KWL Hygrobox KWL HB.. EH/WW
Installation and Operating Instructions
8.3 SETTINGS
• The parameter
Temperature
is used to set the air tem-
perature at the outlet of the air humidification unit bet-
ween 15 °C and 25 °C in intervals measuring one degree
each. The factory setting is preset at 21 °C.
• The parameter
TemperaturE
(E = external temperature
sensor), is used to set the desired air temperature at the
external sensor between 15 °C and 25 °C in 1° intervals.
• The parameter
Humidity
is used to set the target outlet
air humidity at a level between 40 % and 60 % of relati-
ve humidity, in intervals of five per cent each. The factory
setting is preset at a relative humidity of 50 %.
• The menu item
Service
displays information about the
operational status.
• Internal sensor
shows the currently measured air tem-
perature and the relative humidity at the air outlet of the
air humidification unit.
• External sensor
indicates the currently measured air
temperature at the external temperature sensor.
• If a sensor is not connected, the following will be dis-
played (see adjacent image).
• The installed software version is shown under
Info
.
• Error messages, which appear in the Info line of the dis-
play, are deleted using the
Delete Fault Yes<
function.
• With
Expert
, you can access the next lower menu level by
entering a code. This parameter can be opened only by
the respective expert.
Temperatur 21°C<
Feuchte
50%<
Service <
Interner Fühler <
Temperatur 21°C
Feuchte 50%
Externer Fühler <
Ext. Fühler 21°C
g
Ext. Fühler nich
t an
gesch
lossen!
Info
<
V 1.0
Softwareversion
01.09.08
Fehler löschen <
Fehler Ja<
löschen? Nein
Experte
<
Kennzahl?
------
9. Operating statuses
9.1 AUTOMATIC ACTIVATION/DEACTIVATION AUTUMN/SPRING (AUTO STANDBY)
• The air humidification unit switches on when the air hu-
midity is too low (Autumn) and off when the air humidity
is too high (Spring). The following appears on the display
(see adjacent image).
• If the evaporative power within 24 hours is less than one
litre, the device switches off (Auto STANDBY).
• If the humidity undershoots the set humidity by 7% for a
period of 24 hours, the air humidification unit switches on
again.
a
uto S
TANDBY
REGELUNG EIN