16 

 
 

In the 

Energy Statistics 

menu there is also a total energy counter. This counter sums all the produced energy.  

Statistics and total counter can be cleared any time. The clearing option can be found in the 

Energy Statistics

 menu and is available separately for the total counter and the statistics.  

In order to view or clear energy counters select the "

Energy Statistics

” option. In order to do this: 

Press the following key combination: starting point - MAIN SCREEN: enter the 

MENU

 with 

, get to the option named 

Energy Statistics 

with 

 

 

 

 

, enter the 

Energy Statistics

 option

 

with 

, select the option with 

 or 

, enter the options with 

, select time intervals (day, week, month, year) with 

 or 

, accept the interval 

with 

 which results in displaying a graph, return to the main screen with 

 

 

 

ATTENTION ! A change in date may result in distorting the chronology of recorded events or display of incorrect energy values. For the statistics counters to work 

correctly it is necessary to clear them after each date change. It is not necessary to clear the total energy yield counter after a date change

.

 

10.

 

Vacation function 

Vacation function switches on the option of  

night

 

cooling

 and 

collector overheating protection

. Additionally, this option allows disabling additional heating devices 

connected to the controller in the active time period declared by the user – 

applies to scheme no. 3, 4, 5, 14.

 Active vacation option is indicated by the display of the 

screen 

HOLIDAY

 alternating with the scheme on the main screen of the controller.  

11.

 

Software update 

This option makes it possible to update the software using an appropriate cable and the application installed on the computer. In order to do this, use port RS485 in the controller. 

12.

 

Description of control parameters (parameter settings) 

Parameter 

Description 

Scope 

Factory 

settings 

Solar  

collector 

type

 

The parameter makes it possible to select solar collector type (flat or tube).  
If a tube collector is selected, then between 8.00

17.00, every full hour, the collector pump is switched on for a minute. Because 

of the fact that temperature sensors are located at the bottom of the collector, in case of extremely low ambient temperatures the 
temperature  inside  the  collector  might  deviate  from  the  temperature  indicated  by  the  sensor.  If  the  T1  sensor  reaches  a 
temperature required for system operation, the P pump will continue operating 

Flat / Tube 

Flat

 

Temp. T1&T2 difference 

– pump ON 

 

This parameter defines the conditions for switching the collector pump on and off. If the T1 temperature is higher than the sum of 

the “

Temp. T1&T2 difference – pump ON ”

 parameter and the T2 temperature of water in the heater, the collector pump will be 

switched on. 

 

4

15

6

C

 

Temperature difference 

ON  

add. pump, valve

 

This  parameter is  used  for  controlling  advanced  systems  and  therefore  its  description  has  been  included  in  point  7  only  for 
selected external devices.  

2

15

5

C

 

MaxTemp. T2  

OFF  

collector’s pump

 

This parameter is related to the T2 sensor located at the heater bottom. It defines the maximum allowable temperature of water 
in the heater measured by the T2 sensor up to which solar collector pumps keep operating.  

10

85

65

C

 

Min. temp. T5  

ON  

Boiler pump

 

A parameter used in schemes 6, 14 and 18. It defines the minimum boiler temperature (T5 sensor) for switching boiler pump on.  

10

85

41

C

 

Max. temp. T4  

OFF  

heat source

 

Maximum  temperature  for  switching  an  additional  heat  source,  such  as  boiler,  electrical  heater  or  a  heat  pump,  OFF.  This 

parameter  is  used  in  advanced  schemes.  Because  of  the  variety of  roles  it  plays  in  specific  schemes,  the  description  of  its 
functions has been included in point 4 for selected external devices only.  

10

85

50

C

 

Max. water temperature 

from boiler C

 

A parameter only used in schemes no 14 and 18. It defines the maximum temperature of water measured by the T4 sensor for 
the operation of C pump cooperating with the water circuit of fireplace or solid-fuel boiler.  

10

85

60

C

 

Regulation of collector’s  

pump

 

P solar collector pump circulation adjustment. Switching this option on results in smooth changes the pump’s rotational speed. 

When the option is switched off, the controller only distinguishes between collector pump being switched on or off. 

Yes / No 

Yes

 

Coll. power  

OFF  

boiler, heater, heat pump

 

A parameter used in installation schemes 3, 4, 5 and 14. The controller forces additional heating devices (boiler, heater, heat 
pump) to switch off once the set collector power parameter is exceeded.  
In order to eliminate too frequent on/off cycles of the devices during transient insolation conditions, the controller accounts for a 5 
minute delay in switch off and switch on of heating devices.  

ATTENTION!  Setting the value of 9900W  m

akes  the operation  of  heating  devices  independent  from  the operation  of  solar 

collectors.

 

 

100

9900W 

1500W

 

Overheat protection of 

collectors

 

This parameter defines switch on and switch off of the option protecting solar collectors from overheating.  
When switched on, P collector pump gets switched off once the collector temperature exceeds 110

C. If  the collector 

temperature falls below 99

C or once the T2 heater temperature “

MaxTemp. T2 OFF  overheat protection” 

 is exceeded

 

the P 

collector pump gets switched off. This function works even if the maximum water temperature 

MaxTemp. T2 OFF collector’s 

pump”

 in the heater is exceeded.

 

 

Yes / No 

No

 

MaxTemp. T2  

OFF  

overheat protection

 

The parameter defines maximum temperature of water in the heater up to which collector pumps keep working when the option 

Protection against collector overheating

” is active.  

60

80

80

C

 

Freezing protection of 

collectors ON 

The parameter is used in those countries where water serves as heat transfer fluid in solar collectors. 

 

This parameter defines switch on and switch off of the option protecting solar collectors from freezing. 
If this function is switched on, the P solar collector pump gets switched on once the temperature in the water heater as measured 
by the T2 sensor is higher than 7

C, and the temperature on collectors falls below the temperature set in the 

Heat transfer fluid

 

option. Once the temperature of water in the heater falls to 4

C or the temperature on collectors exceeds the temperature set in 

the 

Heat transfer fluid

 option, the solar collector pump switches off.

 

ATTENTION!  Original  heat  transfer  fluid(with  no  water  added)  does  not  freeze,  so  it  is  not  necessary  to  use  the 

"Protection against collector freezing” option

Unjustified activation of the function may result in cooling water in the heater.

 

Yes / No 

No

 

Selection of heating 

priority  

 

This parameter defines the selection of heating priority in schemes with two heat receivers (e.g.  pool).  
Selecting 

A > B

 results in setting priority heating to the pool or additional heater. If the conditions are not suitable for heating the 

pool or an additional heater, heating is switched to the solar heater. Selecting 

B > A

 results in setting priority heating to the solar 

heater. If the conditions are not suitable for the solar heater, heating is switched to the pool or an additional heater. 
Selecting 

B

 results in setting absolute heating priority of the solar heater. Heating will be directed to the pool or an additional 

heater only after reaching preset temperature of the solar heater. 

A and B letters are connected with three-way valve outlets or the name of heat receivers. 

 

B > A 

A > B 

B > A 

Содержание GH26-P09

Страница 1: ...USER MANUAL OF AN INDEPENDENT REGULATION BLOCK GH26 P09 GH26 P09A Controller of a solar collector system applicable from version 0 1a ...

Страница 2: ...t Maximum current intensity 2A O2 Transmitter output no voltage output relay Maximum current intensity 2A S1 S2 NC normally closed S2 S3 NO normally open May operate as voltage output applying voltage to S2 will result in changeover voltage output O3 230V output relay Maximum current intensity 2A O4 230V output bridging inside the controller It is allowed to bridge outside with a terminal of a rel...

Страница 3: ...ch on for the blanking period set Screen blanking aims at limiting energy consumption Connect the electrical plug to the socket equipped with a protective terminal and protected with RCD It is forbidden to install pump units in close vicinity of open flames high temperatures and storage of flammable materials 3 2 Controller keyboard description The controller has a touch keyboard with 7 keys which...

Страница 4: ...erence pump ON value than the T2 temperature in the lower part of the heater If the heater s temperature reaches the set value of MaxTemp T2 OFF collector s pump the P pump will be switched off Additionally in order to avoid unstable pump operation when the temperature on the sensor changes switch on and switch off hysteresis has been used Controlling the P collector pump Regulation of collector s...

Страница 5: ...to boiler switch on and switch off temperatures An example of a table of resistances depending on the manufacturer of a given boiler has been presented in the table below ATTENTION The original tap water temperature sensor remains disconnected and replaced by 2 wire cable from the controller GH26 Table 2 Resistor resistance for selected boiler manufacturers Fig 5 Schematic and electrical diagram o...

Страница 6: ...larly as in scheme no 1 description in point 4 1 Controlling the C circulation pump Similarly as in scheme no 2 description in point 4 2 Controlling K boiler pump The K boiler pump will be switched on if the T5 temperature at the boiler outlet gets higher by the Temperature difference ON add pump valve value than the T4 temperature in the upper part of the heater The pump will remain switched on u...

Страница 7: ...he set allowable value of Max temp T4 OFF heat source Fig 9 Schematic and electrical diagram of installation no 7 4 8 Double heater system makes it possible to provide additional solar energy heating for the boiler heater with the use of a circulation return scheme no 8 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the C circulation pump Similarl...

Страница 8: ...be found in the Parameter settings menu The C pool pump is always switched on when pool water is heated with solar collectors ATTENTION If the C pool pump is switched offwhen the solar collector pump is working and the U valve is set to the pool may damage the piping system of the pool circuit In order to protect the exchanger against lack of heat collection by the pool pump a T4 sensor should be ...

Страница 9: ... scheme Controlling the C circulation pump Similarly as in scheme no 2 description in point 4 2 Fig 14 Schematic and electrical diagram of installation no 12 4 13 The system with a buffer tank used for cooperation with a central heating installation scheme no 13 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the C boiler pump The C boiler pump is ...

Страница 10: ...ers have been used in the diagram Max temp T4 OFF heat source for heating with the use of an electrical boiler or a liquid fuel boiler and Max water temperature from boiler C for heating with the use of a fireplace or a solid fuel boiler for heating water in the upper part of the combi heater measured by the T4 sensor Fig 16 Schematic and electrical diagram of installation no 14 4 15 Tap water hea...

Страница 11: ...ure in the A heater reaches Max temp T4 OFF heat source When the T4 temperature exceeds the set value the controller switches the valve back into the B heater direction and switches the P collector pump off When water is being heated in the A heater once an hour for 5 minutes the controller forces P collector pump switch off in order to check the conditions for heating the B heater and switch heat...

Страница 12: ... Fig 20 Schematic and electrical diagram of installation no 18 4 19 Tap water heating system controlling solar collector pump mixing pump and system of solar energy heating for the boiler heater with the use of a circulation return scheme no 19 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the K mixing pump Similarly as in scheme no 7 description...

Страница 13: ...option named Parameters setting with enter the Parameter settings menu with get to the option named Time program K with enter the option named Time program K with select time with or accept operation time white square or cancel operation time with accept and return a continuous sound with return to the main screen with ATTENTION Hourly setting of K are identical to those of the Time program C 5 5 ...

Страница 14: ...er the flow value that results from the number of collectors in the system into the edition field Next set the required flow rate value in such a way that the Current value corresponds to the calculated value entered before The required flow can be obtained by changing the rotational speed in option Collector pump ATTENTION Leaving the field unchanged or entering wrong value does not affect the op...

Страница 15: ... water heater by switching the solar collector pumps on in a specific time interval starting from 0 00 to the time set in the Stop cooling at h parameter The cooling option will be active if cooling is on Night cooling Yes and the T2 temperature in the heater is higher or equal to the set Start cooling temperature Cooling will remain active until the heater gets cooler to the Stop cooling temperat...

Страница 16: ...ption of its functions has been included in point 4 for selected external devices only 10 85 C 50 C Max water temperature from boiler C A parameter only used in schemes no 14 and 18 It defines the maximum temperature of water measured by the T4 sensor for the operation of C pump cooperating with the water circuit of fireplace or solid fuel boiler 10 85 C 60 C Regulation of collector s pump P solar...

Страница 17: ...the circulating pump Time of switching off the C circulation pump in a set cyclic mode according to the preset working times 1 59min 10min Table 3 Controller parameter description 13 Error alarms and controller notifications Temperature sensor error check sensors for visual condition or for proper connection to the controller The controller checks whether temperature sensors have been connected If...

Страница 18: ...ing with the operation of the system and the controller Lack of required heater protection by titanium anode applies to the GH26 P09A controller only The controller is used as a power supply for the titanium anode placed in the water heater for protection of the latter against corrosion The lack of anode incorrect connection or damage to the anode circuit will switch on the sound alarm and display...