4 Start-Up
DI 24 01
Page 22 of 34
HI 800 201 E Rev. 1.00
4.4
Configuring a Module Using ELOP II Factory
4.4.1
Configuring the Inputs
The signals previously defined in the Signal Editor (Hardware Management) are assigned
to the individual channels (inputs) using ELOP II Factory. Refer to the System Manual for
Compact Systems or the online help for more details.
The following chapter describes the system signals used for assigning signals in the
controller.
4.4.2
Signals and Error Codes for the Inputs
The following tables specify the system signals that can be read and set for the inputs,
including the corresponding error codes.
In the user program, the error codes can be read using the signals assigned within the
logic.
The error codes can also be displayed in ELOP II Factory.
4.4.2.1 Digital
Inputs
System Signal
R/W
Description
Mod.SRS [UDINT]
R
Slot number (System Rack Slot)
Mod. Type [UINT]
R
Type of module, target value: 0xFA05 [64005
dec
]
Mod. Error Code
[WORD]
R
Error codes for the module
Coding
Description
0x0000
I/O processing, if required with errors
see other error codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: wrong configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not plugged in
DI.Error Code
[WORD]
R
Error codes for all digital inputs
Coding
Description
0x0001 Module
fault
0x0002
FTT test of test pattern faulty
0x0004
FTT test: 1st temperature threshold exceeded
0x0008
FTT test: 2nd Temperature threshold exceeded
DI[xx].Error Code
[BYTE]
R
Error codes for the digital input channels
Coding
Description
0x01
Fault in the analog input module
DI[xx].Value [BOOL]
R
Input values for the digital input channels
0 = input de-energized
1 = input energized
Table 13: ELOP II Factory - Digital Input System Signals