If the controller has been switched into regular operation mode, you can access the main controller MENU by pressing the 

 key. Navigation keys 

 or 

 serve the 

purpose of selecting some options. Then you can enter the selected option by pressing the 

key.  

In order to edit controller parameters use navigation keys 

 or 

 to select a given parameter and press 

 to confirm parameter editing (the values will flash). Then use 

navigation keys 

 or 

 to change the required value and press 

in order to accept it. By pressing 

 you will return to the previous screen. 

 

ATTENTION  !  The  operation  scheme  presented  applies  for  almost  all  the  controller  options.  After  any  changes  of  the  scheme  or  parameters  in  the  controller,  

it is recommended to switch it off and then on again with ON/OFF button.  

4.

 

Installation schemes (scheme selection) 

This option makes it possible to select an appropriate installation scheme necessary for correct operation of the controller. In order to select an installation scheme: 
Press the following key combination: starting point - MAIN SCREEN: enter into the MENU 

, Select scheme 

, Select an appropriate scheme 

 or 

, confirm 

 (a 

continuous sound signal), return to the main screen 

 

ATTENTION ! Broken lines in all  the installation schemes refer to temperature sensors which can be connected to the controller, but are not required for its proper 
operation for the selected scheme. Connection of titanium anode is marked on the diagrams (applies to the 

GH26-P09A

 controller only) 

4.1  Tap water heating system - controlling solar collector pump – scheme no 1  

Controlling the P collector pump - Regulation of collectors’ pump – scheme no 1 

 

The P collector pump will be switched on if the T1 solar collector gets hotter by the “

Temp. T1&T2 difference - pump ON”

 value than the T2 temperature in the lower part of the 

heater. If the heater’s temperature reaches the set value of “

MaxTemp. T2 OFF collector’s pump”,

 the P pump will be switched off. Additionally, in order to avoid unstable pump 

operation when the temperature on the sensor changes, switch on and switch off hysteresis has been used.  

Controlling the P collector pump - Regulation of collector’s pump - YES 
Applies to the electronic pumps controlled with PWM signal only. When a normal circulation pump is connected, the pump will operate on an on/off basis although the 
control is enabled. 

The P collector pump will be switched on and off in the case described above but the collector changes the rotational speed of the P collector pump depending on the difference in temperature (T1-
T2) and the set parameter “

Temp. T1&T2 difference - pump ON”

. This option makes it possible to effectively collect energy from the collectors with variable solar radiation. 

 

Fig. 3. Schematic and electrical diagram of installation no 1.

 

4.2  Tap water heating system - controlling solar collector pump and a circulation pump - scheme no 2 

Controlling the P collector pump

 

Similarly as in scheme no 1 - description in point 4.1. 

 

Controlling the C circulation pump 

 

The C circulation pump is only switched on in the time programmed by the user in the “

Time program  C

” setting. The C pump can work in two modes set by the user, that is, continuous or 

discontinuous (“

Time of switching on the circulating pump”

 and

 “Time of switching off the circulating pump”) 

in the 

“Circulation param.”

 setting.  

Moreover, C pump operation is limited by T4 temperature in the upper part of the heater; if the T4 temperature is lower than the set value of “

Min. temp. T4 switching on the circulation pump”  

in 

the 

“Circulation param.”

 setting. C circulating pump operation mode can be selected in the “

Parameter settings

” menu.  

 

Fig. 4. Schematic and electrical diagram of installation no 2. 

Содержание GH26-P09

Страница 1: ...USER MANUAL OF AN INDEPENDENT REGULATION BLOCK GH26 P09 GH26 P09A Controller of a solar collector system applicable from version 0 1a ...

Страница 2: ...t Maximum current intensity 2A O2 Transmitter output no voltage output relay Maximum current intensity 2A S1 S2 NC normally closed S2 S3 NO normally open May operate as voltage output applying voltage to S2 will result in changeover voltage output O3 230V output relay Maximum current intensity 2A O4 230V output bridging inside the controller It is allowed to bridge outside with a terminal of a rel...

Страница 3: ...ch on for the blanking period set Screen blanking aims at limiting energy consumption Connect the electrical plug to the socket equipped with a protective terminal and protected with RCD It is forbidden to install pump units in close vicinity of open flames high temperatures and storage of flammable materials 3 2 Controller keyboard description The controller has a touch keyboard with 7 keys which...

Страница 4: ...erence pump ON value than the T2 temperature in the lower part of the heater If the heater s temperature reaches the set value of MaxTemp T2 OFF collector s pump the P pump will be switched off Additionally in order to avoid unstable pump operation when the temperature on the sensor changes switch on and switch off hysteresis has been used Controlling the P collector pump Regulation of collector s...

Страница 5: ...to boiler switch on and switch off temperatures An example of a table of resistances depending on the manufacturer of a given boiler has been presented in the table below ATTENTION The original tap water temperature sensor remains disconnected and replaced by 2 wire cable from the controller GH26 Table 2 Resistor resistance for selected boiler manufacturers Fig 5 Schematic and electrical diagram o...

Страница 6: ...larly as in scheme no 1 description in point 4 1 Controlling the C circulation pump Similarly as in scheme no 2 description in point 4 2 Controlling K boiler pump The K boiler pump will be switched on if the T5 temperature at the boiler outlet gets higher by the Temperature difference ON add pump valve value than the T4 temperature in the upper part of the heater The pump will remain switched on u...

Страница 7: ...he set allowable value of Max temp T4 OFF heat source Fig 9 Schematic and electrical diagram of installation no 7 4 8 Double heater system makes it possible to provide additional solar energy heating for the boiler heater with the use of a circulation return scheme no 8 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the C circulation pump Similarl...

Страница 8: ...be found in the Parameter settings menu The C pool pump is always switched on when pool water is heated with solar collectors ATTENTION If the C pool pump is switched offwhen the solar collector pump is working and the U valve is set to the pool may damage the piping system of the pool circuit In order to protect the exchanger against lack of heat collection by the pool pump a T4 sensor should be ...

Страница 9: ... scheme Controlling the C circulation pump Similarly as in scheme no 2 description in point 4 2 Fig 14 Schematic and electrical diagram of installation no 12 4 13 The system with a buffer tank used for cooperation with a central heating installation scheme no 13 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the C boiler pump The C boiler pump is ...

Страница 10: ...ers have been used in the diagram Max temp T4 OFF heat source for heating with the use of an electrical boiler or a liquid fuel boiler and Max water temperature from boiler C for heating with the use of a fireplace or a solid fuel boiler for heating water in the upper part of the combi heater measured by the T4 sensor Fig 16 Schematic and electrical diagram of installation no 14 4 15 Tap water hea...

Страница 11: ...ure in the A heater reaches Max temp T4 OFF heat source When the T4 temperature exceeds the set value the controller switches the valve back into the B heater direction and switches the P collector pump off When water is being heated in the A heater once an hour for 5 minutes the controller forces P collector pump switch off in order to check the conditions for heating the B heater and switch heat...

Страница 12: ... Fig 20 Schematic and electrical diagram of installation no 18 4 19 Tap water heating system controlling solar collector pump mixing pump and system of solar energy heating for the boiler heater with the use of a circulation return scheme no 19 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the K mixing pump Similarly as in scheme no 7 description...

Страница 13: ...option named Parameters setting with enter the Parameter settings menu with get to the option named Time program K with enter the option named Time program K with select time with or accept operation time white square or cancel operation time with accept and return a continuous sound with return to the main screen with ATTENTION Hourly setting of K are identical to those of the Time program C 5 5 ...

Страница 14: ...er the flow value that results from the number of collectors in the system into the edition field Next set the required flow rate value in such a way that the Current value corresponds to the calculated value entered before The required flow can be obtained by changing the rotational speed in option Collector pump ATTENTION Leaving the field unchanged or entering wrong value does not affect the op...

Страница 15: ... water heater by switching the solar collector pumps on in a specific time interval starting from 0 00 to the time set in the Stop cooling at h parameter The cooling option will be active if cooling is on Night cooling Yes and the T2 temperature in the heater is higher or equal to the set Start cooling temperature Cooling will remain active until the heater gets cooler to the Stop cooling temperat...

Страница 16: ...ption of its functions has been included in point 4 for selected external devices only 10 85 C 50 C Max water temperature from boiler C A parameter only used in schemes no 14 and 18 It defines the maximum temperature of water measured by the T4 sensor for the operation of C pump cooperating with the water circuit of fireplace or solid fuel boiler 10 85 C 60 C Regulation of collector s pump P solar...

Страница 17: ...the circulating pump Time of switching off the C circulation pump in a set cyclic mode according to the preset working times 1 59min 10min Table 3 Controller parameter description 13 Error alarms and controller notifications Temperature sensor error check sensors for visual condition or for proper connection to the controller The controller checks whether temperature sensors have been connected If...

Страница 18: ...ing with the operation of the system and the controller Lack of required heater protection by titanium anode applies to the GH26 P09A controller only The controller is used as a power supply for the titanium anode placed in the water heater for protection of the latter against corrosion The lack of anode incorrect connection or damage to the anode circuit will switch on the sound alarm and display...

Отзывы: