Installation Instructions and Owner’s Manual

Unvented Liquid Propane Fired Room Heater

Figure 12

CHECKING GAS CONNECTIONS

WARNING:

 Test all gas piping and connections for 

leaks after installing or servicing. Correct all leaks 

at once. 

WARNING:

 Never use an open flame to check for 

a gas leak. Apply a mixture of liquid soap and water 

to all joints. Bubbles forming show a leak. Correct 

all leaks at once. 

PRESSURE TESTING GAS SUPPLY PIPING 

SYSTEM
High Pressure 

Test pressure in Excess of ½ psig (3.5kPa)

1.  The appliance and its appliance main gas valve 

must be disconnected from the gas supply 

piping system during any pressure testing of 

that system at test pressures in excess of 

½ 

 

psi (3.5 kPa). The appliance must be isolated 

from the gas supply piping system by closing 

its equipment shutoff valve during any pressure 

testing of the gas supply piping system at test 

pressures equal to or less than 

½

 psi (3.5 kPa).

2.  Cap off open end of gas pipe where equipment 

shutoff valve was connected.

3.  Pressurize supply piping system by either using 

compressed air or opening main gas valve on 

or near gas meter.

4.  Check all connections and joints in gas supply 

piping system. Apply mixture of liquid soap and 

water to gas joints. Bubbles forming show a leak.

5.  Correct all leaks at once.
6.  Depressurize and relieve pressure in supply 

piping system.

7.  Reconnect heater and equipment shutoff valve 

to gas supply. 

8.  Reconnected fittings must be checked for leaks 

in next section. 

Low Pressure

Test Pressure Equal To or Less Than ½ psig (3.5 kPa)

1.  Close equipment shutoff valve (see figure 13).
2.  Pressurize supply piping system by either using 

compressed air or opening propane/LP supply 

valve.

3.  Check all joints from the propane/LP supply 

valve to equipment shutoff valve (see figure 

14). Apply mixture of liquid soap and water to 

gas joints. Bubbles forming show a leak.

4.  Correct all leaks at once.
5.  Depressurize and relieve pressure from supply 

piping system.

Pressure Testing Heater Gas Connections:

1.  Make sure that the heater supply piping system 

is connected and has been leak tested as 

described above.

2.  Make sure control knob of heater is in OFF 

position.

3.  Open equipment shutoff valve (see figure 13). 

Figure 13

4.  Open propane/LP supply valve.
5.  Check all joints from equipment shutoff valve 

to control valve (see figure 14). Apply mixture 

of liquid soap and water to gas joints. Bubbles 

forming show a leak.

6.  Correct all leaks at once.
7.  Light heater (see 

Operating Your Heater

, page 

page 10.

Equipment 

Shutoff Valve

Open

Closed

Control Valve

Equipment 

Shutoff Valve

To regulated propane 

source

Figure 14

Nipple

Tee Joint

Cap

Shutoff Valve

HEATER CABINET

Nipple

Nipple

Tee Joint

Ground Joint Union

3/8” NPT Pipe Nipple

Pressure 
Regulator

Test Gauge
Connection

1/8” NPT Plug Tap

Reducer Bushing
to 1/8” NPT

Nipple

Sediment 
Trap

3” minimum

Fuel line from 

Regulated LP Tank

(11”W.C to 14” WC Pressure)

Содержание HSVFBF10LP

Страница 1: ...r from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be pro...

Страница 2: ...liance Due to high temperatures heater should be kept out of traffic and away from furniture and draperies Surface of heater becomes very hot when running Keep children and adults away from hot surfaces to avoid burns or clothing ignition Heater will remain hot for a time after shutdown Allow heater surfaces to cool before handling Young children should be carefully supervised when they are in the...

Страница 3: ...you provide fresh outside air If heater keeps shutting off it requires servicing 5 Turn off and let cool before servicing Only a qualified service person should service and repair heater 6 Do not run heater Where flammable liquids or vapors are used or stored During dusty conditions 7 Before using furniture polish wax carpet cleaner or similar products turn heater off If heated the vapors from the...

Страница 4: ...nstruction provide adequate combustion and ventilation air by the methods described in the National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 or applicable local codes 3 Add the Btu hr of all the fuel burning appliances in the space such as Vent free heater Gas water SAFETY DEVICE This heater has a pilot with an Oxygen Depletion Sensor ODS safety shut off system The ODS pilot shuts off the hea...

Страница 5: ...ecause the actual Btu hr used is more than the maximum Btu hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet and the space of an adjoining room If the extra space provides an unconfined space remove door to adjoining room or add ventilation grills between the rooms See Ventilation Air From Inside Building Fig 2 B Vent room directly to the...

Страница 6: ...t be at least 18 inches above floor Locate heater where moving vehicle will not hit it CAUTION This heater creates warm air currents These currents move heat to wall surfaces next to heater Installing heater next to vinyl or cloth wall covering or operating heater where impurities such as tobacco smoke aromatic candles cleaning fluids oil or kerosene lamps etc are present in the air may discolor w...

Страница 7: ... mounting bracket is firmly fastened to wall studs Attaching to Wall using Anchor For attaching mounting bracket to hollow walls wall areas between studs or solid walls concrete or masonry Note Wall anchors mounting screws and spacer are in hardware package The hardware package is provided with heater 1 Drill holes at marked locations using 5 16 drill bit For solid walls concrete or masonry drill ...

Страница 8: ...r Use of floor mounting feet will require you to use a 3 8 NPT street elbow to make gas connection CAUTION Never connect heater directly to the Propane supply This heater requires an external regulator not supplied Install the external regulator between the heater and Propane LP supply The installer must supply an external regulator The external regulator will reduce the incoming gas pressure to b...

Страница 9: ...Reconnect heater and equipment shutoff valve to gas supply 8 Reconnected fittings must be checked for leaks in next section Low Pressure Test Pressure Equal To or Less Than psig 3 5 kPa 1 Close equipment shutoff valve see figure 13 2 Pressurize supply piping system by either using compressed air or opening propane LP supply valve 3 Check all joints from the propane LP supply valve to equipment shu...

Страница 10: ...ushed in slightly Do not force 4 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you do not smell gas go to the next step 5 Push in gas control know slightly and turn counterclockwise to PILOT IGN and depress for five 5 seconds Note The first time that the heater is operated after connecting the ...

Страница 11: ...rille guard is in place before running heater If screen or grille guard is removed for servicing it must be replaced prior to operating the heater WARNING Failure to keep the primary air opening s of the burner s clean may result in sooting and property damage CLEANING ODS PILOT AND BURNER Use as vacuum cleaner pressurized air or small soft bristled brush to clean CLEANING BURNER PILOT AIR HOLE IN...

Страница 12: ... thermocouple 7 Replace Control valve Burner does not light after ODS pilot is lit 1 Burner orifice is clogged 2 Burner orifice diameter to small 3 Inlet gas pressure is too low 1 Clean burner orifice see Cleaning and Maintenance on page 11 or replace burner orifice 2 Replace burner orifice 3 Contact local gas company Delayed ignition of burner 1 Manifold pressure is too low 2 Burner orifice is cl...

Страница 13: ...ing Gas Connections page 9 2 Replace control valve Gas odor during combustion 1 Foreign matter between control valve and burner 2 Gas leak See WARNING statement at top of page 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Connections page 9 Heater produces a clicking ticking noise just after burner is lit or shut off 1 Metal expanding while heati...

Страница 14: ...ner Left Bracket 1 18 N A Heat Shield 1 7 N A ODS Pilot Assembly w Thermocouple LP 1 19 N A Back Heat Shield 1 8 80017 Burner Assembly 1 20 80005 Valve Bracket 1 9 80009 Orifice 1 21 80006 Knob 1 10 N A Burner Right Bracket 1 22 80080 Valve 1 11 80016 Elbow Adapter 90 Regulator Connection 1 23 80034 Glass Bracket 1 12 80078 Regulator 1 70342 Hardware Kit not shown 1 1 2 3 4 5 6 7 8 9 10 11 12 13 1...

Страница 15: ...056 ODS Pilot Assembly w Thermocouple LP 1 15 N A Heat Shield 1 6 N A ODS Bottom Bracket 1 16 N A Back Heat Shield 1 7 N A Fireproof Plate 1 17 80005 Valve Bracket 1 8 70597 3 8 FTP x 3 8 MPT Elbow 1 18 80006 Knob 1 9 80078 Regulator 1 19 80080 Valve 1 10 N A Regulator Mounting Bracket 1 70342 Hardware Kit not shown 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 PARTS LIST AND DIAGRAM WARNING F...

Страница 16: ...aterial and workmanship for a period of five years from the date of manufacture During the first two years EGI will repair or replace this product if it is proven to be defective within the first two years and it is returned at customer expense with proof of purchase to the location of EGI s choice EGI will be the sole judge of what is determined to be a defect In year s three to five EGI will pro...

Отзывы: