Operating Instructions and Owner’s Manual

Additional requirements for horizontal venting:

• 

Category III venting systems may NOT be common vented, and no 
other gas units are allowed to be vented into it.

• 

Vent must terminate a minimum of 3 feet (914mm) above any 
forced air inlet that is located within 10 feet.

• 

The bottom of the vent terminate must be located a minimum 
of 12 inches above grade level and must extend beyond any 
combustible overhang.

• 

When horizontally vented, minimum clearance for termination 
from any door, window, gravity air inlet, gas or electric 
meter, regulators, and relief equipment is 4 ft. (1.2m) for U.S. 
installations. Refer to NFPA 54/ANSI Z223.1 in the U.S.A. and 
CSA B149.1 Natural Gas and Propane Installation Code and .2 in 
Canada or with authorities having local jurisdiction. In Canada, 
vent termination must have a minimum 6 ft. (1.8 m) horizontal 
clearance from gas and electric meters and relief devices as 
specified in the Canadian B149.1, Natural Gas Installation Code.

• 

Never join two sections of double wall vent pipe within one 
horizontal vent system, as it is impossible to verify that inner pipes 
are completely sealed.

• 

For a vent termination located under an eave, the distance of the 
overhang must be at least 24”. The clearance to combustibles 
above the exterior vent must be maintained at a minimum of 12”. 
Consult the National Fuel Gas Code for additional requirements 
for eaves that have ventilation openings.

• 

For horizontal venting, the vent pipe shall be supported with 
hangers no more than 3ft.(1m) apart to prevent movement after 
installation.

The Horizontal Run 

of Vent Pipe Shall 

be Pitched Upward 

1/ 4 IN. to the FT. 

(21 MM to the M).

Power 

Exhauster 

Outlet

5 ft. 

Min.

12” 

Min.

Terminal

Tee with Drip Leg and 

Cleanout Cap at Low 
Point of Vent System

Horizontal Venting

FIGURE 8

COMBUSTION AIR REQUIREMENTS

Adequate facilities for supplying air for combustion and ventilation 
must be provided in accordance with the latest edition of section 5.3, 
Air for Combustion and Ventilation, of the National Fuel Gas Code, 
ANSI Z223.1, in the U.S.A., CSA B149.1 Natural Gas and Propane Instal-
lation Code,  the National Standards of Canada or applicable provisions 
of local building codes.

All gas fired appliances require air to be used for the combustion 
process. In many buildings today, there is a negative indoor air pressure 
caused by exhaust fans, etc. If sufficient quantities of combustion air 

are not available, the heater or another appliance will operate in an in-
efficient manner, resulting in incomplete combustion which can result 
in the production of excessive carbon monoxide.

Follow these guidelines and all applicable codes for all models prior to 
installing the combustion air duct work.

 

WARNING: Sufficient combustion air must be supplied 

to the appliance at all times. Lack of combustion air may 
result in property damage, headaches, nausea, dizziness, 
asphyxiation, serious injury, or death.

GAS CONNECTIONS

 

WARNING: Danger of explosion and fire. Improperly 

connected gas lines may result in serious injury and death, 
explosion, poisonous fumes, toxic gases, or asphyxiation. 
Connect gas lines in accordance to national, state, provincial, 
and local codes. 
This heater burns natural gas or liquefied petroleum (LP) gas 
and is equipped with a regulator. The regulator is built into 
the gas valve. The maximum inlet pressure to this regulator 
is 20 in. W.C.. If gas line pressure exceeds 20 in. W.C., then 
an additional regulator must be installed before the heater/
regulator to step down the pressure to a maximum of 20 in. 
W.C.. 
All field gas piping must be pressure/leak tested prior to 
operation. Never use an open flame. Use a soap solution or 
equivalent for testing. 
You must follow these instructions exactly. If over-heating 
occurs or if gas supply fails to shut off, shut off the manual 
gas valve to the appliance before shutting off electrical 
supply.

 

CAUTION: Gas lines should be purged of air as described 

in ANSI Z223.1 (NFPA 54) or CSA-B149.1– latest version. 
Installation of the piping must also conform with the local 
building codes, or in the absence of local codes, with the 
latest edition of the National Fuel Gas Code (NFPA 54). In 
Canada, installation must be in accordance with CSA-B149.1. 
 
When leak testing the gas supply piping system, the 
appliance and its combination gas control must be isolated 
during any pressure testing in excess of 14” W.C. (1/2 psi). 
The unit should be isolated from the gas supply piping 
system by closing its field installed manual shut-off valve. 
This manual shut-off valve should be located within 6’ of the 
heater. 
Turn off all gas before installing appliance

NOTICE:

 The total input to the appliance must fall /- 5% of 

the rated input as indicated on the rating plate. Otherwise the heat 
exchanger may prematurely fail.

All piping installed must comply with local codes and ordinances or 
with National Fuel Gas Code, ANSI Z223.1 (NFPA 54), whichever takes 
precedence. When installing piping, the following requirements must 
be taken into consideration: Canadian installations must comply with 
the B149.1.2 Gas Code.

• 

Use new properly reamed black pipe free from chips.

• 

Apply a good quality pipe compound to all male threads prior 
to assembly. If LP gas is the fuel, ensure that pipe compound is 
resistant to LP gas. 

Do not use Teflon™ tape.

Содержание HSU200NG

Страница 1: ...ce agency or the gas supplier WHAT TO DO IF YOU SMELL GAS DO NOT try to light appliance DO NOT touch any electrical switch do not use any phone in your building Leave the building immediately Immediat...

Страница 2: ...BTU Efficiency 80 80 80 80 LANGUAGES ENGLISH 1 28 SPANISH 29 56 FRENCH 57 84 CONTENTS SAFETY 2 INTRODUCTION 5 INSTALLATION 6 START UP 16 MAINTENANCE 20 FUEL CONVERSION INSTRUCTIONS 22 TROUBLESHOOTINGG...

Страница 3: ...perly Set ________________________________ Furnace BTU input _____________________________________ Level ___________________________________________________ Line Pressure _____________________________...

Страница 4: ...al Standard Institute Inc 11 West 42nd Street New York NY 10036 These units are CSA International design certified These unit heaters are certified for installation to combustible material as listed i...

Страница 5: ...nual is to provide information regarding safety design guidelines installation operation and maintenance of the this gas fired unit heater You must read and understand the instructions and all safety...

Страница 6: ...tion of these units must comply with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition and other applicable local building codes In Canada the installation of these units must comply with...

Страница 7: ...ntal pitch as directed in these instructions and the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 or CSA B149 1 Installation Code Determine that there is not blockage restriction l...

Страница 8: ...h a diameter 4 inches greater than the vent pipe diameter must be used If there is 6 feet or more of vent pipe prior to passing through the combustible wall or floor then the metal thimble need only b...

Страница 9: ...than any part of a building within a horizontal distance of 10 3 05m unless otherwise specified by the American National Fuel Gas Code ANSI Z223 1 or Canada CAN CGA B149 Installation Code The vent mu...

Страница 10: ...ombustion which can result in the production of excessive carbon monoxide Follow these guidelines and all applicable codes for all models prior to installing the combustion air duct work WARNING Suffi...

Страница 11: ...drip leg should be installed in the vertical pipe run to the unit In some localities codes may require that a manual main shutoff valve and union furnished by installer be installed external to the un...

Страница 12: ...putting into service For leak testing on pressures below 20 inches W C Before leak testing close the field installed manual shut off valve shown on Figure 9 on the supply line to isolate the gas valve...

Страница 13: ...ure Input Rating W C kPa BTU Hr W W C kPa BTU Hr W HSU200NG 3 81 0 95 184 000 53 925 3 65 0 91 180 000 52 753 HSU250NG 4 15 1 03 230 000 67 407 3 97 0 99 225 000 65 941 HSU300NG 1 46 0 36 276 000 80 8...

Страница 14: ...the side access control compartment of the unit The low voltage thermostat and accessory control devices can be wired to the terminals in the side access control compartment Refer to the wiring diagra...

Страница 15: ...Large Unit Heater 15 Operating Instructions and Owner s Manual Main Components FIGURE 10 Line Voltage Thermostat Wiring Connector on Heater S1 S4 M1 VG MC FS S2 S3 S2 CB SE T1 RFC CFC...

Страница 16: ...Large Unit Heater 16 Operating Instructions and Owner s Manual Internal Wiring Diagram FIGURE 11...

Страница 17: ...field supplied power wires so that they do not come in contact with the flue wrapper or venter housing These hot surfaces may damage the wire s insulation resulting in damage to the unit THERMOSTAT LO...

Страница 18: ...puts set it to the maximum rating 7 Observe the pressure rating on the pressure gauge Verify maximum inlet gas supply pressure 8 Turn off all other gas appliances on the same supply line 9 Observe the...

Страница 19: ...manifold pressure hose connector using a soap solution or equivalent method as described in ANSI Z223 1 NFPA 54 Prior to Leaving Job Site Prior to leaving the job site verify that Service access door...

Страница 20: ...hts burner DO NOT attempt to light the burners manually 5 There is a main shut off valve upstream of the unit Open it See Figure 9 on Page 11 6 Wait five minutes to clear out any gas If you then smell...

Страница 21: ...upply Follow lighting instructions to light unit Check burner flame FLUE PASSAGEWAY AND FLUE BOX The flue passages and flue box should be inspected and cleaned prior to each heating season The sequenc...

Страница 22: ...old Screws FUEL CONVERSION INSTRUCTIONS FIGURE 15 Rotation of the Valve Manifold Assembly ROTATE valve manifold assembly The heater is standard manufactured for operation with natural gas In case of u...

Страница 23: ...NOT FOLLOWED EXACTLY A FIRE EXPLOSION OR PRODUCTION OF CARBON MONOXIDE MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE THE QUALIFIED SERVICE AGENCY PERFORMING THIS WORK ASSUMES RES...

Страница 24: ...space tightly sealed building 1 Remove obstruction or correct vent lengths 2 Replace wiring or hose connections 3 Replace pressure switch The control board does not send spark to the electrode 1 The e...

Страница 25: ...ontrol board does not send 120 VAC to the air movement fan after approx 30 seconds after ignition and if contact relay fan control is open and there isn t 24VAC on relay fan control 3 The control boar...

Страница 26: ...er listed on the unit rating plate Heatstar Large Unit Heater Model HSU200NG HSU250NG HSU300NG HSU400NG Liquid Propane to Natural Gas Conversion Kit HSU200NG F260165 HSU250NG F260166 HSU300NG F260167...

Страница 27: ...91 60291 60291 20 BLOWER DRIVE RELAY 60292 60292 60292 60292 21 PRESSURE SWITCH 60293 60294 60294 60294 22 DETECTION ELECTRODE 60295 60295 60295 60295 23 MANUAL RESET SAFETY THERMOSTAT 140 C 60296 602...

Страница 28: ...447 2194 Address any Warranty Claims to the Service Department Heatstar Inc 4560 W 160TH ST CLEVELAND OHIO 44135 Include your name address and telephone number and include details concerning the claim...

Страница 29: ...a de servicio o la compa a de gas QU HACER SI DETECTA OLOR A GAS NO intente encender el artefacto NO toque ning n interruptor el ctrico no use ning n tel fono en el edificio Abandone el edificio inmed...

Страница 30: ...S 1 28 ESPA OL 29 56 FRANC S 57 84 CONTENIDO SEGURIDAD 2 INTRODUCCI N 5 INSTALACI N 6 PUESTA EN MARCHA 16 MANTENIMIENTO 20 INSTRUCCIONES PARA CONVERSI N DE COMBUSTIBLE 22 GU A DE DIAGN STICO DE PROBL...

Страница 31: ...____________________ BTU de entrada del calefactor __________________________________ Nivelado ____________________________________________________ Presi n de la l nea ________________________________...

Страница 32: ...sponible en American National Standard Institute Inc 11 West 42nd Street New York NY 10036 Estas unidades cuentan con la certificaci n internacional de dise o CSA Estos calefactores est n certificados...

Страница 33: ...El prop sito de este manual es brindar informaci n sobre seguridad pautas de dise o instalaci n operaci n y mantenimiento de este calefactor a gas Debe leer y comprender las instrucciones y todas las...

Страница 34: ...stas unidades debe cumplir con la Norma Nacional de Gas Combustible ANSI Z223 1 NFPA 54 ltima edici n y con las dem s normas de construcci n locales aplicables En Canad la instalaci n de estas unidade...

Страница 35: ...n para ver si tiene el tama o adecuado y la inclinaci n horizontal como se indica en estas instrucciones y en la ltima edici n de la Norma Nacional de Gas Combustible ANSI Z223 1 NFPA 54 o en la norma...

Страница 36: ...uardacabo de metal con un di metro 4 pulgadas mayor que el di metro de la tuber a de ventilaci n Si existen 6 pies o m s de tuber a de ventilaci n antes de pasar a trav s de la pared o el piso combust...

Страница 37: ...r lo menos 2 pies 0 6 m m s alta que cualquier otra parte del edificio dentro de un radio de 10 pies 3 05 m a menos que la Norma nacional de gas combustible EE UU ANSI Z223 1 o la CAN CSA B149 Canad N...

Страница 38: ...nera ineficiente dando como resultado una combusti n incompleta que podr a causar una producci n excesiva de mon xido de carbono Siga estas pautas y todas las normas aplicables para todos los modelos...

Страница 39: ...n en el ca o vertical que se dirige a la unidad En algunas localidades las normas pueden requerir la instalaci n de una llave de corte manual general y una uni n suministradas por el instalador extern...

Страница 40: ...iones inferiores a 20 pulgadas de columna de agua Antes de la prueba de fugas cierre la v lvula de paso manual instalada en campo que se muestra en la Figura 9 en la l nea de suministro para aislar la...

Страница 41: ...614 6 66 1 66 192 000 56 269 HSU250NG 7 23 1 8 250 000 73 268 6 66 1 66 240 000 70 337 HSU300NG 3 81 0 95 300 000 87 921 3 51 0 88 288 000 84 404 HSU400NG 4 74 1 18 400 000 117 228 4 37 1 09 384 000...

Страница 42: ...rol de acceso lateral de la unidad El bajo voltaje termostato y dispositivos de control de accesorios se puede conectar a los terminales en el compartimiento de control de acceso lateral Consulte el d...

Страница 43: ...ctor grande 15 Instrucciones de uso y manual del propietario Componentes principales FIGURA 10 Tensi n de l nea Conector de cableado del termostato al calefactor S1 S4 M1 VG MC FS S2 S3 S2 CB SE T1 RF...

Страница 44: ...ESTE APARATO SE DEBE REEMPLAZAR CON UN CABLE DE IGUAL TAMA O CAPACIDAD Y ESPESOR DEL AISLAMIENTO ADVERTENCIA TENGA EN CUENTA QUE UNA DESCARGA EL CTRICA PUEDE CAUSAR LESIONES O LA MUERTE LA UNIDAD DEB...

Страница 45: ...los cables de alimentaci n en el campo de manera que no entren en contacto con la cubierta de la chimenea o de la ventilaci n Estas superficies calientes pueden da ar el aislamiento del cable y da ar...

Страница 46: ...os otros aparatos a gas tienen m ltiples entradas aj stelos a la calefacci n m xima 7 Observe la indicaci n de presi n en el man metro Verifique la presi n m xima de suministro de gas de entrada 8 Apa...

Страница 47: ...rejillas de aire direccionales est n ajustadas para el flujo de aire deseado y no se cierren ni se ajusten a m s de 60 con respecto a la perpendicular de la cara de la unidad La llave de paso manual...

Страница 48: ...a PROCEDIMIENTOS DE APAGADO 1 Coloque el termostato en su posici n m s baja 2 Apague toda alimentaci n el ctrica al artefacto si va a efectuar cualquier reparaci n 3 Cierre la llave de paso manual que...

Страница 49: ...Antes de cada temporada de calefacci n se deben inspeccionar y limpiar los conductos y la caja del gas de combusti n La secuencia de operaci n debe ser la siguiente 1 Desconecte la unidad del suminist...

Страница 50: ...UCCIONES PARA CONVERSI N DE COMBUSTIBLE FIGURA 15 Rotaci n del mecanismo de v lvula colector ROTE el mecanismo de la v lvula colector El calefactor est fabricado normalmente para funcionar con gas nat...

Страница 51: ...ROVOCAR A DA OS MATERIALES LESIONES PERSONALES O MUERTES LA AGENCIA DE SERVICIO CALIFICADA QUE REALICE ESTE TRABAJO ASUME LA RESPONSABILIDAD DE LA CONVERSI N ADECUADA DE ESTE ARTEFACTO CON ESTE JUEGO...

Страница 52: ...o 1 Elimine la obstrucci n o corrija las longitudes de ventilaci n 2 Reemplace el cableado o la conexi n de la manguera 3 Reemplace el interruptor de presi n La placa de control no env a chispas al el...

Страница 53: ...aprox 30 segundos del encendido y cuando el rel de control del ventilador est abierto y no hay 24 V CA en el rel de control del ventilador 3 La placa de control no env a 120 V CA al ventilador despu...

Страница 54: ...ue aparece en la placa de especificaciones Heatstar Calefactor grande Modelo HSU200NG HSU250NG HSU300NG HSU400NG Kits de Conversi n de Propano L quido a Gas Natural HSU200NG F260165 HSU250NG F260166 H...

Страница 55: ...0293 60294 60294 60294 22 ELECTRODO DE DETECCI N 60295 60295 60295 60295 23 TERMOSTATO DE SEGURIDAD DE REINICIO MANUAL 140 C 60296 60296 60296 60296 24 TERMOSTATO AUTOM TICO DE SEGURIDAD NC 60 C 60297...

Страница 56: ...si le falta alguna llame a nuestro Departamento de Asistencia T cnica al 866 447 2194 Dirija todos los reclamos de garant a al Departamento de servicios Heatstar Inc 4560 W 160TH ST CLEVELAND OHIO 441...

Страница 57: ...sseur de gaz SI VOUS SENTEZ DU GAZ NE TENTEZ PAS d allumer l appareil NE TOUCHEZ aucun commutateur lectrique n utilisez aucun t l phone dans votre b timent Sortez imm diatement du b timent Appelez imm...

Страница 58: ...320 000 BTU Rendement 80 80 80 80 LANGUES ANGLAIS 1 28 ESPAGNOL 29 56 FRAN AIS 57 84 TABLE DES MATI RES S CURIT 2 INTRODUCTION 5 INSTALLATION 6 D MARRAGE 16 ENTRETIEN 20 INSTRUCTIONS DE CONVERSION DU...

Страница 59: ..._____________ Niveau de BTU d entr e de la chaudi re _________________________ niveau _____________________________________________________ Pression des conduits ______________________________________...

Страница 60: ...ute Inc 11 West 42nd Street New York NY 10036 La conception de ces appareils est homologu e par CSA International Ces appareils de chauffage sont homologu s pour l installation aux distances de d gage...

Страница 61: ...nctionnement et de l entretien de cet appareil de chauffage gaz Vous devez lire et comprendre les instructions et toutes les consignes de s curit avant d installer cet appareil de chauffage gaz Ce man...

Страница 62: ...ures graves ou la mort Aux tats Unis l installation de ces appareils doit se conformer au National Fuel Gas Code ANSI Z223 1 NFPA 54 plus r cente dition et aux autres codes du b timent locaux applicab...

Страница 63: ...xistant et qu il emploie un syst me de ventilation d j en place inspectez le syst me de ventilation pour confirmer qu il est de bonne taille et de bonne inclinaison horizontale comme le demandent ces...

Страница 64: ...tible une bague en m tal d un diam tre de 4 po 10 16 cm de plus que le diam tre du conduit doit tre utilis e S il y a 6 pi 1 82 m ou plus de conduit de ventilation avant le passage au travers une cloi...

Страница 65: ...ale de 10 pi 3 05 m moins de mention contraire dans le National Fuel Gas Code ANSI Z223 1 tats Unis ou le Code d installation CAN CGA B149 Canada Le conduit doit se prolonger au moins 5 pi 1 6 m au de...

Страница 66: ...de chauffage ou autre appareil fonctionnera de fa on inefficace ce qui aboutira une combustion incompl te qui peut mener la production d un exc s de monoxyde de carbone Suivez ces directives et tous l...

Страница 67: ...e de conduit pour viter une chute de pression excessive Un collecteur de s diments doit tre install dans la canalisation verticale vers l appareil Dans certaines localit s les codes pourraient exiger...

Страница 68: ...t de mettre l appareil en service Pour les tests l aff t de fuites des pressions inf rieures 20 po W C Avant de tester pour les fuites fermez la soupape de fermeture manuelle install e sur place sur l...

Страница 69: ...610 910mm Pression au Collecteur valuation d Entr e Pression au Collecteur valuation d Entr e W C kPa BTU Hr W W C kPa BTU Hr W HSU200NG 7 23 1 8 200 000 58 614 6 66 1 66 192 000 56 269 HSU250NG 7 23...

Страница 70: ...bornes dans le compartiment d acc s lat ral Consultez le diagramme de c blage pour voir l emplacement des bornes pour tout c blage basse tension AVIS Ces appareils de chauffage emploient un syst me d...

Страница 71: ...fage pour grands locaux 15 Mode d emploi et guide du propri taire Composants principaux FIGURE 10 Tension secteur Connexion du fil du thermostat sur l appareil de chauffage S1 S4 M1 VG MC FS S2 S3 S2...

Страница 72: ...DE COMBUSTION DU MOTEUR SOUPAPE DE GAZ COMMANDE DU TRANSFORMATEUR CAPTEUR DE FLAMME LECTRODE D ALLUMAGE COMMANDE DE RELAIS CONTACT DU VENTILATEUR INTERRUPTEUR DE GAZ AUTOMATIQUE DE S CURIT INTERRUPTE...

Страница 73: ...onnexion MISE EN GARDE Ins rez les fils d alimentation de fa on ce qu ils n entrent pas en contact avec la doublure de la chemin e ou le bo tier de ventilation Ces surfaces chaudes peuvent endommager...

Страница 74: ...i les autres appareils gaz ont plusieurs entr es r glez les l entr e maximum 7 Observez la pression nominale sur l indicateur de pression V rifiez la pression d entr e maximum de l approvisionnement e...

Страница 75: ...directionnelles pour l air sont ajust es pour la circulation d air d sir e et ne sont pas ferm es ou ajust es au del de 60 perpendiculaires la face de l appareil La soupape de fermeture manuelle est...

Страница 76: ...trique PROC DURES D ARR T 1 R glez le thermostat au niveau le plus bas 2 teignez l alimentation lectrique l appareil si vous vous appr tez faire des t ches de service ou d entretien 3 Tournez la poign...

Страница 77: ...GAZ DE COMBUSTION ET BO TE D VACUATION Les passages d vacuation et la bo te d vacuation doivent tre inspect s et v rifi s avant chaque saison de chauffage La s quence suivre est la suivante 1 Coupez...

Страница 78: ...RSION DU COMBUSTIBLE FIGURE 15 Rotation de l assemblage soupape collecteur FAITES PIVOTER l assemblage soupape collecteur L appareil de chauffage est fabriqu selon les normes pour l utilisation avec d...

Страница 79: ...PRODUCTION DE MONOXYDE DE CARBONE POURRAIENT CAUSER DES DOMMAGES AUX BIENS DES BLESSURES OU M ME LA MORT L ENTREPRISE DE SERVICE QUALIFI E EFFECTUANT LES TRAVAUX ASSUME LA RESPONSABILIT DE LA CONVERSI...

Страница 80: ...ou corrigez la longueur du conduit 2 Remplacez le c blage ou les raccords de conduit 3 Remplacez le pressostat Le tableau de commande ne semble pas envoyer l tincelle l lectrode 1 L lectrode semble p...

Страница 81: ...commande de relais contact du ventilateur est ouverte et s il n y a pas de tension 24 V AC la commande de relais du ventilateur 3 Le tableau de commande n envoie pas de tension 120 V AC au ventilateu...

Страница 82: ...la plaque signal tique de l appareil Heatstar Appareil de chauffage pour grands locaux Mod les HSU200NG HSU250NG HSU300NG HSU400NG Kits de Conversion de Propane Liquide en Gaz Naturel HSU200NG F26016...

Страница 83: ...DU SOUFFLEUR 60292 60292 60292 60292 21 PRESSOSTAT 60293 60294 60294 60294 22 LECTRODE DE D TECTION 60295 60295 60295 60295 23 INTERRUPTEUR DE GAZ DE S CURIT POUR R INITIALISATION MANUELLE 140 C 60296...

Страница 84: ...mmag e ou manquante communiquez avec notre service du soutien technique au 866 447 2194 Acheminez toute r clamation sous garantie Service Department Heatstar Inc 4560 W 160TH ST CLEVELAND OHIO 44135 I...

Отзывы: