Pressure Transmitters 050D series 

 

Operating Instructions 

 

- English - V1.0

 

 

PN-TI118-EN-14-1/7 

Hengesbach GmbH & Co. KG  

·

  Schimmelbuschstr. 17 

·

  40699 Erkrath  

· 

 Tel. +49 (0) 21 04 / 30 32-0  

·

  Fax +49 (0) 21 04 / 30 32-22   

· 

www.hengesbach.com

 

4

 

Commissioning 

 

The  commissioning  process  enables  you  to  parametrise  the  transmitter  with  only  a  few  actions.  The  empty  and  full  adjustment  enable 
setting  the  thresholds  of  4  und  20mA  .  The  wavelet  set  lies  between  these  two  thresholds.  This  is  represented  by  the  transmitter  by  a 
16mA loop current linear to the process.  

 

When making the adjustment, ensure that the  (under) pressure lies within the max. permissible threshold for the 
transmitter. 

 

4.1

 

Setting the measuring range begin (empty adjustment) 

Use  the  empty  adjustment  to  set  the  start  of  the  transmitter  measuring  range.  To  this  end,  apply  the  desired  (under)  pressure  to  the 
transmitter / filling level and hold the 

 key depressed. Whilst continuing to hold the key depressed, the status LED will extinguish and 

then  after  c.  5  s  will  illuminate  green  permanently.  You  can  release  the  key  -  the  transmitter  has  saved  the  pressure  value  as  the  new 
measuring range begin and issues a  4mA  signal. 

 

 

 

 

 

 

 

 

 

Hold the 

 key 

depressed 

 

Status LED  

extinguishes 

 

Initialisation 

phase (5s) 

 

Status LED 

illuminates green 

 

Release the 

 

key 

 

4.2

 

Setting the end of the measuring range (full adjustment) 

Use the full adjustment to set the transmitter measuring range end. To this end, apply the desired (under) pressure to the transmitter / 
filling level and hold the 

 key depressed. Whilst continuing to hold the key depressed, the status LED will illuminate and then after c. 5 s 

will continue to illuminate green. You can release the key - the transmitter has saved the pressure value as the new measuring range end 
and issues a  20mA  signal. 

 

 

 

 

 

 

 

 

 

Hold the 

 key 

depressed 

 

Status LED  

extinguishes 

 

Initialisation 

phase (5s) 

 

Status LED 

illuminates green 

 

Release the 

 

key 

 

 

If  the  status  LED  illuminates 

red

  after  extinguishing,  the  transmitter  is  not  able  to  process  the  current  (under) 

pressure for the empty or full adjustment. In this case, check whether the measuring range is smaller than 25% of 
the  nominal  measuring  range.  Before  adjusting,  it  may  be  necessary  to  restore  the  factory  settings,  so  that 
threshold values already set can be reset to their origin. 

 

Содержание 050D Series

Страница 1: ...PN TI118 EN 14 1 1 Hengesbach GmbH Co KG Schimmelbuschstr 17 40699 Erkrath Tel 49 0 21 04 30 32 0 Fax 49 0 21 04 30 32 22 www hengesbach com ...

Страница 2: ..._______ _____________________________________________________________________________________________________ _____________________________________________________________________________________________________ _____________________________________________________________________________________________________ ______________________________________________________________________________________...

Страница 3: ...the measuring range full adjustment 4 3 Restoring factory settings 4 4 Reading the status LED in measuring mode 5 Opening the outer packaging 6 Identifying the device 7 Assembly information 8 The connection and operating elements in the device head 9 Electrical connection 9 1 Operating voltage range 9 2 Types of electrical connection 9 3 Connection diagram for normal measuring mode 9 4 Calibration...

Страница 4: ...tion Electrostatic danger Electrostatic danger points to the fact that the device or its components could suffer irreparable damage from electrostatic discharge Magnetically sensitive Magnetically sensitive points to the fact that placement of the device in electromagnetic fields can subject its operation to a negative influence Caution heat Caution heat is a warning of personal injury from burns ...

Страница 5: ... of flashing is c 2Hz The status LED flashes red green alternately The status LED in the device head flashes red green alternately The frequency of flashing of every colour is c 6Hz key This symbol represents the key in the device head with the following designation key This symbol represents the key in the device head with the following designation and keys This symbol represents the combination ...

Страница 6: ...osive atmosphere Please read these operating instructions carefully before commissioning the devices If you have questions please contact the manufacturer s technical department The manufacturer can be contacted under the following address Hengesbach Prozessmesstechnik GmbH Co KG Schimmelbuschstr 17 40699 Erkrath GERMANY Tel 49 0 2104 3032 0 Fax 49 0 2104 3032 22 www hengesbach com info hengesbach...

Страница 7: ...n release the key the transmitter has saved the pressure value as the new measuring range begin and issues a 4mA signal Hold the key depressed Status LED extinguishes Initialisation phase 5s Status LED illuminates green Release the key 4 2 Setting the end of the measuring range full adjustment Use the full adjustment to set the transmitter measuring range end To this end apply the desired under pr...

Страница 8: ... operation The following flash patterns and their significance are explained here Status LED illuminates green The current process pressure is located within the operating thresholds set for the transmitter The output current is proportional to the measuring value The transmitter is in its optimum transducer mode Status LED flashes green The current process pressure is located outside the operatin...

Страница 9: ...of the shipment until its commissioning and the check of the moisture proof status of the screw connections Check that the goods are correct undamaged and complete Compare the details on the delivery note with the contents of the shipment received Please notify the manufacturer of any discrepancies 6 Identifying the device The following figures show a transmitter type plate example and the meaning...

Страница 10: ...move the protective cover from the measuring cell during the assembly preparations Only remove the cover shortly before installing the transmitter Make sure that you don t touch the membrane during the installation The device manufacturer recommends that device openings such as ventilation openings should point downwards during the installation if possible This way in the event that process media ...

Страница 11: ...ess calibrator can be connected to the connection terminal without needing to disconnect the power supply to control Additionally potential equalisation to the control unit can be made via the terminal Slide switch The slide switch can be used to switch the transmitter from normal measuring operation and the calibration function It enables power supply of the device from a further source Status LE...

Страница 12: ...nsmitter will not be damaged as its connection terminals are secured against voltage reversal 9 2 Types of electrical connection Depending on the connection variant which you have ordered the transmitter can come in one of four possible configurations The electrical connection of the device is contained in the device designation The four possible variants are listed in the following Cable screw co...

Страница 13: ...following schematic Connect the power supply with the transmitter via the terminals 1 and 2 Observe and comply with the permissible voltage range of 12 30V DC Ensure maintenance of the correct polarity the voltage reversal does not cause any damage but it will not commence measurement operation The pressure value determined by the transmitter is depicted in the supply loop with a current proportio...

Страница 14: ...t be able to provide a minimum current of 22mA In this configuration the transmitter is supplied by a mobile instrument and depicts its measured value through a proportional current in the calibrator loop The supply via the terminals 1 and 2 is not in operation it need not be disconnected The slide switch does not establish a galvanic isolation between the two circuits The calibration function is ...

Страница 15: ... of the measuring value If the reference cable is used the ventilation tube must also be free from foreign objects The transmitters are fully encapsuled and therefore have no dead spaces However especially during the cleaning process major heating up with subsequent cooling down processes can result in a vacuum inside the device This effect will be reduced to a minimum due to the small dead space ...

Страница 16: ... with the returned device Tell us what you would like us to do with the returned item if applicable Use the product accompaniment form included in the scope of delivery when returning the device The manufacturer s returns address is Hengesbach Prozessmesstechnik GmbH Co KG service hengesbach com info hengesbach com Schimmelbuschstr 17 www hengesbach com 40699 Erkrath Tel 49 0 2104 3032 0 GERMANY F...

Страница 17: ...not perform as expected please check the following points before contacting the manufacturer Fault Possible causes Check correction The device does not start or no current is flowing in the loop the status LED remains out The voltage of the power supply is reversed or incorrectly connected Make sure that the power supply is connected correctly The power supply is not switched on Use a voltmeter to...

Страница 18: ...g span span 25 100 of the sensor s nominal measuring span Burst pressure DIN16086 4 fold nominal measuring range Output Output signal 2 wire 4 to 20mA with a test circuit connection in the device Fault signal 22mA Current limitation 3 8mA and 21mA Measuring accuracy Reference conditions acc to DIN IEC 770 Linearity hysteresis and repeatability acc to the limit point method DIN IEC 770 0 2 of the s...

Страница 19: ...EHEDG type EL ASEPTIC CLASS I certified connection system PZM with press screw M38x1 5 and elastomer sealing Process seal EPM FDA temperature range 20 150 C Process seal FPM FDA temperature range 40 200 C Materials Field housing lid CrNiSt 1 4301 304 Housing seal FPM Viton Pressure compensation element polyamide Process connection connection adapter CrNiSt 1 4404 304 Process membrane CrNiSt 1 4435...

Отзывы: