INSTALLATION GUIDE
hidglobal.com
An ASSA ABLOY Group brand
© 2012 - 2018 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID GLOBAL, HID, the HID Brick logo, the Chain Design, and PIVCLASS are trademarks or registered
trademarks of HID Global, ASSA ABLOY AB, or its affiliate(s) in the U.S. and other countries and may not be used without permission. All other trademarks, service marks, and
product or service names are trademarks or registered trademarks of their respective owners.
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output
are fictitious. Specifications are subject to change without notice.
pivCLASS
R10-H, RP10-H, R40-H, RP40-H, RK40-H, RPK40-H, RKCL40-P,
RPKCL40-P, RKCLB40-P
Wiegand and OSDP Protocol
Installation
1
Mounting
Attach Backplate and Mounting Gasket to Junction Box.
Contactless Models Contact Models
1
Communication protocols other than Wiegand
or Clock & Data require an additional hardware
module which increases current by 30 mA.
PRODUCT
BASE PART
NUMBER
INPUT VOLTAGE
(VDC)
CURRENT
1
OPERATING
TEMPERATURE
CABLE LENGTH
5
UL REF
NUMBER
Standby
AVG
2
Maximum
AVG
3
PEAK
4
R10-H
900N
5-16VDC
12VDC for RS-485
60mA
100mA
200mA
-30° to 150° F
(-35° to 65° C)
Communication Lines
Wiegand
= 500 ft - 22 AWG
(152 m)
300 ft - 24 AWG
(91 m)
RS-485
= Max. bus length
4000 ft - 24 AWG
(1,219 m)
Max length between nodes:
1,640 ft - 24 AWG (500m)
R10E
x
1
x
2
x
3
RP10-H
900P
75mA
RP10E
x
1
x
2
x
3
R40-H
920N
65mA
110mA
R40E
x
1
x
2
x
3
RP40-H
920P
85mA
RP40E
x
1
x
2
x
3
RK40-H
921N
85mA
125mA
220mA
RK40E
x
1
x
2
x
3
RPK40-H
921P
95mA
RPK40E
x
1
x
2
x
3
RKCL40-P
923N
12VDC
150mA
185mA
250mA
-4° to 122° F
(-20° to 50° C)
RKCL40E
x
1
x
2
x
3
RPKCL40-P
923P
RPKCL40E
x
1
x
2
x
3
UL Reference Number Deciphering
x
1
Reader Colors:
K = Black
x
2
Wiring:
N = Pigtail
T = Terminal
x
3
Communications: N = No Module,
R = RS-485 (OSDP)
2
Standby AVG - RMS current draw without a card in the RF field.
3
Maximum AVG - RMS current draw during continuous PIV card reads.
Not evaluated by UL.
4
Peak - highest instantaneous current draw during RF communication.
5
Wiegand Cable Lengths: 100 ft (30.5 m) 22 AWG @ 5 - 6.4VDC
500 ft (152 m) 22 AWG @ 6.5 - 16VDC
Junction box not included.
Mounting holes for US single-
gang electrical boxes.
Install gasket for RK40 and
RPK40 models.
Mounting holes for US
double-gang electrical
boxes.
Reverse Configuration
Rotating the backplate
180° allows for placing the Contact reader on left
and the Keypad reader on right.
See Section B Reconfigure Reader Assembly for
instructions, before proceeding to Section 2.