background image

 

MAKING THE ELECTRICAL CONNECTIONS 

 

WARNING: THIS WATER HEATER MUST BE EARTHED.  

 

The electrical installation must be in accordance with the current BS.7671 (IEE Wiring Regulations) 
and “Part P” of the Building Regulations and/or local regulations 

 

Wiring to the mains (Check the unit rating to see which applies) 

 

 

Rating 

Fuse/MCB 

Isolating Switch  Cable Size 

9.5 kW 

40 amps 

40 amps 

6 mm² / 10 mm² * 

10.8 kW 

45 amps 

45 amps 

10 mm²  

12 kW 

50 amps 

50 amps 

10 mm² /16mm² * 

 

* For cable runs over 10 metres or where cable is not flat clipped and surface mounted,  
   the larger size is the minimum required. 

 

A means for disconnection in all poles must be incorporated in the fixed wiring in 

accordance with the wiring rules. 

 

If the unit is fitted in a Bathroom:  

 

9.5 kW and 10.8 kW Multiflow: A standard 45-amp cord operated isolator switch is recommended. 

 

12 kW Multiflow: A double pole 50 amp isolator switch is required. 

                        This must be mounted out of reach of the shower cubicle or bath.  
                        (A pull cord isolator switch is not available for this model) 

 

Wiring the Multiflow 

 

 

The unit has been designed to accept up to 16mm² supply cable.                                                                                   

It will be necessary to cut the rubber entry grommet (diagram 6, point X to X) to enable 10mm² 

and 16mm² to be correctly installed.  No cutting is required for 6mm² cable.                                                                            
In all cases, the outer sheath of the cable MUST project through the grommet (diagram 6),                                            
if side entry is used.  This will prevent water getting into the unit.  

 

 

Strip back the insulation on the 

LIVE

 (brown or red) and 

NEUTRAL 

(blue or black) mains wires 

about 8mm.  Strip back any insulation on the 

EARTH

 (green/yellow or green) about 20mm. 

 

 

Feed the cable through the side or rear entry grommets, as appropriate. 

 

 

Connect the cables to the terminal block and earth stud (diagram 6) 

 

 

Make sure that the live and neutral terminal block screws are tightened securely (1Nm minimum) 

 

 

Make sure that the earth wire is wrapped around its terminal stud and into the saddle washer.         
The nut should be tightened securely (2Nm minimum). 

 

WARNING:  FAILURE TO COMPLY WITH THESE INSTRUCTIONS COULD RESULT IN  

                FAILURE OF THE TERMINAL BLOCK 

 

 

Check that the Power Selector Screw on the flow switch is set to “HI” (diagram 7).                                                          

 

If flow switch is set to “LO” only one heater element will operate. 

 

 

Fit the front cover and tighten the retaining nuts.

 

 

Ensuring the earth continuity 

 

 

If the unit is fitted in a bathroom, to conform with the current BS.7671 (formally IEE regulations), 

the units earth continuity conductor must be effectively connected to 

ALL

 exposed metal parts of 

ALL

 other appliances in the room. 

Содержание Multiflow 10.8kW

Страница 1: ...h the user after installation and demonstration It should be kept in a safe place as you may need to refer to it for general instructions or future maintenance HEATSTORE MULTIFLOW UNVENTED INSTANTANEOUS WATER HEATER Installation and User Guide ...

Страница 2: ... the current edition of BS 7671 the IEE Wiring Regulations and Part P of the Building Regulations in force at the time of installation Installations outside England and Wales must also conform to any local regulations in effect This appliance is intended to be permanently connected to the fixed electrical wiring of the mains supply with its own dedicated supply Ensure that the mains water supply m...

Страница 3: ...namic Water Pressure Basin Shower Minimum Maximum Minimum Maximum Up to 9 5kW 10 psi 0 7 bar 69 kPa 150 psi 10 3 bar 1035 kPa 15 psi 1 1 bar 103 kPa 150 psi 10 3 bar 1035 kPa Up to 10 8kW 15 psi 1 1 bar 103 kPa 150 psi 10 3 bar 1035 kPa 20 psi 1 4 bar 138 kPa 150 psi 10 3 bar 1035 kPa Up to 12 0kW 20 psi 1 4 bar 138 kPa 150 psi 10 3 bar 1035 kPa 25 psi 1 8 bar 172 kPa 150 psi 10 3 bar 1035 kPa FIX...

Страница 4: ... the backplate diagram 3 Feed the cable through the grommet before you fix the unit to the wall Fixing to the wall Undo the retaining nuts and take the front cover off the unit Hold the backplate in position against the wall whilst you mark the four fixing holes Drill the holes and fix the unit to the wall using the screws supplied Plumbing the unit WARNING IF A NON RETURN VALVE IS FITTED IN THE I...

Страница 5: ...Connecting the unit to the pipes The inlet and outlet are clearly marked on the unit They each have a Ø15mm straight shank connections The unit comes with a service valve diagram 5 which should be fitted on the inlet of the unit The valve can be used to turn off the water supply to the unit if it needs servicing or to reduce the main supply flow if it is too high Fitting the attachments If the uni...

Страница 6: ... 6 point X to X to enable 10mm and 16mm to be correctly installed No cutting is required for 6mm cable In all cases the outer sheath of the cable MUST project through the grommet diagram 6 if side entry is used This will prevent water getting into the unit Strip back the insulation on the LIVE brown or red and NEUTRAL blue or black mains wires about 8mm Strip back any insulation on the EARTH green...

Страница 7: ...on light goes out then turn it back until the neon just comes on check the water temperature at the handset and if necessary turn the cold tap on and adjust to get the desired shower temperature WARNING YOU MUST REGULARLY INSPECT THE SHOWER HOSE FOR WEAR AND DAMAGE REPLACE IF NECESSARY OR EVERY TWO YEARS WITH OUR APPROVED PART WARNING IN ORDER TO MAINTAIN THE PERFORMANCE OF YOUR SHOWER YOU MUST DE...

Страница 8: ...shed do not switch off the power if you are going to use the unit again shortly Shower Check that the power is switched on at the mains local isolator switch Turn on the hot or flow tap FULLY diagram 9 If the unit has been used recently run the water through for a few seconds to let the temperature settle down we advise you DO NOT enter the water flow during this time WARNING YOU MAY INITIALLY GET...

Страница 9: ... the thermal cut out is operating A second outlet has been turned on Increase the supply water flow Make sure that the service valve is correctly adjusted Do not use the basin whilst using the shower Shower spray pattern deteriorates The shower handset is clogged Clean the handset using a descaling solution if required see page 9 We offer a technical advisory service on the telephone to installers...

Страница 10: ...n supply to the INLET marked in blue Use a pump to boost the supply from a storage tank Reset it by opening the unit and pushing the button on the cut out diagram 11 Before you do this you must remove the cause of the problem Contact Heatstore Water too cold neon light on The power select screw is set to LO One element is not working The Power Supply Voltage has dropped Change the power select scr...

Страница 11: ...s means that with the 12 0kW unit you can shower at 39 C with a flow rate of 5 litres minute in the middle of winter The unit includes a dual thermal cut out diagram 11 which is attached to the heat exchanger tube It will switch off the heater elements if the water flow is reduced too much and the temperature goes above a set limit The first stage cut out is cyclic and will automatically reset as ...

Страница 12: ... NOT cover damage or defects arising from poor or incorrect installation improper use or lack of maintenance including the build up of limescale The unit MUST NOT be fitted to any type of thermostatic mixer valve or tap The unit MUST NOT be fitted to a bath or kitchen sink other than for hand washing purposes It is the responsibility of the installer to check that the installation parameters meet ...

Отзывы: