In the
Energy Statistics
menu there is also a total energy counter. This counter sums all the produced energy.
Statistics and total counter can be cleared any time. The clearing option can be found in the
Energy Statistics
menu and is available separately for the total counter and the statistics.
In order to view or clear energy counters select the "
Energy Statistics
” option. In order to do this:
Press the following key combination: starting point - MAIN SCREEN: enter the
MENU
with
, get to the option named
Energy Statistics
with
, enter the
Energy Statistics
option
with
, select the option with
or
, enter the options with
, select time intervals (day, week, month, year) with
or
, accept the interval
with
which results in displaying a graph, return to the main screen with
.
ATTENTION ! A change in date may result in distorting the chronology of recorded events or display of incorrect energy values. For the statistics counters to work
correctly it is necessary to clear them after each date change. It is not necessary to clear the total energy yield counter after a date change
.
10.
Vacation function
Vacation function switches on the option of
night
cooling
and
collector overheating protection
. Additionally, this option allows disabling additional heating devices
connected to the controller in the active time period declared by the user –
applies to scheme no. 3, 4, 5, 14.
Active vacation option is indicated by the display of the
screen
HOLIDAY
alternating with the scheme on the main screen of the controller.
11.
Software update
This option makes it possible to update the software using an appropriate cable and the application installed on the computer. In order to do this, use port RS485 in the controller.
12.
Description of control parameters (parameter settings)
Parameter
Description
Scope
Factory
settings
Solar
collector
type
The parameter makes it possible to select solar collector type (flat or tube).
If a tube collector is selected, then between 8.00
17.00, every full hour, the collector pump is switched on for a minute. Because
of the fact that temperature sensors are located at the bottom of the collector, in case of extremely low ambient temperatures the
temperature inside the collector might deviate from the temperature indicated by the sensor. If the T1 sensor reaches a
temperature required for system operation, the P pump will continue operating
Flat / Tube
Flat
Temp. T1&T2 difference
– pump ON
This parameter defines the conditions for switching the collector pump on and off. If the T1 temperature is higher than the sum of
the “
Temp. T1&T2 difference – pump ON ”
parameter and the T2 temperature of water in the heater, the collector pump will be
switched on.
4
15
C
6
C
Temperature difference
ON
add. pump, valve
This parameter is used for controlling advanced systems and therefore its description has been included in point 7 only for
selected external devices.
2
15
C
5
C
MaxTemp. T2
OFF
collector’s pump
This parameter is related to the T2 sensor located at the heater bottom. It defines the maximum allowable temperature of water
in the heater measured by the T2 sensor up to which solar collector pumps keep operating.
10
85
C
65
C
Min. temp. T5
ON
Boiler pump
A parameter used in schemes 6, 14 and 18. It defines the minimum boiler temperature (T5 sensor) for switching boiler pump on.
10
85
C
41
C
Max. temp. T4
OFF
heat source
Maximum temperature for switching an additional heat source, such as boiler, electrical heater or a heat pump, OFF. This
parameter is used in advanced schemes. Because of the variety of roles it plays in specific schemes, the description of its
functions has been included in point 4 for selected external devices only.
10
85
C
50
C
Max. water temperature
from boiler C
A parameter only used in schemes no 14 and 18. It defines the maximum temperature of water measured by the T4 sensor for
the operation of C pump cooperating with the water circuit of fireplace or solid-fuel boiler.
10
85
C
60
C
Regulation of collector’s
pump
P solar collector pump circulation adjustment. Switching this option on results in smooth changes the pump’s rotational speed.
When the option is switched off, the controller only distinguishes between collector pump being switched on or off.
Yes / No
Yes
Coll. power
OFF
boiler, heater, heat pump
A parameter used in installation schemes 3, 4, 5 and 14. The controller forces additional heating devices (boiler, heater, heat
pump) to switch off once the set collector power parameter is exceeded.
In order to eliminate too frequent on/off cycles of the devices during transient insolation conditions, the controller accounts for a 5
minute delay in switch off and switch on of heating devices.
ATTENTION! Setting the value of 9900W m
akes the operation of heating devices independent from the operation of solar
collectors.
100
9900W
1500W
Overheat protection of
collectors
This parameter defines switch on and switch off of the option protecting solar collectors from overheating.
When switched on, P collector pump gets switched off once the collector temperature exceeds 110
C. If the collector
temperature falls below 99
C or once the T2 heater temperature “
MaxTemp. T2 OFF overheat protection”
is exceeded
the P
collector pump gets switched off. This function works even if the maximum water temperature
MaxTemp. T2 OFF collector’s
pump”
in the heater is exceeded.
Yes / No
No
MaxTemp. T2
OFF
overheat protection
The parameter defines maximum temperature of water in the heater up to which collector pumps keep working when the option
“
Protection against collector overheating
” is active.
60
80
C
80
C
Freezing protection of
collectors ON
The parameter is used in those countries where water serves as heat transfer fluid in solar collectors.
This parameter defines switch on and switch off of the option protecting solar collectors from freezing.
If this function is switched on, the P solar collector pump gets switched on once the temperature in the water heater as measured
by the T2 sensor is higher than 7
C, and the temperature on collectors falls below the temperature set in the
Heat transfer fluid
option. Once the temperature of water in the heater falls to 4
C or the temperature on collectors exceeds the temperature set in
the
Heat transfer fluid
option, the solar collector pump switches off.
ATTENTION! Original heat transfer fluid(with no water added) does not freeze, so it is not necessary to use the
"Protection against collector freezing” option
.
Unjustified activation of the function may result in cooling water in the heater.
Yes / No
No
Selection of heating
priority
This parameter defines the selection of heating priority in schemes with two heat receivers (e.g. pool).
Selecting
A > B
results in setting priority heating to the pool or additional heater. If the conditions are not suitable for heating the
pool or an additional heater, heating is switched to the solar heater. Selecting
B > A
results in setting priority heating to the solar
heater. If the conditions are not suitable for the solar heater, heating is switched to the pool or an additional heater.
Selecting
B
results in setting absolute heating priority of the solar heater. Heating will be directed to the pool or an additional
heater only after reaching preset temperature of the solar heater.
A and B letters are connected with three-way valve outlets or the name of heat receivers.
B > A
A > B
B
B > A