5
Wall installed unit KWL EC 60 Pro / ... Pro FF
Installation and Operating Instructions
UK
D8 = Language:
Language selection between Ger-
man, English, French or Italian.
D9 = Date and time:
Setting of the current date and time
(time zone).
D10 = Display fade-out time:
The display fade-out time can be set
between 5 - 30 seconds. If no confir-
mation at the comfort controller is
carried out for this time, the display
goes out and the control returns to
the highest menu level.
D11 = Knob light:
Location light: If the display is off, the
knob of the rotary encoder is blue
lighted. The lightness can be set bet-
ween 0 – 100 %.
Error indication: If the display is off
and an error is present, the knob of
the rotary encoder is flashing red.
The lightness can be set between 20
– 100 %.
D12 = Service menu:
Over the service menu several para-
meters can be adjusted individually.
In order to get into the password-
protected menu, enter password
5255.
E1 = Operating hours display:
The counting of the operating hours
take place as soon as one or both
fans are running.
An operating hours reset can only be
carried out in the factory.
E2 = Heat exchanger frost protec-
tion:
0 till 10° C
E3 = Min. fan speed
The minimum fan speed can be set
between level 0 and 1. If level 0 is
specified, the KWL-unit can be swit-
ched off. If level 1 is specified, level 0
cannot be activated, nor in the wee-
kly program.
E9 = Controller address
The controller address can be chan-
ged later. It should be noted that the
addresses are always only once
assigned. Maximum 4 controllers can
be connected.
E11 = Software version:
Query to the current state of the soft-
ware version of the main board and
controller
E12 = Resetting to factory setting
All parameters can be reset to fac-
tory setting. If the settings in the wee-
kly program should not be reset, this
option can be set in advance.
E13 = Motor monitoring:
Speed monitoring: The motors are
speed monitored – if the speed in
level 1 falls below 1100 1/min, auto-
matically a speed increase follows to
level 2. If the speed is still below 1100
1/min after about 10 seconds, the
KWL-unit stops and the shutters clo-
se. This also occurs if the speed is
too low in level 2 - 4.
Current monitoring: The motor cur-
rents are monitored permanently – if
minimum or maximum value is rea-
ched, the KWL-unit stops and the
shutters close.
Voltage monitoring: The output volta-
ges at the board are monitored per-
manently - if minimum or maximum
value is reached, the KWL-unit stops
and the shutters close.
Error code:
E1
è
Status line fan “Supply air”
E2
è
Status line fan “Extract air”
E3
è
Exceeding maximum current
”Supply air“
E4
è
Exceeding maximum current
”Extract air“
E5
è
Falling below minimum current
”Supply air“
E6
è
Falling below minimum current
”Extract air“
E7
è
Terminal fault “Supply air“
E8
è
Terminal fault “Extract air“
E9
è
Supply voltage 24 V