Parameters of heater E and heater P

The  first parameter  shown  is activation/deactivation  of  connected  electric  heater (below,  to  the  left). YES  will  start  to  pulsate
after pressing OK. The setting can be changed to NO using an arrow. Press OK to approve, or ESC to cancel without saving
(the parameter returns to initial value). When no value pulsates, it is possible to move using arrows to another parameter, which
allows setting the temperature of heating with a heater while heat pump is on (below, to the right). The heater will be heating up
the tank with heat pump to that value, provided that heat pump independent operation priority is not activated. It is important to
ensure  that  this temperature  setting  is  not  higher  than  the temperature,  to  which heat  pump keeps  heating - otherwise heat
pump will  never  be  able  to  work,  because heater will  keep  the  required  water parameter. The  heater works  at  constant
hysteresis of 2°C (drop of water temperature, which restarts heat pump). This solution is frequently called the PARTY mode - if
more people than usually are to use utility water, it is worth activating simultaneous operation of heater or other heating source,
so as to ensure the comfort of suitable hot water volume.

Another parameter in heater settings is the required HUW temp., while heat pump is off (below, to the left). If heat pump enters
an alarm mode (conditions, which may disturb correct operation, or there is too low min. temperature of air supplied to the heat
pump), or it is switched off manually from the controller level, then heater may keep heating up the tank to higher temperatures,
because  in  this  case  heating  costs  do  not  depend  on  the temperature  of  water  being  heated  up. If  we  have  a  system  with  a
suspended or solid fuel fired boiler and we set heating priority to either of them - the heater will not switch on.

Another parameter is heater stoppage while heat pump operates. At the moment, when the value is set to YES, the heater will
not activate if heat pump operates or is waiting for restart of work (that is drop of temperature in the tank, which will restart the
heat pump).

The last parameter in heater settings is its stoppage while
boiler  D  operates. If  we  have  selected  a  diagram,  which
supports  suspended  (automatic)  boiler,  then  automatic
boiler  will  switch  on  as  the  first  unit  at  the  moment  when
heat  pump  cannot  work  (alarm  states, low COP,  or  the
pump is switched off manually from the controller).

Circulating pump parameters

Circulating  pump  operation depends on  two  preset parameters. The  first  is minimum circulating  pump  activation temperature
depending  on temperature at  the  tank  top (temperature  sensor T2). This  value  may  be  set  between 20 and 60°C.  Factory
setting is 35°C.

The second parameter involves setting of circulating pump operation mode. We have the choice of continuous operation mode -
circulating pump will work all the time according to time settings, or intermittent operation mode - in this case circulating pump
will be working in the regime 5 min. operation/10 min. stop, according to time settings.

Содержание PCWU 2.5kW

Страница 1: ...the most complex controller in the HUW heat pump market in Poland possibility to control and analyse operation statistics in EKONTROL pL a separate LAN module is needed access to thoroughly metered t...

Страница 2: ...Secure the unit COOLING RELATED failures Do not put your fingers inside the unit housing if it is connected to power supply There is a hazard of burning electric shock or cutting your fingers In part...

Страница 3: ...tory element of power supply If user observes any alarming symptoms e g noise or odour indicating abnormal equipment operation it is required to cut off power supply and consult authorised service cen...

Страница 4: ...between 6 5 and 9 5 conductivity under 2500 uS cm at 20 C ammonia under 0 5 mg l nitrates under 50 mg l chlorides content under 250 mg l copper under 2 mg l permissible value provided that it does no...

Страница 5: ...nd or service works one must satisfy important for environment requirements regarding recovery reuse and utilisation of materials In particular keep to the following standards concerning cooling mediu...

Страница 6: ...nt drops with decreasing air temperature and due to physical parameters of the medium in compressor system it becomes impossible to receive heat for certain low temperature of the source The same prob...

Страница 7: ...the compressor in heat pump system 1 Increases cooling medium pressure and temperature to allow efficient heat transfer in heat pump condenser 2 The compressor has considerable impact on the efficien...

Страница 8: ...NUOUS factory setting INTERM Solid fuel fired boiler B shown in diagrams no 5 7 9 Max boiler pump deactivation temperature 10 85 C factory setting 65 C Min boiler pump activation temperature 30 60 C f...

Страница 9: ...eat pump Press arrow down to move to internal diagram of heat pump Press arrow up or wait few seconds to return to the main screen Press this button to enter individual settings menu A list of setting...

Страница 10: ...llation and service instructions in the controller map Operation parameters settings After approval we may enter parameter settings screen view below on the left side Scrolling arrow down we may also...

Страница 11: ...olid fuel fired boiler is working heat pump will not activate when the option of heating with solid fuel fired boiler is set Parameters of accessory equipment The second item in the list of Parameter...

Страница 12: ...is too low min temperature of air supplied to the heat pump or it is switched off manually from the controller level then heater may keep heating up the tank to higher temperatures because in this ca...

Страница 13: ...list is the priority of heating with solid fuel fired boiler below to the right If YES value is set and conditions required for boiler pump activation are fulfilled all other pieces of equipment opera...

Страница 14: ...wish to activate the Anti Legionella function It will start on midnight Sunday Monday and keep running no longer than until 6 a m on Monday The superheating function will end earlier if temperature of...

Страница 15: ...ng of inactivity time until backlight dimming the screen will get dimmed if user does not touch any keys for preset time Sounds Sound parameters allow setting keyboard sound if set to YES we will hear...

Страница 16: ...Mediterranean countries however occasionally it appears in Poland as well An effective method to destroy Legionella bacteria is periodic tank superheating to water temperature reaching 70 C At this te...

Страница 17: ...ipment operation statistics Another important advantage of the unit remote control is round the clock observation by the system and prompt information concerning alarms in the installation A network L...

Страница 18: ...ng medium during condensation As a result of this the COP coefficient value depends not only on ambient temperature but on air humidity as well 4 Is it possible to connect the PCWU 2 5kW heat pump to...

Страница 19: ...are applicable A It is prohibited to repair the unit without contact with HEWALEX service In case of incorrect equipment operation report failures by phone 32 214 17 10 or e mail serwis hewalex pl De...

Страница 20: ...NO 11 Is the system provided with tested safety valve max 7 bar per HUW tank and does water flow after depressing the valve handle YES NO 12 Are suitable valves installed which would according to the...

Страница 21: ...and organisational conditions which should be met by computer equipment and systems used for personal data processing O J Poland No 100 item 1024 Your personal information is kept in adequately secur...

Отзывы: