3 Product Description
F3 DIO 16/8 01
Page 24 of 58
HI 800 177 E Rev. 1.01
3.4.2 Communication
The remote I/O communicates with the associated controller via safe
ethernet
.
3.4.2.1
Connections for Ethernet Communication
Property
Description
Port
2 x RJ-45
Transfer standard
10/100/Base-T, half and full duplex
Auto negotiation
Yes
Auto crossover
Yes
Connection socket
RJ-45
IP address
Freely configurable
1)
Subnet mask
Freely configurable
1)
Supported protocols
Safety-related:
safe
ethernet
Non-safety-related:
programming and debugging tool (PADT), SNTP
1)
The general rules for assigning IP address and subnet masks must be adhered to.
Table 9:
Ethernet Interfaces Properties
The two RJ-45 connectors with integrated LEDs are located on the bottom left-hand side of
the enclosure. For more information on the communication LEDs, refer to Chapter 3.4.1.3.
The connection parameters are read based on the MAC address (media access control
address) defined during manufacturing.
The MAC address for the remote I/O is specified on a label located above the two RJ-45
connectors (1 and 2).
Figure 9:
Sample MAC Address Label
The remote I/O is equipped with an integrated switch for safety-related Ethernet
communication (safe
ethernet
). For further information on the integrated switch and
safe
ethernet,
refer to Chapter C
ommunication
of the System Manual for Compact Systems
(HI 800 141 E).
3.4.2.2
Network Ports Used for Ethernet Communication
UDP ports
Usage
8000
Programming and operation with the programming tools
8001
Configuration of the remote I/O using the PES (ELOP II Factory)
8004
Configuration of the remote I/O using the PES (SILworX)
6010 safe
ethernet
123
SNTP (time synchronization between PES and remote I/O, PES and
external devices)
Table 10: Network Ports in Use