background image

18 

 
 

 

II step

 – (When the 

T1-T2 > 50°C

 or 

T3-T2 > 50°C

 condition is fulfilled for another 10 minutes), the controller switches off the specific solar collector pump and generates a 

sound signal and displays the following message: 

LACK OF

 

FLOW, FAILURE OF THE P OR K PUMP, AIR-LOCKED SYSTEM, BLOCKED FLOW

. By pressing the key for 

acceptance 

 the user will switch on the solar collector pump again. If the above-mentioned conditions continue, the alarm will be cyclically repeated. 

 

ATTENTION! The LACK OF FLOW... message is off and the circulation pumps get unlocked automatically when the T1 or T3 temperature (scheme no 

15 and 16) on solar 

collectors falls below 50°C. 

Lack of required pressure of the heat transfer fluid in the installation 

The controller is equipped with a pressure control of the heat transfer fluid (the function Pressure switch enabled – see 

Control parameters

). 

The pressure drop below 1.5 bar for 30 minutes is indicated by the following message: 

LACK OF REQUIRED PRESSURE. 

By pressing the 

 

key for acceptance the user will 

return to the main screen of the controller. If the lack of pressure continues, the alarm will be cyclically repeated. The removal of the alarm consists in completing the installation with 
the heat transfer fluid to the pressure of 

2 bar

ATTENTION! Lack of required pressure will only display a message without interfering with the operation of the system and the controller. 

Lack of required heater protection by titanium anode (applies to the GH26-P09A controller only). 

The controller is used as a power supply for the titanium anode placed in the water heater for protection of the latter against corrosion.  

The  lack  of  anode,  incorrect  connection  or  damage  to  the  anode  circuit  will  switch  on  the  sound  alarm  and  display  the  message. 

NO  SUFFICIENT  TANK  PROTECTION

 

BY 

TITANIUM ANODE

. The controller distinguishes the error type and displays the above-mentioned message with the relevant failure code: 

No code  

– information on the occurrence of a temporary failure   

(1)

 

– open circuit of titanium anode, 

(2)

 

– short circuit of titanium anode, 

(3)

 

– controller error. 

By pressing the 

 

key for acceptance the user will switch off the controller. If the failure continues, the alarm will be cyclically repeated. 

ATTENTION! The lack of proper protection of the water heater by the anode 

may cause corrosion and damage of the heater.

 

14.

 

Information on marking and collecting used electrical and electronic equipment  

 

 A  symbol  found  on  the  product  or  its  packaging  points  to  the  necessity  of  separate  collection  of  used  electronic 

 equipment. This means that the product must not be thrown away together with other household waste. Correct disposal of old and used 
electrical equipment may help to avoid potential damage to the environment and human health.  

 A user who should give the used equipment to a collector should be responsible for separate collection of used electronic equipment.  

 

Содержание GH26-P09

Страница 1: ...USER MANUAL OF AN INDEPENDENT REGULATION BLOCK GH26 P09 GH26 P09A Controller of a solar collector system applicable from version 0 1a ...

Страница 2: ...t Maximum current intensity 2A O2 Transmitter output no voltage output relay Maximum current intensity 2A S1 S2 NC normally closed S2 S3 NO normally open May operate as voltage output applying voltage to S2 will result in changeover voltage output O3 230V output relay Maximum current intensity 2A O4 230V output bridging inside the controller It is allowed to bridge outside with a terminal of a rel...

Страница 3: ...ch on for the blanking period set Screen blanking aims at limiting energy consumption Connect the electrical plug to the socket equipped with a protective terminal and protected with RCD It is forbidden to install pump units in close vicinity of open flames high temperatures and storage of flammable materials 3 2 Controller keyboard description The controller has a touch keyboard with 7 keys which...

Страница 4: ...erence pump ON value than the T2 temperature in the lower part of the heater If the heater s temperature reaches the set value of MaxTemp T2 OFF collector s pump the P pump will be switched off Additionally in order to avoid unstable pump operation when the temperature on the sensor changes switch on and switch off hysteresis has been used Controlling the P collector pump Regulation of collector s...

Страница 5: ...to boiler switch on and switch off temperatures An example of a table of resistances depending on the manufacturer of a given boiler has been presented in the table below ATTENTION The original tap water temperature sensor remains disconnected and replaced by 2 wire cable from the controller GH26 Table 2 Resistor resistance for selected boiler manufacturers Fig 5 Schematic and electrical diagram o...

Страница 6: ...larly as in scheme no 1 description in point 4 1 Controlling the C circulation pump Similarly as in scheme no 2 description in point 4 2 Controlling K boiler pump The K boiler pump will be switched on if the T5 temperature at the boiler outlet gets higher by the Temperature difference ON add pump valve value than the T4 temperature in the upper part of the heater The pump will remain switched on u...

Страница 7: ...he set allowable value of Max temp T4 OFF heat source Fig 9 Schematic and electrical diagram of installation no 7 4 8 Double heater system makes it possible to provide additional solar energy heating for the boiler heater with the use of a circulation return scheme no 8 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the C circulation pump Similarl...

Страница 8: ...be found in the Parameter settings menu The C pool pump is always switched on when pool water is heated with solar collectors ATTENTION If the C pool pump is switched offwhen the solar collector pump is working and the U valve is set to the pool may damage the piping system of the pool circuit In order to protect the exchanger against lack of heat collection by the pool pump a T4 sensor should be ...

Страница 9: ... scheme Controlling the C circulation pump Similarly as in scheme no 2 description in point 4 2 Fig 14 Schematic and electrical diagram of installation no 12 4 13 The system with a buffer tank used for cooperation with a central heating installation scheme no 13 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the C boiler pump The C boiler pump is ...

Страница 10: ...ers have been used in the diagram Max temp T4 OFF heat source for heating with the use of an electrical boiler or a liquid fuel boiler and Max water temperature from boiler C for heating with the use of a fireplace or a solid fuel boiler for heating water in the upper part of the combi heater measured by the T4 sensor Fig 16 Schematic and electrical diagram of installation no 14 4 15 Tap water hea...

Страница 11: ...ure in the A heater reaches Max temp T4 OFF heat source When the T4 temperature exceeds the set value the controller switches the valve back into the B heater direction and switches the P collector pump off When water is being heated in the A heater once an hour for 5 minutes the controller forces P collector pump switch off in order to check the conditions for heating the B heater and switch heat...

Страница 12: ... Fig 20 Schematic and electrical diagram of installation no 18 4 19 Tap water heating system controlling solar collector pump mixing pump and system of solar energy heating for the boiler heater with the use of a circulation return scheme no 19 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the K mixing pump Similarly as in scheme no 7 description...

Страница 13: ...option named Parameters setting with enter the Parameter settings menu with get to the option named Time program K with enter the option named Time program K with select time with or accept operation time white square or cancel operation time with accept and return a continuous sound with return to the main screen with ATTENTION Hourly setting of K are identical to those of the Time program C 5 5 ...

Страница 14: ...er the flow value that results from the number of collectors in the system into the edition field Next set the required flow rate value in such a way that the Current value corresponds to the calculated value entered before The required flow can be obtained by changing the rotational speed in option Collector pump ATTENTION Leaving the field unchanged or entering wrong value does not affect the op...

Страница 15: ... water heater by switching the solar collector pumps on in a specific time interval starting from 0 00 to the time set in the Stop cooling at h parameter The cooling option will be active if cooling is on Night cooling Yes and the T2 temperature in the heater is higher or equal to the set Start cooling temperature Cooling will remain active until the heater gets cooler to the Stop cooling temperat...

Страница 16: ...ption of its functions has been included in point 4 for selected external devices only 10 85 C 50 C Max water temperature from boiler C A parameter only used in schemes no 14 and 18 It defines the maximum temperature of water measured by the T4 sensor for the operation of C pump cooperating with the water circuit of fireplace or solid fuel boiler 10 85 C 60 C Regulation of collector s pump P solar...

Страница 17: ...the circulating pump Time of switching off the C circulation pump in a set cyclic mode according to the preset working times 1 59min 10min Table 3 Controller parameter description 13 Error alarms and controller notifications Temperature sensor error check sensors for visual condition or for proper connection to the controller The controller checks whether temperature sensors have been connected If...

Страница 18: ...ing with the operation of the system and the controller Lack of required heater protection by titanium anode applies to the GH26 P09A controller only The controller is used as a power supply for the titanium anode placed in the water heater for protection of the latter against corrosion The lack of anode incorrect connection or damage to the anode circuit will switch on the sound alarm and display...

Отзывы: