System Manual Compact Systems
7 Start-Up
HI 800 141 E Rev. 2.02
Page 85 of 110
External devices that should communicate with HIMatrix controllers must have the following
network settings:
Parameter
Alternative 1
Alternative 2
Alternative 3
Alternative 4
Speed Mode
Autoneg
Autoneg
10 Mbit/s
100 Mbit/s
Flow Control Mode
Autoneg
Half Duplex
Half Duplex
Half Duplex
Table 56: Permissible Communication Settings for External Devices - CPU OS up to V7
The following network settings are not allowed:
Parameter
Alternative 1
Alternative 3
Alternative 4
Speed Mode
Autoneg
10 Mbit/s
100 Mbit/s
Flow Control Mode
Full Duplex
Full Duplex
Full Duplex
Table 57: Impermissible Communication Settings for External Devices - CPU OS up to V7
COM OS V8.32 and Higher and ELOP II Hardware Management V7.56.10 and Higher:
The operating parameters of each Ethernet port on the integrated Ethernet switch can be set
individually.
For HIMatrix controllers and remote I/Os with extended settings, set the
Speed Mode
and
Flow
Control Mode
to
Autoneg
. To ensure that the parameters of this dialog box become effective,
the option
Activate Extended Settings
must be selected, see Figure 11.
Figure 11: Communication System Properties - CPU OS up to V7
The parameters
ARP
,
MAC Learning
,
IP Forwarding
,
Speed Mode
and
Flow Control Mode
are
explained in details in the ELOP II Factory online help.
i
Replacement of one controller with identical IP address:
If a controller has its
ARP Aging Time
set to 5 minutes and its
MAC Learning
set to
Conservative
, its communication partner does not adopt the new MAC address until a period
of 5 to 10 minutes after the controller is replaced. During this time period, no communication is
possible with the replaced controller.
The port settings of the integrated Ethernet switch on a HIMatrix resource can be configured
individually starting with the following versions.
V8.32 of the communication operating system and
V7.56.10 of ELOP II Hardware Management
Select
Ethernet Switch -> New -> Port Configuration
to define the configuration parameters
for each switch port.