ATTENTION ! Leaving the field unchanged or entering wrong value does not affect the operation of the controller and the system (the controller reads the actual flow rate 

from the electronic flow meter). 

Measurement: Rotameter 

– cooperation with

 a mechanical flow meter (rotameter). 

The controller works with declared values (calculating power and energy outputs). 

ATTENTION ! The bottom of the rotameter float indicates the actual flow rate value. 

 

Nominal

 

flow rate 

– entry to the nominal flow rate option results in switching P collector pump on with maximum efficiency - this value results from the number of solar 

collector employed. Enter the calculated flow value resulting from the number of collectors in the system in the edition field and set the required flow  in option 

Pump 

collector

 column 

Max

 (example: rotational speed of the pump set to 3500 rpm – the obtained flow rate is 6 l/min) – 

6 l/min

 is entered into the field. 

 

Minimum  flow  rate

  –  switching  into  the  minimum  flow  rate  option  results  in  switching  P  collector  pumps  on  with  minimum  efficiency  and  reducing  flow.  

– entry to the minimum flow option results in switching P collector pump on with minimum efficiency – the value results from the number of solar collectors used. Set the 
value obtained by changing the pump speed in the edition field in option 

Pump collector

 column 

Min

 (example: rotational speed of the pump set to 1000 rpm – the 

obtained flow rate is 2 l/min) – the value of 

2 l/min

 is entered into the field. 

The flow rate values set as above determine the linear characteristic of flow used for computing power output of collectors at variable speed of P collector pump (Fig. 22). 

 

Fig. 22. Graphical representation of flow settings.  

 

ATTENTION ! If after entering the minimum flow rate option, there is no flow shown by rotameter float, it is recommended to increase the speed of the pump. 

Nominal and minimum flow rate settings are only relevant when P collector pump adjustment is switched on. When this adjustment option is switched off it is only the 

nominal flow rate to be regulated.  

Leaving the field unchanged or entering wrong value may cause incorrect calculating of the power and thermal energy coming from solar collectors, but it does not 

affect the operation of the controller and the system. 

 

Measurement: Electr-OTHER

 – integration with 

any electronic flow meter

.

 

The controller reads the number of pulses declared by the user via the 

Weight

 parameter and converts 

into the actual flow rate (l/min). 

 

“Nominal” flow rate

 – entry to the nominal flow rate option results in switching P collector pump on with maximum efficiency. Enter the flow value that results from the 

number of collectors in the system into the edition field. Next, set the required flow rate value in such a way that the 

“Current”

 value corresponds to the calculated value 

entered before. The required flow can be obtained by changing the rotational speed in option 

Collector pump

ATTENTION!!! Leaving the field unchanged or entering wrong value does not affect the operation of the controller and the system (the controller reads the actual flow 

rate from the electronic flow meter – on the basis of entered “pulse weight”). 
Selecting the option Measurement: Electr-OTHER sets the same values for the second flow rate meter connected to the FLOW2 terminal. 

5.7

 

Collector pump 

The controller has the ability to control rotational speeds of different circulation pumps controlled by PWM signal. For proper operation of the system in the controller, a proper type of 
pump installed in the ZPS pump control unit is to be set as follows: 

Press the following combinations of keys: starting point – MAIN SCREEN: entering the 

MENU

 

 (enter password), moving to the option 

Parameters settings

 

, entering the 

menu 

Parameter settings 

, moving to the option 

Collector pump 

 

 

 

 

 

, entering the option 

Collector pump 

, choosing the parameter to be changed 

 

or 

, editing

, changing the values 

 or 

, acceptance (continuous tone) 

Minimum value – 

make the speed conditional on the required minimum and actual flow rate resulting from the type and number of solar collectors (see 5.6)

 

Maximum value – 

make the speed conditional on the required and actual flow rate resulting from the type and number of solar collectors (see 5.6)

 

Return to the main screen 

 

 

 

5.8  Default settings

 

There are optimal factory settings pre-programmed in the controller for correct controller operation (List of factory settings values – see Table 3).  

In order to restore the controller to factory settings: 
Press the following key combination: start – MAIN SCREEN: enter the MENU with 

 (enter password), get to the option named Parameter settings with 

, enter the 

Parameter 

settings

 menu with 

, get to the option named 

Default

 with 

 

 

 

 

 

 

, enter the option named 

Default 

with 

, restore to default settings and return with 

, return to the main screen with 

 

.  

6.

 

Controller settings 

6.1

 

Date and time  

This option makes it possible to set current date and time. In order to change date or time: 

Press the following key combination: starting point - MAIN SCREEN: enter the 

MENU

 with 

, get to the option named 

Controller settings 

with 

 

, enter the 

Controller 

settings

 menu with 

, get to the option named 

Date and time

 with

 

, choose appropriate parameters with 

, change values with 

 or 

, accept values with 

, leave 

the option named 

Date and time

 with 

 or use the 

 key to run through all the parameters, return to the main screen with 

 

.

 

6.2  Display 

Pump efficiency 

Minimum 

Nominal 

Flow [l/min] 

Содержание GH26-P09

Страница 1: ...USER MANUAL OF AN INDEPENDENT REGULATION BLOCK GH26 P09 GH26 P09A Controller of a solar collector system applicable from version 0 1a ...

Страница 2: ...t Maximum current intensity 2A O2 Transmitter output no voltage output relay Maximum current intensity 2A S1 S2 NC normally closed S2 S3 NO normally open May operate as voltage output applying voltage to S2 will result in changeover voltage output O3 230V output relay Maximum current intensity 2A O4 230V output bridging inside the controller It is allowed to bridge outside with a terminal of a rel...

Страница 3: ...ch on for the blanking period set Screen blanking aims at limiting energy consumption Connect the electrical plug to the socket equipped with a protective terminal and protected with RCD It is forbidden to install pump units in close vicinity of open flames high temperatures and storage of flammable materials 3 2 Controller keyboard description The controller has a touch keyboard with 7 keys which...

Страница 4: ...erence pump ON value than the T2 temperature in the lower part of the heater If the heater s temperature reaches the set value of MaxTemp T2 OFF collector s pump the P pump will be switched off Additionally in order to avoid unstable pump operation when the temperature on the sensor changes switch on and switch off hysteresis has been used Controlling the P collector pump Regulation of collector s...

Страница 5: ...to boiler switch on and switch off temperatures An example of a table of resistances depending on the manufacturer of a given boiler has been presented in the table below ATTENTION The original tap water temperature sensor remains disconnected and replaced by 2 wire cable from the controller GH26 Table 2 Resistor resistance for selected boiler manufacturers Fig 5 Schematic and electrical diagram o...

Страница 6: ...larly as in scheme no 1 description in point 4 1 Controlling the C circulation pump Similarly as in scheme no 2 description in point 4 2 Controlling K boiler pump The K boiler pump will be switched on if the T5 temperature at the boiler outlet gets higher by the Temperature difference ON add pump valve value than the T4 temperature in the upper part of the heater The pump will remain switched on u...

Страница 7: ...he set allowable value of Max temp T4 OFF heat source Fig 9 Schematic and electrical diagram of installation no 7 4 8 Double heater system makes it possible to provide additional solar energy heating for the boiler heater with the use of a circulation return scheme no 8 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the C circulation pump Similarl...

Страница 8: ...be found in the Parameter settings menu The C pool pump is always switched on when pool water is heated with solar collectors ATTENTION If the C pool pump is switched offwhen the solar collector pump is working and the U valve is set to the pool may damage the piping system of the pool circuit In order to protect the exchanger against lack of heat collection by the pool pump a T4 sensor should be ...

Страница 9: ... scheme Controlling the C circulation pump Similarly as in scheme no 2 description in point 4 2 Fig 14 Schematic and electrical diagram of installation no 12 4 13 The system with a buffer tank used for cooperation with a central heating installation scheme no 13 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the C boiler pump The C boiler pump is ...

Страница 10: ...ers have been used in the diagram Max temp T4 OFF heat source for heating with the use of an electrical boiler or a liquid fuel boiler and Max water temperature from boiler C for heating with the use of a fireplace or a solid fuel boiler for heating water in the upper part of the combi heater measured by the T4 sensor Fig 16 Schematic and electrical diagram of installation no 14 4 15 Tap water hea...

Страница 11: ...ure in the A heater reaches Max temp T4 OFF heat source When the T4 temperature exceeds the set value the controller switches the valve back into the B heater direction and switches the P collector pump off When water is being heated in the A heater once an hour for 5 minutes the controller forces P collector pump switch off in order to check the conditions for heating the B heater and switch heat...

Страница 12: ... Fig 20 Schematic and electrical diagram of installation no 18 4 19 Tap water heating system controlling solar collector pump mixing pump and system of solar energy heating for the boiler heater with the use of a circulation return scheme no 19 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the K mixing pump Similarly as in scheme no 7 description...

Страница 13: ...option named Parameters setting with enter the Parameter settings menu with get to the option named Time program K with enter the option named Time program K with select time with or accept operation time white square or cancel operation time with accept and return a continuous sound with return to the main screen with ATTENTION Hourly setting of K are identical to those of the Time program C 5 5 ...

Страница 14: ...er the flow value that results from the number of collectors in the system into the edition field Next set the required flow rate value in such a way that the Current value corresponds to the calculated value entered before The required flow can be obtained by changing the rotational speed in option Collector pump ATTENTION Leaving the field unchanged or entering wrong value does not affect the op...

Страница 15: ... water heater by switching the solar collector pumps on in a specific time interval starting from 0 00 to the time set in the Stop cooling at h parameter The cooling option will be active if cooling is on Night cooling Yes and the T2 temperature in the heater is higher or equal to the set Start cooling temperature Cooling will remain active until the heater gets cooler to the Stop cooling temperat...

Страница 16: ...ption of its functions has been included in point 4 for selected external devices only 10 85 C 50 C Max water temperature from boiler C A parameter only used in schemes no 14 and 18 It defines the maximum temperature of water measured by the T4 sensor for the operation of C pump cooperating with the water circuit of fireplace or solid fuel boiler 10 85 C 60 C Regulation of collector s pump P solar...

Страница 17: ...the circulating pump Time of switching off the C circulation pump in a set cyclic mode according to the preset working times 1 59min 10min Table 3 Controller parameter description 13 Error alarms and controller notifications Temperature sensor error check sensors for visual condition or for proper connection to the controller The controller checks whether temperature sensors have been connected If...

Страница 18: ...ing with the operation of the system and the controller Lack of required heater protection by titanium anode applies to the GH26 P09A controller only The controller is used as a power supply for the titanium anode placed in the water heater for protection of the latter against corrosion The lack of anode incorrect connection or damage to the anode circuit will switch on the sound alarm and display...

Отзывы: