3 Product Description
F3 DIO 16/8 01
Page 18 of 58
HI 800 177 E Rev. 1.01
3.1.4.3
Test Period and Monitoring Time
For line diagnosis, configure the test period and the monitoring time. These time
parameters influence all the channels configured for line diagnosis.
During the monitoring time, the status is read back in 1 ms intervals and, if no faults are
detected, the process values are rewritten to the output. The monitoring time can be set in
intervals of 1 ms between 0 and 50 ms (default value 0 ms).
i
The duration of the monitoring time is added to the cycle time. During the monitoring time,
the output circuit is supplied with a reduced voltage.
The time period can be configured in intervals of 1 second between 1 and 100 seconds.
The interval depends on following parameters:
Number of test pulses allowed in the external circle
Monitoring
time
If the time period is set to 1 second, a test pulse is sent in intervals of 250 ms for the
duration of the monitoring time.
Within one test period, 4 test pulses are generally pulsed in intervals of 0.25 seconds.
After the period time the line diagnosis is finished and the next line diagnosis cycle starts.
3.2
Equipment, Scope of Delivery
The available variants and their part numbers are listed below:
Designation
Description
Part no.
F3 DIO 16/8 01
Remote I/O with 16 digital inputs, 8 digital outputs
and 2 pulsed outputs,
operating temperature 0...+60 °C, for ELOP II
Factory programming tool.
98 2200423
F3 DIO 16/8 01
SILworX
Remote I/O with 16 digital inputs, 8 digital outputs
and 2 pulsed outputs,
operating temperature 0...+60 °C for SILworX
programming tool.
98 2200486
Table 4:
Part Numbers