damage.
WARNING
Only for device variants featuring supply voltage with characteristic
value K9 or KK:
ELECTRIC SHOCK
Install this device only in a switch cabinet or in an operating site with
restricted access, to which maintenance staff have exclusive access.
Failure to follow this instruction can result in death, serious injury, or
equipment damage.