background image

5

Installation Instructions and Owner’s Manual

Unvented Liquid Propane Fired Room Heater

Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, 

Air for Combustion and Ventilation for required size of 

ventilation grills or ducts.

*IMPORTANT:

 Do not provide openings for inlet or 

outlet into attic. If attic has a thermostat-controlled 

power vent, heated air entering the attic will activate 

the power vent.

IMPORTANT:

 Vent-free heaters add moisture to 

the air. Although this is beneficial, installing heater 

in rooms without enough ventilation air may cause 

mildew to form from too much moisture. See Fresh 

Air for Combustion and Ventilation, pages 3 

 

through 5. 

INSTALLATION

WARNING: 

Any change to this heater or its 

controls can be dangerous.

NOTICE:

 This heater is intended for the use as 

supplemental heat. Use this heater along with your 

primary heating system. Do not install this heater as 

your primary heat source. If you have a central heating 

system, you may run system’s circulating blower while 

using heater. This will help circulate the heat throughout 

the house. In the event of a power outage, you can use 

this heater as your primary heat source for the duration 

of the outage. 

heater, Gas furnace, Vented gas heater, Gas 

fireplace logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-

vent draws combustion air from the outdoors and 

vents to the outdoors.
Example:
Gas water heater  40,000 Btu/hr
Vent Free   20,000 Btu/hr
Total 

 

=60,000 Btu/hr

4. Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.
Example: 51,800 Btu/hr (maximum Btu/hr the   

 

space can support)

 

60,000 Btu/hr (Actual amount of Btu/hr used)

The space in the above example is a confined 

space because the actual Btu/hr used is more than 

the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options 

are as follows:

A. Rework worksheet, and the space of an adjoining 

room. If the extra space provides an unconfined 

space, remove door to adjoining room or add 

ventilation grills between the rooms. See Ventilation 

Air From Inside Building (Fig. 2)

B. Vent room directly to the outdoors. See Ventilation 

Air From Outdoors (Fig. 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size 

makes room unconfined. 

If actual Btu/hr used is less than the maximum 

Btu/hr the space can support, the space is an 

unconfined space. You will need no additional fresh 

air ventilation.

VENTILATION AIR
Ventilation from Inside Building

This fresh air would come from an adjoining unconfined 

space. When ventilation to an adjoining unconfined 

space, you must provide two permanent openings: one 

within 12” of the ceiling and one within 12” of the floor 

on the wall connecting the two spaces (see options 

1 & 2 of figure 2). You can also remove door into 

adjoining room (see option3, fig 2). Follow the National 

Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, 

Air for Combustion and Ventilation for required size of 

ventilation grills or ducts.

 WARNING:

 Rework worksheet, adding the space 

of the adjoining unconfined space. The combined 

space must have enough fresh air to supply all 

appliance in both spaces. 

Ventilation from Outdoors

If necessary provide extra fresh air by using ventilation 

grills or ducts. Connect these items directly to the 

outdoors or spaces open to the outdoors. These 

include attics* and crawl spaces. Follow the National 

Ventilation 

Gills into 

Adjoining 

Room - Op-

tion 1

Ventilation Gills into Ad-

joining Room - Option 2

12”

12”

Or remove 

door into 

Adjoining 

Room - 

Option 3

INLET 

AIR

OUTLET 

AIR

VENTILATION CRAWL SPACE

TO CRAWL 

SPACE

TO ATTIC

VENTILATION AIR

VENTILATED 

ATTIC

OUTLET AIR

Figure 2

Figure 3.

Содержание HSVFBF10LP

Страница 1: ...r from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be pro...

Страница 2: ...liance Due to high temperatures heater should be kept out of traffic and away from furniture and draperies Surface of heater becomes very hot when running Keep children and adults away from hot surfaces to avoid burns or clothing ignition Heater will remain hot for a time after shutdown Allow heater surfaces to cool before handling Young children should be carefully supervised when they are in the...

Страница 3: ...you provide fresh outside air If heater keeps shutting off it requires servicing 5 Turn off and let cool before servicing Only a qualified service person should service and repair heater 6 Do not run heater Where flammable liquids or vapors are used or stored During dusty conditions 7 Before using furniture polish wax carpet cleaner or similar products turn heater off If heated the vapors from the...

Страница 4: ...nstruction provide adequate combustion and ventilation air by the methods described in the National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 or applicable local codes 3 Add the Btu hr of all the fuel burning appliances in the space such as Vent free heater Gas water SAFETY DEVICE This heater has a pilot with an Oxygen Depletion Sensor ODS safety shut off system The ODS pilot shuts off the hea...

Страница 5: ...ecause the actual Btu hr used is more than the maximum Btu hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet and the space of an adjoining room If the extra space provides an unconfined space remove door to adjoining room or add ventilation grills between the rooms See Ventilation Air From Inside Building Fig 2 B Vent room directly to the...

Страница 6: ...t be at least 18 inches above floor Locate heater where moving vehicle will not hit it CAUTION This heater creates warm air currents These currents move heat to wall surfaces next to heater Installing heater next to vinyl or cloth wall covering or operating heater where impurities such as tobacco smoke aromatic candles cleaning fluids oil or kerosene lamps etc are present in the air may discolor w...

Страница 7: ... mounting bracket is firmly fastened to wall studs Attaching to Wall using Anchor For attaching mounting bracket to hollow walls wall areas between studs or solid walls concrete or masonry Note Wall anchors mounting screws and spacer are in hardware package The hardware package is provided with heater 1 Drill holes at marked locations using 5 16 drill bit For solid walls concrete or masonry drill ...

Страница 8: ...r Use of floor mounting feet will require you to use a 3 8 NPT street elbow to make gas connection CAUTION Never connect heater directly to the Propane supply This heater requires an external regulator not supplied Install the external regulator between the heater and Propane LP supply The installer must supply an external regulator The external regulator will reduce the incoming gas pressure to b...

Страница 9: ...Reconnect heater and equipment shutoff valve to gas supply 8 Reconnected fittings must be checked for leaks in next section Low Pressure Test Pressure Equal To or Less Than psig 3 5 kPa 1 Close equipment shutoff valve see figure 13 2 Pressurize supply piping system by either using compressed air or opening propane LP supply valve 3 Check all joints from the propane LP supply valve to equipment shu...

Страница 10: ...ushed in slightly Do not force 4 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you do not smell gas go to the next step 5 Push in gas control know slightly and turn counterclockwise to PILOT IGN and depress for five 5 seconds Note The first time that the heater is operated after connecting the ...

Страница 11: ...rille guard is in place before running heater If screen or grille guard is removed for servicing it must be replaced prior to operating the heater WARNING Failure to keep the primary air opening s of the burner s clean may result in sooting and property damage CLEANING ODS PILOT AND BURNER Use as vacuum cleaner pressurized air or small soft bristled brush to clean CLEANING BURNER PILOT AIR HOLE IN...

Страница 12: ... thermocouple 7 Replace Control valve Burner does not light after ODS pilot is lit 1 Burner orifice is clogged 2 Burner orifice diameter to small 3 Inlet gas pressure is too low 1 Clean burner orifice see Cleaning and Maintenance on page 11 or replace burner orifice 2 Replace burner orifice 3 Contact local gas company Delayed ignition of burner 1 Manifold pressure is too low 2 Burner orifice is cl...

Страница 13: ...ing Gas Connections page 9 2 Replace control valve Gas odor during combustion 1 Foreign matter between control valve and burner 2 Gas leak See WARNING statement at top of page 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Connections page 9 Heater produces a clicking ticking noise just after burner is lit or shut off 1 Metal expanding while heati...

Страница 14: ...ner Left Bracket 1 18 N A Heat Shield 1 7 N A ODS Pilot Assembly w Thermocouple LP 1 19 N A Back Heat Shield 1 8 80017 Burner Assembly 1 20 80005 Valve Bracket 1 9 80009 Orifice 1 21 80006 Knob 1 10 N A Burner Right Bracket 1 22 80080 Valve 1 11 80016 Elbow Adapter 90 Regulator Connection 1 23 80034 Glass Bracket 1 12 80078 Regulator 1 70342 Hardware Kit not shown 1 1 2 3 4 5 6 7 8 9 10 11 12 13 1...

Страница 15: ...056 ODS Pilot Assembly w Thermocouple LP 1 15 N A Heat Shield 1 6 N A ODS Bottom Bracket 1 16 N A Back Heat Shield 1 7 N A Fireproof Plate 1 17 80005 Valve Bracket 1 8 70597 3 8 FTP x 3 8 MPT Elbow 1 18 80006 Knob 1 9 80078 Regulator 1 19 80080 Valve 1 10 N A Regulator Mounting Bracket 1 70342 Hardware Kit not shown 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 PARTS LIST AND DIAGRAM WARNING F...

Страница 16: ...aterial and workmanship for a period of five years from the date of manufacture During the first two years EGI will repair or replace this product if it is proven to be defective within the first two years and it is returned at customer expense with proof of purchase to the location of EGI s choice EGI will be the sole judge of what is determined to be a defect In year s three to five EGI will pro...

Отзывы: