background image

20

 

2.  Blank or incomplete display on board 

A.  Transformer unplugged 

A.  Plug transformer into uninterrupted power supply, 

     

 

 

 

verify power connection is plugged into 4-prong 

     

 

 

 

connection on PC board

     

B.  No electric power at outlet 

B.  Repair outlet or use working outlet, should read 115V

     

 

 

 

with voltmeter at outlet.  Verify power cannot be turned 

     

 

 

 

off with another switch 

     

C.  Defective transformer 

C.  Check voltate at connection with transformer plugged  

     

 

 

 

in.  Should read >12 volt AC with voltmeter.  Replace   

     

 

 

 

transformer if inadequate voltage

     

D.  Low battery after power outage 

D.  If power outage occurred and battery on board has    

     

 

 

 

low voltage, the microprocessor may not recover cleanly 

     

 

 

 

and display properly.  Disconnect power from circuit    

     

 

 

 

board and remove battery, wait 5 minutes.  Reconnect 

     

 

 

 

power, if displays appropriately, replace battery (lithium 

     

 

 

 

CR2032).  If you do not have battery at time of evalua-

  

     

 

 

 

tion, leave the battery out of board, only concern will 

     

 

 

 

be time of day reset will be needed if power outage 

     

 

 

 

occurs again.  Voltage on battery should be > than 3 

     

 

 

 

volts.

  3.  Control valve does not regenerate 

A.  Transformer unplugged 

A.  Connect transformer

    automatically when REGEN button 

B.  No electric power at outlet 

B.  Repair outlet or use working outlet

    is depressed and held 

C.  Broken drive gear or drive cap assembly 

C.  Replace drive gear or drive cap assembly

     

D.  Defective PC board 

D.  Replace PC board 

  4.  Control valve does not regenerate 

A.  Bypass valve in bypass position 

A.  Put control valve in service position

    automatically but does when 

B.   Meter connection disconnected 

B.  Connect meter to PC board

    REGEN button is depressed 

C.  Restricted/stalled meter turbine 

C.  Remove meter and check for free rotation

     

 

 

 

or foreign matter

     

D.   Defective meter 

D.  Replace meter

     

E.  Defective PC board 

E.  Replace PC board

     

F.  Programming error 

F.  Check control valve set-up procedure 

 

  5.  Time of day flashes on and off 

A.  Battery back-up maintains time-of-day up 

A.  Reset time of day and replace battery on PC Board

     

 

to 2 years in event of power outage and  

 

(Lithium coin type battery 2032)

     

 

battery is not depleted. Time of day flashes

     

 

when battery is depleted.

 

  6.  Softener delivers hard water. 

A.  Bypass valve is open or faulty. 

A.  Close bypass valve or replace.

     

B.  No salt or low salt level in brine tank. 

B.  Add salt to brine tank and maintain salt level 

 

     

 

 

 

above water level.

     

C.  Softener fails to draw brine. 

C.  See problem #10.

     

D.  Excessive water usage. 

D.  Check gallon capacity settings.

     

E.  Insufficient brine level in brine tank. 

E.  Check  brine  refill  setting  and  refill  flow  restrictor  for   

 

     

 

 

 

blockage.

     

F.   Resin level inadequate. 

F.  See problem #7. 

     

G.  Meter faulty. 

G.  Test meter and clean or replace meter.

     

H.  Raw water hardness fluctuation. 

H.  Test raw water hardness and adjust settings to 

 

     

 

 

 

highest known hardness.

 

  7.  Unit uses too much salt. 

A.  Improper brine refill setting. 

A.   Check  brine  refill  setting  for  proper  salt  dosage

 

     

B.  Improper settings. 

B.  Check water hardness and reevaluate capacity setting

 

     

 

 

 

specification

     

C.  Excessive water in brine tank. 

C.  See problem #9.

     

D.  Leaking faucets, toilets, etc... 

D.  Repair or replace those items.

     

E.  Brine line flow control out of place 

E.  Replace Brine line flow control.

 

 

8.  Loss of resin. 

A.  Backwash controller missing. 

A.  Install backwash controller.

     

B.  Faulty distributor tube assembly. 

B.  Check distributor tube assembly for cracks or holes.

     

C.  Air being drawn in through brine system. 

C.   Check  for  leaks  in  brine  lines,  fittings,  or  air  check. 

 

     

 

 

 

Repair or replace.

     

D.   Air in water supply system 

D.  1. Install upper distributor if missing.

     

 

   

 

2. Ensure that water supply system has an air 

     

 

 

 

eliminator.

 

 

9.  Softener delivers salty water. 

A.  Low water pressure. 

A.  Check incoming water pressure - Must remain at  

 

     

 

 

 

minimum of 25 psi.

     

B.  Excessive water in brine tank. 

B.  See problem #9.

     

C.  Wrong size injector. 

C.  Install correct injector.

 

TROUBLESHOOTING

 PROBLEM 

CAUSE 

CORRECTION

Содержание ProMate 1

Страница 1: ...Owner s Manual Manufactured by HELLENBRAND hellenbrand com info hellenbrand com 106231 Rev A 6 24 19 LBRY 2019 ...

Страница 2: ... on preference Soft water helps fabrics last longer because hardness minerals combined with soap can make fabric fibers brittle 2 What is the health impact of drinking soft water The sodium added to water by softening is a non issue most of the time even for people on a sodium restricted diet One could soften up to 75 grains per gallon water with sodium chloride and still be well within the US Foo...

Страница 3: ...son x _______ Family Size Number of people in family _______ Total Gallons Per Day x _______ Grains Per Gallon of Hardness Note Add 3 grains per gallon of hardness for each ppm iron for total compensated hardness _______ Total Grains Per Day INSTALLATION DATE _________________________________________________________________________________ REVISION REV NUMBER_______________________________________...

Страница 4: ... of weeks initially to determine how much salt you use this will depend on how much water you use As a rule of thumb with 20 gpg hard water about a 1 2 lb of salt per person per day is used In other words a family of four uses 60 lbs of salt a month If your household does not use much water do not fill your salt keeper over 1 2 full salt bridging may occur in the brine tank This may result in hard...

Страница 5: ... existing plumbing must be free from lime and iron build up Piping that is built up heavily with lime and or iron must be replaced If piping is blocked with iron additional equipment must be installed ahead of the water conditioner to correct the problem Drain Line The conditioner should be located close to a drain Avoid overhead drain lines if possible to prevent back pressure on the brine inject...

Страница 6: ...If soldering joints near the drain must be done prior to connecting the drain line flow control fitting Leave at least 6 between the drainlinecontrolfittingandsolder jointswhensolderingpipes that are connected on the drain line control fitting Failure to do this could cause interior damage to the drain line flow control fitting 6 The brine refill flow control assembly is installed in an easy to ac...

Страница 7: ...the regen button until LED display says BRINE Loosen the brine line from the top of the safety brine valve in the brine tank Place finger over the end of the tube to check for suction If no suction see trouble shooting guide If proper suction reattach brine tube to safety brine valve and allow it to draw water down to the bottom of the air check 9 Press REGEN button again until LED once again dis ...

Страница 8: ...f iron present Step 3 Day Override This sets the number of days between regenerations If value set to oFF regeneration initiation is based solely on gallons used If value is set as a number allow able range from 1 to 28 a regeneration initiation will be called for on that day even if sufficient number of gallons were not used to call for a regeneration Set Day Override using or buttons number of d...

Страница 9: ...for the fourth cycle which in this example is dn BRINE using the or button Press NEXT to go to Step 7S Press REGEN to return to the previous step STEP 7S Select the time for the fourth cycle which in this example is 2nd Backwash using the or button Press NEXT to go to Step 8S Press REGEN to return to the previous step CYCLE TIME ADJUSTMENTS Normally it is not recommended to adjust the lengths of t...

Страница 10: ...allon capacity is set to AUTO Press NEXT to go to Step 10S Press REGEN to return to previous step STEP 10S set Gallons Capacity using or button If value is set to AUTO gallon capacity will be automatically calculated and reserve capacity will be automatically estimated oFF regeneration will be based solely on the day override set see Installer Display Settings Step 3I or as a number of gallons all...

Страница 11: ...he pounds of salt in the brine tank and add it to the amount of salt added to the brine tank The example at the left would indicate 200 lbs of salt being added to a brine tank that has 40 lbs remaining Step 4US Press SET CLOCK to exit Adding Salt RETURN TO NORMAL MODE NOTE The salt used per regeneration setting can be set in increments of 0 1 pounds but LBS REMAINING screen will round up or down t...

Страница 12: ...urred on the day the word REGEN will also be displayed This display will show dashes if a water meter is not installed Press NEXT at any time to go to Step 6D Press REGEN to return to previous step STEP 5D STEP 4D Volume reserve capacity used for last 7 days If the valve is set up as a softener a meter is installed and Set Volume Capacity is set to Auto this display shows 0 day for today and flash...

Страница 13: ...TO NORMAL MODE STEP 8D STEP 9D MAV Drive History in the direction of retracted piston rod position Display will not be shown if 1 0T is not selected in Step 2CS or OFF is selected in Step 4CS If the display does appear up to a four digit number will appear after the L which stands for latest and A which stands for average Drive time is measured in 1 100 of a second i e a 17 15 second move is displ...

Страница 14: ... occurred E 1 is displayed Press NEXT to exit valve history STEP 1VH VALVE HISTORY STEP 2VH 970 DAY STEP 3VH 235 STEP 4VH 175 GAL x1000 Can not be reset REGEN STEP 5VH E1101 CYCLE SEQUENCE Cycle Sequence instructions allows the operator to set the order of the cycle The Softener System Setup allows the operator to set how long the cycles will last The operator may choose up to 9 cycles in any orde...

Страница 15: ...e MAV Softener System Setup Step 10S Set to AUTO Set to AUTO Softener System Setup Step 11S Set regeneration time option to On O Set regeneration time option to On O Installer Display Setting Step 3I Set Day Over ride to oFF Set Day Over ride to oFF NOTE If the control valve is in an error state during regeneration mode the MAV will close the B port and keep open the A port until the error is corr...

Страница 16: ... Selection requires that a connection to a Clack Motorized Alternator Valve MAV is made to the two pin connector labeled ALTERNATOR DRIVE located on the printed circuit board The C port of the MAV must be connected to the valve inlet and the A port connected to the separate source used during regeneration The B port must be connected to the feed water supply When set to SEPS the MAV will be driven...

Страница 17: ... dPdEL If the dP switch is closed for an accumulative time of 2 minutes a regeneration will occur at the scheduled regeneration time HoLd If the dP switch is closed a regeneration will be prevented from occurring Press NEXT to go to Step 9CS Press REGEN to return to previous step STEP 5CS First Regeneration Cycle Press or buttons to select in this example it is backwash Press NEXT to go to Step 6C...

Страница 18: ...ation B EPA and NSF approved Sani System by Pro Products This can be purchased from your water treatment provider or at http proproducts com products sani system 1 Salt Usage See your water conditioning professional for a recommendation on the best type of salt for your application 2 Brine Tank Cleaning a Remove brine tank cover b Scoop out as much old salt as possible c Disconnect brine tubing fr...

Страница 19: ...ation modes Transformer should provide 12 volts when plugged into outlet and not attached to board if not replace transformer Error Code 103 Motor ran too long C1 Piston unable to reach home position C1 Incorrect assembly check drive bracket is correctly timed out trying to reach home position seated and snapped into place on backplate wires outside of guides on backplate can impede drive bracket ...

Страница 20: ... control valve set up procedure 5 Time of day flashes on and off A Battery back up maintains time of day up A Reset time of day and replace battery on PC Board to 2 years in event of power outage and Lithium coin type battery 2032 battery is not depleted Time of day flashes when battery is depleted 6 Softener delivers hard water A Bypass valve is open or faulty A Close bypass valve or replace B No...

Страница 21: ...bed A Use iron reducing resin cleaner to clean resin bed and increase salt dosage or regenerate more frequently or rebed softener Install an Iron Curtain System ahead of the softener B Iron is not in a soluble state B Test water to determine type of iron install iron reduction system C Prefilter failure C Check prefilter D Iron level excessive D Install iron reduction system E Control fails to reg...

Страница 22: ... 33 1 104409 Brine Tank 18 x 40 1 104415 b 24x50 Salt Keeper Tank Black 1 104497 9a Brine Tank Cover 18x40 1 101448 b Brine Tank Cover 24x50 Included with 8a 10 14 Safety Brine Valve Assy 50 104173 10 Cap Brine Well 2 101365 11 Safety Brine Valve 1 101274 12 Float Assembly 1 111853 13 Air Check 1 101181 14 a Brine Well 40 41 1 102877 b Brine Well 50 102878 15 2 Piece Overflow 1 102217 16 a Grid Pl...

Страница 23: ...nds or unplug power source jack from the printed circuit board black wire and plug back in This resets the electronics and establishes the service piston position The display should flash all wording then flash the software version ex 154 and then reset the valve to the service position Do not use vaseline oils other hydrocarbon lubricants or spray silicone anywhere A silicon lubricant may be used...

Страница 24: ...ector plugs are located in both holes The nuts and caps are designed to be unscrewed or tightened by hand or with the special plastic wrench If necessary a pliers can be used to unscrew the nut or cap Do not use a pipe wrench to tighten or loosen nuts or caps Do not place screwdriver in slots on caps and or tap with a hammer Do not use pipe dope or other sealants on threads Teflon tape must be use...

Страница 25: ... not use pipe dope or other sealants on threads Teflon tape must be used on threads of the 1 NPT connection and on the threads for the drain line connection Teflon tape is not necessary on the nut connection nor caps because of o rings seals Figure 18 Figure 19 Systemsareshippedwithout3 4 nutfordrainelbow polytubeinstal lation only and 5 8 polytube insert polytube installation only See System Spec...

Страница 26: ...ass Handle 2 7 109479 Bypass Rotor Seal Retainer 2 8 102159 O Ring 135 2 9 102161 O Ring 112 2 10 102160 O Ring 214 2 Bypass Valve Not Shown Bypass Vertical Adapter Assembly ORDER NO DESCRIPTION QTY 102141 Nut 1 Quick Connect 2 102437 Split Ring 2 102165 O Ring 215 2 106858 Bypass Verticle Adapter 2 WATER METER AND METER PLUG 1 102141 Nut 1 QC 1 2 4 102051 Meter Assy 1 3 102687 Turbine Assy 1 4 10...

Страница 27: ...ants on threads Teflon tape must be used on threads of the 1 NPT connection and on the threads for the drain line connection Teflon tape is not necessary on the nut connection nor caps because of o rings seals 101639 Fitting 1 PVC Male NPT ITEM NO ORDER NO DESCRIPTION 101640 Fitting 3 4 1 PVC Solv 90 108618 Fitting 1 Lead Free Brass Sweat 108617 Fitting 3 4 Lead Free Brass Sweat 101643 Fitting 1 M...

Страница 28: ... 2 3 2 0 5 0 5 0 5 0 5 0 5 VIOLET RED RED WHITE YELLOW 0 18 0 21 0 21 0 25 0 44 0 23 0 27 0 27 0 32 0 57 850 1 125 1 125 1 700 2 275 1 1 1 1 1 3 4 3 4 3 4 3 4 3 4 3 8 3 8 3 8 3 8 3 8 3 4 3 4 3 4 3 4 3 4 3 8 3 8 3 8 3 8 3 8 High Salting may requiredifferent grid height and or larger brinetank Factory default setting are shown in bold Recommended minimum pipes sizes arecopper pipeequivalent when usi...

Страница 29: ... any valid war ranty claims against Hellenbrand THIS WARRANTY DOES NOT COVER defects caused by sand sediment or bacteria fouling accident fire flood Act of God misuse misapplica tion neglect alteration installation or operation contrary to Hellenbrand s printed instructions or installation repair or service by anyone other than Hellenbrand or an authorized seller of Hellenbrand products IN ADDITIO...

Отзывы: