background image

dIXEL 

Operating Manual 

1592020130 

 

1592020130 XR03_04CX GB 16.01.07.doc 

                           

XR03CX – XR04CX

 

 

Hy Differential: 

(0,1°C 

÷

 25°C) Intervention differential for set point. Compressor Cut IN is SET 

POINT + differential (Hy). Compressor Cut OUT is when the temperature reaches the set point. 

LS Minimum 

SET 

POINT: (-55°C÷SET/-58°F÷SET): Sets the minimum value for the set point.. 

US  Maximum SET POINT: (SET÷99°C/ SET÷99°F). Set the maximum value for set point. 

ot  First probe calibration: (-9.9÷9.9°C) allows to adjust possible offset of the first probe. 

P2  Evaporator probe presence:  n= not present; y= the defrost stops by temperature. (Only 

XR04CX

oE  Second probe calibration: (-9.9÷9.9°C) allows to adjust possible offset of the second probe. 

(Only XR04CX

od  Outputs activation delay at start up: (0÷99min) This function is enabled at the initial start up of 

the instrument and inhibits any output activation for the period of time set in the parameter.  

AC   Anti-short cycle delay: (0÷50 min) minimum interval between the compressor stop and the 

following restart. 

Cy  Compressor ON time with faulty probe: (0÷99 min) time during which the compressor is active 

in case of faulty thermostat probe. With Cy=0 compressor is always OFF. 

Cn  Compressor OFF time with faulty probe: (0÷99 min) time during which the compressor is OFF 

in case of faulty thermostat probe. With Cn=0 compressor is always active. 

CH  Kind of Action (Only XR03CX): cL= cooling action; Ht = heating action; 
DISPLAY 

 

CF Measurement 

unit: 

(°C÷°F) °C =Celsius; °F =Fahrenheit. WARNING: When the measurement 

unit is changed the SET point and the values  of the parameters Hy, LS, US, oE, o1, AU, AL 

have to be checked and modified if necessary). 

rE  Resolution (only for °C):(dE ÷ in) dE= decimal between -9.9 and 9.9°C; in= integer 

Ld Default 

display: 

(P1 ÷ P2) P1= thermostat probe; P2= evaporator probe. SP=Set point (Only 

XR04CX) 

dy Display 

delay: 

(0

÷

15 min.) when the temperature increases, the display is updated of 1 °C/1°F 

after this time. 

 

DEFROST 

 

td Defrost 

type: 

(EL – in) EL=  electrical heater, compressor OFF; in= hot gas, compressor ON;

 

dE  Defrost termination temperature (Only XR04CX): (-50÷50°C) if P2=Y it sets the temperature 

measured by the evaporator probe, which causes the end of defrost.

 

id  Interval between defrost cycles: (0÷99 ore) Determines the time interval between the 

beginning of two defrost cycles.  

Md  Maximum length for defrost: (0÷99 min. with 0 no defrost) when P2=n, (not evaporator probe: 

timed defrost) it sets the defrost duration, when P2 = y (defrost end based on temperature) it sets 

the maximum length for defrost. 

dd  Start defrost delay: ( 0÷99min) This is useful when different defrost start times are necessary to 

avoid overloading the plant. 

dF Display 

during 

defrost: 

(rt / it / St / dF) rt= real temperature; it= start defrost temperature; SP= 

SET-POINT; dF= label dF. 

dt   Drip time: (0÷99 min) time interval between reaching defrost termination temperature and the 

restoring of the control’s normal operation. This time allows the evaporator to eliminate water 

drops that might have formed due to defrost. 

dP  Defrost at power –on: (y÷n) y= at power on defrost starts; n= defrost doesn’t start at power-on 

 

ALARMS 

 

AU  Maximum temperature alarm: (AL÷99°C) when this temperature is reached  the alarm is 

enabled, after the “Ad” delay time. 

AL  Minimum temperature alarm: (-55÷AU°C) when this temperature is reached  the alarm is 

enabled, after the “Ad” delay time. 

Ad Temperature 

alarm 

delay: (0÷99 min) time interval between the detection of an alarm condition 

and alarm signalling. 

dA  Exclusion of temperature alarm at startup: (0÷99 min) time interval between the detection of 

the temperature alarm condition after instrument power on and alarm signalling. 

tb Silencing 

buzzer 

(n-y):(Only XR03CX)  n= silencing disabled, alarm relay stays on till alarm 

conditions lasts; y= silencing enabled: alarm relay is switched OFF by pressing a key during an 

alarm

o1  Auxiliary relay configuration (dF/Fn/AL/AU/db): (Only XR03CX)  dF= defrost; Fn= Fans; AL= 

Alarm; AU= auxiliary; db= neutral zone; 

AP  Alarm relay polarity (cL-OP): (Only XR03CX) cL= when active is closed; OP= when active is 

opened 

DIGITAL INPUT (Only XR03CX) 

 

iP   Digital input polarity: (oP ÷ cL) oP= activated by closing the contact; cL= activated by opening 

the contact; 

iF  Digital input configuration: (EA/bA/do/dF/Au/Hc) EA= external alarm: “EA” message is 

displayed; bA= serious alarm “CA” message is displayed; do= door switch function; dF= defrost 

activation; Au =not used; Hc= inversion of the kind of action; 

di  Digital input delay: (0÷99 min) with iF=EA or bA delay between the detection of the external 

alarm condition and its signalling. . With iF=do it represents the delay to activate the door open 

alarm. 

dC  Compressor and fan status when open door: (no/Fn/cP/Fc): no= normal; Fn = Fans OFF; cP 

=Compressor OFF; Fc = Compressor and fans OFF; 

rd  Regulation with door open: (n÷y) n = no regulation if door is opened; Y= when di is elapsed 

regulation restarts even if door open alarm is present; 

OTHER 

 

d1   Thermostat probe display (read only)  
d2  Evaporator probe display (read only) (Only XR03CX) 

Pt   Parameter code table 

rL   Software release 

8. DIGITAL  INPUTS 

The free voltage digital input is programmable in different configurations by the “iF” parameter. 

 

DOOR SWITCH (iF=do) 

 

It signals the door status and the corresponding relay output status through the “dC” parameter: no = 

normal (any change); Fn = Fan OFF; CP = Compressor OFF; FC = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter “di”, the door alarm is enabled, 

the display shows the message “dA” and the regulation restarts if rd = y. The alarm stops as soon 

as the external digital input is disabled again. With the door open, the high and low temperature alarms 

are disabled. 

 

EXTERNAL ALARM (iF=EA) 

 

As soon as the digital input is activated the unit will wait for “di” time delay before signalling the “EA” 
alarm message. The outputs status don’t change. The alarm stops just after the digital input is de-

activated. 

 

SERIOUS ALARM (iF=bA) 
When the digital input is activated, the unit will wait for “di” delay before signalling the “CA” alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-

activated. 
SWITCHING SECOND RELAY ON (iF=Au) 
When o1=Au it switches on and off the second relay. 

 

START DEFROST (iF=dF) 
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 

restart only if the digital input is disabled otherwise the instrument will wait until the “dd” safety time is 
expired. 
INVERSION OF THE KIND OF ACTION: HEATING - COOLING  (iF=Hc) 

 

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

9. INSTALLATION AND  MOUNTING 

 

Instrument  XR03CX and XR04CX shall be mounted on vertical 

panel, in a 29x71 mm hole, and fixed using the special bracket 

supplied. 
The temperature range allowed for correct operation is 0

÷

60 °C. 

Avoid places subject to strong vibrations, corrosive gases, 

excessive dirt or humidity. The same recommendations apply to 

probes. Let air circulate by the cooling holes. 

 

 

10. ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5 

mm

2

. Before connecting cables make sure the power supply complies with the instrument’s 

requirements. Separate the probe cables from the power supply cables, from the outputs and the 

power connections. Do not exceed the maximum current allowed on each relay, in case of heavier 

loads use a suitable external relay. 

1.1

 

PROBES 

 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid 

infiltration. It is recommended to place the thermostat probe away from air streams to correctly 

measure the average room temperature. Place the defrost termination probe among the evaporator 

fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 

defrost, to prevent premature defrost termination. 

11.  HOW TO USE THE HOT KEY 

1.2

 

HOW TO PROGRAM THE HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “Hot key” and push   key; the  "uP" message appears 

followed a by flashing “Ed” 

3.

 

Push “SET” key and the “Ed” will stop flashing. 

4.

 

Turn OFF the instrument remove the “Hot Key”, then turn it ON again. 

 

NOTE: the “Er” message is displayed for failed programming. In this case push again o key if you want 

to restart the upload again or remove the “Hot key” to abort the operation. 

1.3

 

HOW TO PROGRAM AN INSTRUMENT USING HOT KEY (DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON. 

3.

 

Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the 

do” message is blinking followed a by flashing “Ed”. 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the “Hot Key”.. 

 

NOTE: the “Er” message is displayed for failed programming. In this case push again o key if you want 

to restart the upload again or remove the “Hot key” to abort the operation. 

12. ALARM 

SIGNALLING 

Mess.  Cause 

Outputs 

"P1"  

Room probe failure 

Compressor output according to “Cy” e “Cn”  

"P2"  

Evaporator probe failure 

Defrost end is timed (Only XR04CX) 

"HA" 

Maximum temperature alarm 

Outputs unchanged 

"LA" 

Minimum temperature alarm 

Outputs unchanged 

“EA” External 

alarm 

Outputs 

unchanged 

“CA” 

Serious external alarm 

All outputs OFF. 

“dA” 

Door Open 

Compressor and fans restarts  

1.4

 

ALARM RECOVERY 

Probe alarms P1” and “P2” start some seconds after the fault in the related probe; they automatically 

stop some seconds after the probe restarts normal operation. Check connections before replacing the 

probe. Temperature alarms “HA” and “LA” automatically stop as soon as the temperature returns to 

normal values. 

Alarms “EA” and “CA” (with iF=bA) recover as soon as the digital input is disabled. 

13. TECHNICAL 

DATA 

Housing: self extinguishing ABS. 

Case: frontal 32x74 mm; depth 60mm; 

Mounting: panel mounting in a 71x29mm panel cut-out 

Содержание OWZA

Страница 1: ...a Dimensions 2 3 General Information 4 Installation 5 6 Refrigeration Piping 7 Plumbing 8 Electrical Connections 9 Air Flow Defrost Temp Control 10 Use Maintenance 11 Parts Ordering 12 Appendix A Domestic Wiring Diagrams Appendix B Export Wiring Diagrams Appendix C Controller Information Appendix D User Set Points ...

Страница 2: ...ii ...

Страница 3: ...ning messages will inform you of what the potential hazard is how to reduce the risk of death injury or damage and what may happen if the instructions are not properly followed D A N G E R DANGER indicates an immediate threat of death or serious injury if all instructions are not followed care fully W A R N I N G WARNING indicates a possible threat of death or seri ous injury if all instructions a...

Страница 4: ...Outlet psig Superheat Set Point bulb Fo Discharge Air Fo Return Air Fo Discharge Air Velocity 5 FPM OWZA 8 med temp 9 3 60 8 6 8 25 7 33 3 200 OWZA 8 low temp 13 5 16 3 6 8 17 3 200 5 Average discharge air velocity at peak of defrost System Requirements Model Volts Phase Hz Plug Style Cord Length OWZA 8 230 1 60 L14 30P 10 1 For export cases a NEMA L6 30 electrical plug is used Condensing Unit Dat...

Страница 5: ...m 96 in 243 8 cm 8 CASE 1 1 2 in 3 8 cm 42 5 8 in 108 2 cm C L 43 in 109 2 cm 13 1 8 in 33 3 cm 8 7 8 in 22 6 cm 33 11 16 in 85 6 cm 7 7 8 in 20 0 cm 29 5 8 in 75 3 cm 43 1 4 in 109 9 cm 42 9 16 in 108 1 cm 51 5 16 in 130 3 cm 38 1 2 in 97 8 cm 12 7 8 in 32 7 cm COIL PLENUM 6 THERMOPANE GLASS FRONT 3 ...

Страница 6: ...expect peak performance attractive fits and finish and long case life We are always interested in your suggestions for improvements e g case design technical documents etc Please feel free to contact our Marketing Services group at the toll free number listed below Thank you for choosing Hill PHOENIX and we wish you the very best in outstanding food merchandising HILL PHOENIX 1925 Ruffin Mill Rd C...

Страница 7: ... cases 2 Using chalk lines or a laser transit mark the floor where the cases are to be located for the entire lineup The lines should coincide with the outside edges of the base frame 3 Leveling is necessary to ensure proper case alignment and to avoid potential damage Locate the highest point on the positioning line as a reference for determining the proper height of the shim pack levelers A lase...

Страница 8: ... through the air cooled condenser to aid heat transfer Dual Pressure Control A device that protects the compressor from low charge and high pressure Split Evaporator The component of the refrigeration system that absorbs heat from the air by boiling liquid refrigerant to vapor Evaporator Fans Fans that circulate air through the case and force air through the evaporator to aid heat transfer Filter ...

Страница 9: ...Fan Plenum 1 4 Access Valve Flow Direction Service Valve Compressor Condenser Fan Receiver Filter Drier Dual Pressure Control Condenser TVX TVX 1 4 Access Valve Condenser Compressor Service Valve Condenser Fan Service Valve Service Valve Receiver Flow Direction Filter Drier 7 ...

Страница 10: ...imply remove the front kick plate Should any future maintenance issues arise it is important to note the outlet is specially molded with PVC material and the P trap is constructed of PVC Care should be given to make certain that all connections are water tight and are sealed with appro priate PVC primer and PVC cement Be certain that the case is properly leveled to ensure proper drainage P TRAP DR...

Страница 11: ...erature preference low temperature operation only uses the left hand controller while medium temperature opera ELECTRICAL CONNECTIONS NEMA L6 30 PLUG TWIST LOCK BREAKER SWITCH MODEL OWZA tion utilizes on the right hand controller The case is turned ON OFF via an electric breaker that is located on the electrical junction box in the left hand side of the case behind the front kick plate NOTE Dixell...

Страница 12: ... on remov Electric defrost termination sensor bulb Electric defrost termination probe Temperature control sensor bulb Discharge air probe 1 DISCHARGE AIR 2 LOAD LIMIT 3 AIR CURTAIN 4 RETURN AIR ing the front kick plate and lower front panel see the trim out section of this manual on page 5 It is important to consult the control setting guidelines shown on page 2 before setting the defrost schedule...

Страница 13: ...or cleaning Failure to do so may result in serious injury or death CLEANING PROCEDURES A periodic cleaning schedule should be established to maintain proper sanitation insure maximum operating ef ficiency and avoid the corrosive action of food fluids on metal parts that are left on for long periods of time We recommend cleaning once a week To avoid shock hazard be sure all electrical power is turn...

Страница 14: ...s intended Length of the part if applicable Color of part if painted or color of polymer part Whether part is for left or right hand application Quantity Serial plate is located on the right hand side of the rear baffle inside the product area 3 If the parts are to be returned for credit ask the Parts Department to furnish you with a Return Material Authorization Number PARTS ORDERING 12 ...

Страница 15: ...APPENDIX A DOMESTIC WIRING DIAGRAM ...

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...APPENDIX B EXPORT WIRING DIAGRAM ...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ...APPENDIX C CONTROLLER INFORMATION ...

Страница 26: ...point if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point value again In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters Cy and Cn 5 DEFROST XR03CX Defrost is performed through a simple stop of the compressor Parameter id controls the int...

Страница 27: ...1 Thermostat probe display read only d2 Evaporator probe display read only Only XR03CX Pt Parameter code table rL Software release 8 DIGITAL INPUTS The free voltage digital input is programmable in different configurations by the iF parameter DOOR SWITCH iF do It signals the door status and the corresponding relay output status through the dC parameter no normal any change Fn Fan OFF CP Compressor...

Страница 28: ...99 C 99 F ot First probe calibration 9 9 9 9 C 18 18 F 0 0 P2 Second probe presence Only XR04CX n Y y oE Second probe calibration Only XR04CX 9 9 9 9 C 18 18 F 0 0 od Outputs activation delay at start up 0 99 min 0 AC Anti short cycle delay 0 50 min 1 Cy Compressor ON time faulty probe 0 99 min 15 Cn Compressor OFF time faulty probe 0 99 min 30 CH Kind of Action Only XR03CX cL Ht cL DISPLAY CF Mea...

Страница 29: ...APPENDIX D USER SET POINTS ...

Страница 30: ......

Страница 31: ...sales tax or upgrading 5 When the operation is impaired due to improper installation 6 When installation and startup forms are not properly complete or returned within two weeks after startup THIS PLAN DOES NOT COVER CONSEQUENTIAL DAMAGES Manufacturer shall not be liable under any circumstanc es for any consequential damages including loss of profit additional labor cost loss of refrigerant or foo...

Страница 32: ...wing must be performed PRIOR to cleaning To avoid electrical shock be sure all electric power is turned off before cleaning In some installations more than one switch may have to be turned off to complete ly de energize the case Do not spray cleaning solution or water directly on fan motors or any electrical connections All lighting receptacles must be dried off prior to inser tion and re energizi...

Отзывы: