dIXEL
Operating Manual
1592020130
1592020130 XR03_04CX GB 16.01.07.doc
XR03CX – XR04CX
Protection: IP20; Frontal protection: IP65
Connections: Screw terminal block
≤
2,5 mm
2
wiring.
Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac
±
10%, 50/60Hz,
110Vac
±
10%, 50/60Hz
Power absorption: 3VA max
Display: 2 digits, red LED, 14,2 mm high; Inputs: Up to 2 NTC or PTC probes.
Digital input: free voltage contact
Relay outputs: compressor SPST 8(3) A, 250Vac; or 20(8)A 250Vac
defrost or Aux: SPDT 8(3) A, 250Vac
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B; Pollution grade: 2;Software class: A.;
Rated impulsive voltage: 2500V; Overvoltage Category: II
Operating temperature: 0÷60 °C; Storage temperature: -30÷85 °C.
Relative humidity: 20
÷
85% (no condensing)
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);
Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
14. CONNECTIONS
XR03CX –20A o 8A Compressor
NOTE: The compressor relay is 20(8)A or 16(6)A depending on the model.
NOTE: 120Vac or 24Vac/dc or 12Vac/dc connect to 6-7
XR04CX –20A o 8A Compressor
NOTE: The compressor relay is 20(8)A or 16(6)A depending on the model.
NOTA: 120Vac o 24Vac/dc o 12Vac/dc connect to 6 and 7
15. DEFAULT SETTING VALUES
LAB
EL
DESCRIPTION
RANGE
DEFAULT
REGULATION
Hy
Differential
0.1 ÷ 25°C/1 ÷ 45°F
2.0°C / 4 °F
LS
Minimum Set Point
-55°C÷SET/-67°F÷SET
-55 °C /-
55°F
US
Maximum Set Point
SET÷99°C/ SET÷210°F
99 °C /
99°F
ot
First probe calibration
-9.9÷9.9°C/-18÷18°F
0.0
P2
Second probe presence (Only
XR04CX)
n – Y
y
oE
Second probe calibration (Only
XR04CX)
-9.9÷9.9°C/-18÷18°F 0.0
od
Outputs activation delay at start up
0 ÷ 99 min
0
AC
Anti-short cycle delay
0 ÷ 50 min
1
Cy
Compressor ON time faulty probe
0 ÷ 99 min
15
Cn
Compressor OFF time faulty probe
0 ÷ 99 min
30
CH
Kind of Action (Only XR03CX)
cL ÷ Ht
cL
DISPLAY
CF
Measurement units
°C - °F
°C / °F
rE
Resolution (only for °C)
dE – in
dE
Ld
Default Display (Only XR04CX)
P1-P2 - SP
P1
dy
Display delay
0 ÷ 15 min
0
DEFROST
td
Defrost type
EL – in
EL
dE
Defrost termination temperature
-50÷50°C/-58÷122°F
8.0 °C / 46
°F
id
Interval between defrost cycles
0 ÷ 99 hours
6
Md
Maximum length for defrost
0 ÷ 99 min.
30
dd
Start defrost delay
0 ÷ 99 min.
0
dF
Display during defrost
rt – in – SP – dF
it
dt
Drip time
0 ÷ 99 min
0
dP
Defrost at power-on
y - n
n
ALARMS
AU
Maximum temperature alarm
ALL÷99°C / ALL÷210°F
99 °C / 99
°F
AL
Minimum temperature alarm
-55°C÷ALU/-67°F÷ALU
-55 °C / -55
°F
Ad
Temperature alarm delay
0 ÷ 99 min
15
dA
Exclusion of temperature alarm at
startup
0 ÷ 99 min
90
DIGITAL INPUT (Only XR03CX)
iP
Digital input polarity
cL – oP
cL
iF
Digital input configuration
EA – bA – do – dF –
Au– db
EA
di
Digital input delay
0 ÷ 99 min
5
dC
Compressor and fan status when open
door
no /Fn / cP / Fc
FC
rd
Regulation with door open
n - Y
y
OTHER
d1
Thermostat probe display
Read Only
- - -
d2
Evaporator probe display
Read Only
- - -
Pt
Parameter code table
Read Only
- - -
rL
Firmware release
Read Only
- - -
dIXEL
S.p.a.
Z.I. Via dell’Industria, 27 - 32010 Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
http://www.dixell.com
E-mail:
Содержание OWZA
Страница 2: ...ii ...
Страница 15: ...APPENDIX A DOMESTIC WIRING DIAGRAM ...
Страница 16: ......
Страница 17: ......
Страница 18: ......
Страница 19: ......
Страница 20: ...APPENDIX B EXPORT WIRING DIAGRAM ...
Страница 21: ......
Страница 22: ......
Страница 23: ......
Страница 24: ......
Страница 25: ...APPENDIX C CONTROLLER INFORMATION ...
Страница 29: ...APPENDIX D USER SET POINTS ...
Страница 30: ......