13
Enforcer V10 Programming Guide
Wireless Arming Station functions are programmed in the ‘ASSIGN KEYPADS/READERS menu and are mapped as:
Arming Station #1 : Address [4]
Arming Station #2 : Address [5]
Arming Station #3 : Address [6]
Arming Station #4 : Address [7]
CHANGE INPUTS
A total of 66 inputs can be programmed on the Enforcer system. All inputs are unused by default. To save any
programming the Engineer menu must be exited.
Input Types
See Appendix B for all input type options.
Most commonly used input types:
[06] Intruder. [07] Final Exit. [08] Entry Route. [13] Day Alarm.
Please note
1. If an alarm is triggered from an Entry Route input, it will store for 2 seconds before an alarm is
activated. If a Final Exit input is triggered within this time, the system will select entry time, rather than
an intruder alarm.
2. Inputs may be automatically omitted at the time of reinstatement, which is at the end of confirmation
time. This is irrelevant of whether the input has the attribute ‘Ommitable’ set to ‘Yes’ or ‘No’
Input Areas
The Enforcer supports up to four areas and can be used as follows:
Area A:
All Factory
Area B:
Reception Only
Area C:
Offices Only
Area D:
Factory Floor Only
Input Area (Any/All)
In some installations a ‘common’ area may be required. A common area is an area that only sets when other specific
areas become set. Example: An entry and exit reception area in a building may only need to be set if both the offices
and warehouse are set. If the office in Area A is set, but the warehouse in Area B is still occupied, then the reception
would still need to be inactive so people would be able to leave the premises via the entry / exit reception route.
One input can be allocated to one or more areas. In this example the inputs located in the reception area will be
programmed so that the reception inputs will be in Area A and Area B, so these inputs must have the Input Areas
set as ‘ALL’ programmed.
Area A: Office - Inputs = 3, 4, 5
Area B: Warehouse - Inputs = 6, 7, 8
Reception inputs – 1 and 2 are programmed into both Areas A and B, with both inputs configured as ‘ALL’. The
Reception Area inputs will now only become active if both Area A and Area B are both set.
Please note: All inputs in a common area must be programmed as ‘Entry Route’ or ‘Final Exit’.
Содержание Pyronix Enforcer V10
Страница 1: ...Enforcer Extended Programming Guide Alarm Panel Time 10 09 c Version 01 ...
Страница 56: ......