Page 22
HERZ Wireless control system
Technical specifications
Environmental temperatures:
Operating
shipping and storage
0 °C - 40 °C
- 10 °C - 50 °C
Power supply
230 VAC, 50 Hz
Electrical protection
Class II – IP 20
Output
maximum load
Relais 10 A 250 VAC
up to 10 A - 250 VAC, 50 Hz (2 wires L, N)
Radio frequency &
RF receiving distance
868 MHz < 10 mW (bidirectional communication)
Range of approximately 100 m in open space
Range of approximately 30 m in residentials
EU Declaration of conformity
The equipment is in compliance with the
relevant Community harmonisation legislation:
Directive 2001/95/EC on General Products Safety
Low Voltage Directive 2006/95/EEC
Radio Equipment Directive 1999/5/EC - 2014/53/EU
RoHS Directive 2011/65/EC.
Product corresponds
Classification
Contribution
UE 811/2013 und 2010/30/UE
IV
2 %
Installation and RF Initialisation rules
Install and connect the receiver respecting the following guidelines to guarantee an optimal reception:
•
The receiver must be mounted at a minimum distance of 50 cm of all others electrical or wireless devices like
GSM, Wi-Fi router.
•
Wiring work related to the receiver must be carried out only when de-energized.
•
Connect your receiver to the power supply.
Depending on your installation, an order of pairing must be respected to ensure a correct RF signal transmission:
•
Installation 1: Re RF thermostat
(1) Switch on the receiver.
(2) Press the RF button during 5 sec to switch to
„rF init“
.
(3) The RF LED should be Green fixed or orange blink indicating that the Receiver is now in radio configuration mode
waiting for a thermostat configuration address.
(4) Please refer to the thermostat leaflet for enter the thermostat in
“rF init”
mode.
(5) The receiver RF LED must be switched
OFF
and the thermostat should exit the
“rF init”
mode to indicate correct
pairing between both elements.