9
Fault Reports and their correction
58
Betriebsanleitung_firematic_20-301_Touch_Englisch V1.2
9.2
Maintenance schedule (Customer inspection)
(Some points have also been prescribed in accordance with TGPF H 118!)
For safety reasons, maintenance must only be carried out with the main
switch turned off. However first of all, the system must be switched off by
means of the On/Off button and you must wait for the burnout phase. If you
have to climb into the storage tank or bunker, always make sure that there
is a second person available to supervise you..
Potential carbon monoxide enrichment may put your life in danger.
Interval
Part of the system
Activity
Weekly
a. Entire unit
a. The whole boiler system including the
fuel store must be visually inspected
Every 4-10
weeks
a. Ash
a. Fly ash, combustion chamber and ash
pans are to be cleaned or emptied (if
necessary). After you have removed the
fly ash pan, clean the fly ash area (using
a vacuum cleaner and broom)
Every 4 weeks
a. Operation of the controller
a. Switch the controller on and off, make
sure that it is working properly
b. Fault messages
b. Check: Faults must also be displayed
c. Combustion air fan,induced-
draught fans
c. Check: Fans must be work properly when
the boiler is in operation
d. Combustion chamber
d. Check the combustion chamber and
clean if required
e. Fire-extinguishers
e. Check: Equipment must be reliable (heed
the valid national regulations)
f. Ash storage
f. Check: Correct storage
g. Boiler room
g. No flammable materials must be present.
h. Fire doors
h. Must be in a good state of repair (e.g. fire
doors must close automatically
i.
Gear motor
i.
Check: visual inspection for oil leaks
At least all 3
months
a. Light barrier system
a.
Check light barrier system and clean if
necessary
Annually
a. Gear oil levels
a. Check and top up if necessary
b. Induced-draught fan
b. Disassembly and clean
c. Burn back protection device
c. Check for tightness
Every 2 years
a. Storage room
a. Empty the storage room completely and
clean it out
Every 3 years
a. Boiler system
a. Maintenance must be carried out on the
boiler system (<150 kW) by the system
installer.
b. Gear oil
b. Change the gear oil