Pressure Transmitters 050D series
Operating Instructions
- English - V1.0
PN-TI118-EN-14-1/12
Hengesbach GmbH & Co. KG
·
Schimmelbuschstr. 17
·
40699 Erkrath
·
Tel. +49 (0) 21 04 / 30 32-0
·
Fax +49 (0) 21 04 / 30 32-22
·
www.hengesbach.com
9
Electrical connection
9.1
Operating voltage range
This transmitter is a loop-fed, 2-wire, low-voltage DC device. Like all devices with a 2-wire design, the transmitter is supplied directly from
the current loop and enters a current proportional to the measuring size from 4…20mA .
The operating voltage of the device is 12...30 VDC. The transmitter must under NO circumstances be operated
with ANY other supply voltage. Too low a voltage can result in malfunctions; too great a voltage can cause
irreparable damage to the device.
Ensure the correct polarity when making the electrical connection. Inverted polarity means that the device does
not work. The transmitter will not be damaged, as its connection terminals are secured against voltage reversal.
9.2
Types of electrical connection
Depending on the connection variant, which you have ordered, the transmitter can come in one of four possible configurations. The
electrical connection of the device is contained in the device designation. The four possible variants are listed in the following:
Cable screw connection
PZM050D_1bar_
K
T1
(example for the designation of a device with a cable screw
connection)
Cable connection acc. to connection terminal designation
M12 device plug
PZM050D_1bar_
M
T1
(example for the designation of a device with an M12 device plug)
Assignment of the M12 plug
(as viewed from the plug side
of the housing)
Angle plug
PZM050D_1bar_
W
T1
(example for the designation of a device with an angle plug)
Assignment of the angle plug
(as viewed from the plug side
of the housing)
Reference cable is connected
PZM050D_1bar_
R10
T1
(example for the designation of a device with a connected 10
metre reference cable)
Brown
Black
Supply
–
White
EARTH
Shield
EARTH