F3 DIO 16/8 01
4 Start-Up
HI 800 177 E Rev. 1.01
Page 35 of 58
System Signal
Data
type
R/W Description
Module Error Code
WORD
R
Module error code
Coding
Description
0x0000
I/O processing, if required with errors
see other error codes
0x0001
No I/O processing (remote I/O not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: wrong configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module SRS
UDINT
R
Slot number (System Rack Slot)
Module Type
UINT
R
Type of module, target value: 0x00E2 [226
dez
]
1)
LS/LB
(short-circuit/open-circuits)
Table 21: SILworX - System Parameters for Digital Inputs,
Module
Tab
4.3.2.2
DI 16 LC: Channels
Tab
The
DI 16 LC
:
Channels
tab contains the following system parameters.
System Signal
Data
type
R/W Description
Channel no.
---
R
Channel number, defined by default
-> Error Code
[BYTE]
BYTE
R
Error codes for the digital input channels
Coding
Description
0x01
Fault in the digital input module
0x10
Short-circuit of the channel
0x80
Intermittence between pulsed output TO and
digital input DI, e.g.,
Open-circuit
Open
switch
L+ low voltage
-> Value [BOOL]
BOOL
R
Input values for the digital input channels
0 = input de-energized
1 = input energized
Pulsed Channels
[USINT] ->
USINT
W
Source channel for pulsed supply
Coding
Description
0 Input
channel
1
Pulse of the 1st TO channel
2
Pulse of the 2nd TO channel
Table 22: SILworX - System Parameters for Digital Inputs,
DI 16 LC: Channels
Tab