F3 DIO 16/8 01
4 Start-Up
HI 800 177 E Rev. 1.01
Page 41 of 58
4.4.3
Digital Inputs of F3 DIO 16/8 01
System Signal
R/W
Description
Mod.SRS [UDINT]
R
Slot number (System Rack Slot)
Mod. Type [UINT]
R
Type of module, target value: 0x00E2 [226
dez
]
Module error code
0x0000
I/O processing, if required with errors, see other error
codes
0x0001
No I/O processing (remote I/O not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: wrong configuration
0x0020
No I/O processing: fault rate exceeded
Mod. Error Code [WORD] R
0x0040/
0x0080
No I/O processing: configured module not plugged in
Error code of the DI supply unit as a whole:
DI.Error Code Supply
[WORD]
R
0x0001 Module
fault
Triggering the single DI supplies
0x01
Error DI supply unit
0x02
Supply shutdown due to over current
DI[xx].Error Code Supply
[BYTE]
R
0x04
Error while reading back the supply
Error codes for all digital inputs
0x0001
Fault within the digital inputs
DI.Error Code [WORD]
R
0x0002
FTT test of test pattern faulty
Error codes for the digital input channels
0x01
Fault in the digital input module
0x10
Short-circuit of the channel
DI[xx].Error Code [BYTE]
R
0x80
Intermittence between pulsed output TO and digital
input DI, e.g.,
Open-circuit
Open
switch
L+ low voltage
Input values for the digital input channels
0 Input
de-energized
DI[xx].Value [BOOL]
R
1 Input
enerized
Number of pulsed outputs (supply outputs)
0
No pulsed output planned for LS/LB
1)
detection
1
Pulsed output 1 planned for LS/LB
1)
detection
2
Pulsed outputs 1 and 2 planned for LS/LB
1)
detection
DI Number of
Pulsed Channels [USINT]
W
Pulsed outputs must not be used as safety-related outputs!
Triggering the single DI supplies
0
Sensor supply (1 A) is off.
1
Sensor supply (1 A) is on.
DI Supply[xx] [BOOL]
W
Default setting 0: feeding current 40 mA
DI Pulse
Slot [UDINT]
W
Pulse module slot
(LS/LB
1)
detection), set the value to 3
Surce channel for pulsed supply
0 Input
channel
1
Pulse of the 1st TO channel
DI[xx].Pulsed Channel
[USINT]
W
2
Pulse of the 2nd TO channel