The parameters of the scalar events must be entered in a table with the following columns:
Column
Description
Range of values
Name
Name for the event definition; it must be unique within the
resource.
Text, max. 32
characters
Global Variable
Name of the assigned global variable (added using a drag&drop
operation)
Data Type
Data type of the global variable; it cannot be modified.
Depending on the
global variable type
Event Source
CPU event
The processor module creates the timestamp. It
creates all the events in each of its cycles.
Auto event As CPU event
Default value: Auto Event
CPU, Auto
HH Alarm Text
Text specifying the alarm state of the highest limit (HH).
Text
HH Alarm Value Highest limit (HH) triggering an event. Condition:
(HH Alarm Value - Hysteresis) > H Alarm Value or HH Alarm
Value = H Alarm Value
Depending on the
global variable type
HH Alarm Priority Priority of the highest limit (HH); default value: 500
0...1000
HH Alarm
Acknowledgment
Required
Activated
The user must confirm that the highest limit (HH) has
been exceeded (acknowledgment).
Deactivated The user may not confirm that the highest limit (HH)
has been exceeded.
Default value: Deactivated
Checkbox activated,
deactivated
H Alarm Text
Text specifying the alarm state of the high limit (H).
Text
H Alarm Value
High limit (H) triggering an event. Condition:
(H Alarm Value - Hysteresis) > (L Alarm Value + Hysteresis) or H
Alarm Value = L Alarm Value
Depending on the
global variable type
H Alarm Priority
Priority of the high limit (H); default value: 500
0...1000
H Alarm
Acknowledgment
Required
Activated
The user must confirm that the high limit (H) has
been exceeded (acknowledgment).
Deactivated The user may not confirm that the high limit (H) has
been exceeded.
Default value: Deactivated
Checkbox activated,
deactivated
Return to Normal
Text
Text specifying the normal state
Text
Return to Normal
Severity
Priority of the normal state; default value: 500
0...1000
Return to Normal
Ack Required
The normal state must be confirmed by the user
(acknowledgement); default value: Deactivated
Checkbox activated,
deactivated
L Alarm Text
Text specifying the alarm state of the low limit (L).
Text
L Alarm Value
Low limit (L) triggering an event. Condition:
(L Alarm Value + Hysteresis) < (H Alarm Value - Hysteresis) or L
Alarm Value = H Alarm Value
Depending on the
global variable type
L Alarm Priority
Priority of low limit (L); default value: 500
0...1000
L Alarm
Acknowledgment
Required
Activated
The user must confirm that the low limit (L) has been
exceeded (acknowledgment).
Deactivated The user may not confirm that the low limit (L) has
been exceeded.
Default value: Deactivated
Checkbox activated,
deactivated
LL Alarm Text
Text specifying the alarm state of the lowest limit (LL).
Text
LL Alarm Value
Lowest limit (LL) triggering an event. Condition:
(LL Alarm Value + Hysteresis) < (L Alarm Value) or
LL Alarm Value = L Alarm Value
Depending on the
global variable type
LL Alarm Priority Priority of the lowest limit (LL); default value: 500
0...1000