MegaBox MB
– Centrifugal fans
Installation and Operating Instructions
– The MegaBox Ex centrifugal fans are designed as components of a
stationary
ventilation system. They may only be
operated when installed as intended and safety is ensured by protective installations and the required constructional
explosion protection measures according to DIN EN 14986.
– According to DIN EN 14986, fans are not to be regarded as absolutely gas-tight. The same explosion-proof zone is valid
for inside and outside!
–
The unit may be operated outdoors with an outdoor cover hood .
The fan must only be used for its intended purpose!
– The transportation of solids or solid particles in the transport medium and fluids is not permitted.
– Transport media, which attack the fan material, are not permitted.
– The fan is not suitable for transporting dusty media. Deposits of dust in the fan casing and/or impellers are not per-
mitted.
– The fan must not be connected to a smoke gas duct.
– There must be no rust particles in the air flow.
– The temperature class on the type plate must correspond to the ignition temperature of the potential gas or the fan
must meet the requirements of a higher temperature class.
–
The fan may only be operated within the specified performance curve range, so that sufficient cooling is en-
sured . Usage beyond the range of the performance curve is not permitted!
1 .9 Performance data
The motor type plate provides information about the electrical values; these must be coordinated with the local supply
network. The fan performances* were determined on a test stand according to DIN 24163; they are valid for the rated
speed and standard version with free inflow and discharge. Diverging versions and adverse installation and operation
conditions can lead to a reduction of performance.
1 .10 Noise data
The noise data* also refers to the above mentioned configuration. Casing vibrations, adverse operating conditions,
etc. can lead to an increase of the values specified in the catalogue. Data relating to certain distances (1, 2, 4 m) are
valid for free-field conditions. The sound pressure level can differ significantly from the data published in the catalogue
after installation, as sound pressure levels depend on the absorption capacity on the room, the place of installation
and other factors.
2 .0 Safety information for explosion-proof fans
The usage, connection and operation of explosion-proof fans are subject to special regulations; consul-
tation is required in case of doubt. Helios explosion-proof fans comply with the requirements
of ATEX, Directive 2014/34/EU (Product Safety Act). In order to assess hazardous areas, the alloca-
tion of zones by the operator is necessary. Only fans in the appropriate category approved for the res-
pective zone may be used. Further information can be found in the relevant standards and legal texts.
–
Before any maintenance or installation work or before opening the terminal compartment, the device must
be fully isolated from the power supply and secured against unintended restart! The electrical connection
must be carried out only by a qualified electrician in accordance with the following wiring diagrams!
– Compliance with the EMC Directive refers only to this fan when it is directly connected to the public grid. If the fan
is integrated into a system or supplemented with other components and operated, the manufacturer or operator is
responsible for compliance with the EMC Directive.
– Speed control and abnormally frequent activation/deactivation is not permitted!
– Every motor must have a
motor protection device
of category II (2)G, see Directive 2014/34/EU (Product Safety Act),
which is to be adjusted to the rated current of the motor and which trips within the time tE specified on the motor
type plate, provided the motor is blocked. The function is to be tested on the basis of the tripping characteristic line
enclosed with the protection switch. Also observe the regulations especially enclosed with the device.
– The intake of foreign objects in the fan has to be avoided by using protection devices corresponding to IP20 (EN 60529) or
with a mesh width of no more than 12 mm.
–
The compliance of the air gap (the gap between nozzle and door panel, Fig . 7) represents an extremely important
feature for explosion protection . For example, this can be affected by external influences on the casing . Therefore,
the casing must not be deformed during the assembly .
Maintaining the required gap at any point of the circumference
must be ensured by regular inspection!
– In order to comply with operational safety requirements, a vibration check must be carried out at regular intervals! Alternatively,
it is advisable to install an Ex-version vibration monitoring system on site. This must take the system out of service when the
limits have been exceeded. The permissible vibration limits according to ISO 14694 are shown in the table on page 7, 3.6.
– The planners and operators must ensure easy access for inspection and cleaning work!
– The operator is responsible for compliance with all plant-related safety regulations.
– A uniform inflow and a free discharge must be ensured.
– Upstream and downstream components or those that are directly in the air stream must not have unprotected
aluminium or steel surfaces. According to DIN EN 14986, paint containing aluminium must not be used (risk of a
thermite reaction).
– If there is a danger of lightning, the systems must be protected by suitable lightning protection measures.
– Product must be located at a sufficiently safe distance to transmitters or be protected by suitable shielding.
– The regulations for avoiding an ignition hazard due to electrostatic discharges (TRGS 727) must be implemented.
ATTENTION
m
ATTENTION
m
CHAPTER 2
SAFETY INFORMATION
WARNING
m
ATTENTION
m
*(Performance and noise data from the cur-
rently valid Helios documentation and
the internet)
D
EN
Содержание MegaBox MB
Страница 15: ...13 MegaBox MB Radialventilatoren Montage und Betriebsvorschrift DE...
Страница 29: ...13 MegaBox MB Centrifugal fans Installation and Operating Instructions EN...
Страница 30: ...14 MegaBox MB Centrifugal fans Installation and Operating Instructions EN...
Страница 31: ...15 MegaBox MB Centrifugal fans Installation and Operating Instructions EN...