10
Safety Precautions
Installation Precautions
WARNING!
The area of the room in which R32 refrigerant air conditioner is installed cannot be less than the minimum area specified in
the table below, to avoid potential safety problems due to out-of-limit of refrigerant concentration inside the room caused by
leakage of refrigerant from refrigeration system of the indoor unit.
Once the horn mouth of connecting lines is fastened, it may not be used again (the air tightness may be affected).
A whole connector wire shall be used for indoor/outdoor unit as required in the operation specification of installation process
and operation instructions.
Minimum Room Area
Type
R32
0.306
LFL
kg/m3
hv
m
0.6
1.0
1.8
2.2
Total Mass Charged/kg
Minimum Room Area/m
2
1.224
1.836
2.448
3.672
4.896
6.12
7.956
29
51
116
206
321
543
10
19
42
74
116
196
3
6
13
23
36
60
4
2
9
15
24
40