background image

16

Enerco | enerRadiant® HST Series Heater

Operating Instructions and Owner’s Manual

Non-Pressurized Outside Air Supply Duct

Outside Combustion Air Supply

The Ener-Radiant HST heater is approved for installation with an
outside air supply system. Some compounds such as halogenated
hydrocarbons or other corrosive chemicals in the air can be drawn
into the equipment and cause an accelerated rate of corrosion of
some of the heater components. The use of such chemical
compounds near the enclosure should be avoided.

IMPORTANT:

 If the building has a slight negative pressure or

contaminants are present in the air, an outside combustion air
supply to the heaters is strongly recommended.

For an outside air supply a three (3") inch O.D. single wall pipe may
be attached to the heater. The duct may be up to twenty five (25')
feet maximum length or two (2') feet minimum length with no
more than two (2) elbows.

The air supply duct may have to be insulated to prevent
condensation on the outer surface. The outside air terminal should
be securely fastened to the outside wall by drilling four (4) holes in
the outside flange; wood screws or bolts and expansion sleeves
may be used to fasten terminal.

VERTICAL THROUGH THE ROOF

Intake Vent

3" Starting Collar

¼” per ft.
downwards

6" Min.

3" Dia.

Single-Wall Pipe

Flashing

3' Min.

Vent Cap
(Leslie VersaCap)

Vertical Venting

Air For Combustion (Residential)

If indoor combustion air is to be supplied for a tightly enclosed
area, one square inch of free area opening shall be provided below
the heater for each 1,000 Btu/hr of heater input.

When outside air is used, the opening below the heater shall be
one square inch of free area for each 4,000 Btu/hr of heater input.
In contaminated atmospheres or high humidity areas, optional
outside air for combustion is recommended.

Adequate clearances around the perforated fresh air plate must be
maintained at all times. In larger open areas of buildings,
infiltration normally is adequate to provide air for combustion.

Direct Outside Air For Combustion (Residential)

Outside combustion air should be supplied directly to the heater
when the building is subject to negative pressure or contaminants
are present in the building air. These contaminates include paints,
solvents, corrosive vapors or any other foreign particles that may
cause damage to the heater or result in poor combustion.

Outside combustion air can be brought directly to the heater by a 3
inch diameter duct less than 25 feet long or equivalent. This is
attached to a 3 inch starting collar that is fitted to the top of the
control cabinet after first removing and discarding the perforated
cover. An approved vent cap must be placed directly to the end of
the outside combustion air inlet pipe. The combustion air inlet
should be a minimum of 3 feet, either vertically or horizontally,
from the flue vent termination. The air intake terminal must be
located not less than one foot above grade. It is good installation
practice to supply combustion air from the same pressure zone as
the vent outlet.

In colder climates, where necessary, insulate the fresh air duct.
Avoid locating the fresh air duct directly above the control box.
Provide a capped cleanout T as necessary.

Содержание enerradiant HST35

Страница 1: ...Installation and service must be performed by a qualified installer service agency or the gas supplier If you cannot reach your gas supplier call the Fire Department Gas Fired Low Intensity Infrared H...

Страница 2: ...pour se conformer aux precautions et aux instructions a fourni avec cet appareil de chauffage avoir pour resultat la mort blessure et la perte de propriete ou les dommages physiques serieuses du dang...

Страница 3: ...ST 45 Kit includes 06050 4 Formed Grille 1 End Grilles Installation Kit 02834 1 1 x 24 Long Stainless Flex Hose 2 1 NPT Ball Shut Off Valve 3 1 NPT Pipe Tee 4 1 x 4 Long Nipple 5 1 NPT Pipe Cap Vent K...

Страница 4: ...y downward to the space to be heated Heat Exchanger A U shaped tube through which the heated products of combustion pass Rear Movable Hanger Provides support for the heat exchanger and reflector at th...

Страница 5: ...NS Electrical Rating 120VAC 60Hz single phase 1 amp Connection 3 pin moulded plug Gas Inlet Connection Connection Male NPT Gas Inlet Pressure The minimum inlet gas supply pressure for the purpose of i...

Страница 6: ...is section provides the following information Defines the gas electric and venting requirements for the enerRadiant HST heater Specifies the national standards and applicable codes that apply to the g...

Страница 7: ...the floor Minimum required safe distances to combustibles must be maintained from vehicles parked below the heater When installed over hoists the minimum required safe distances to combustible must be...

Страница 8: ...as required Choose Location for Heater When selecting a suitable mounting location for the enerRadiant HST heater it is important to consider the following 1 The heater must meet the minimum mounting...

Страница 9: ...3 5kPa WARNING Materials and items when stored under this heater will be subjected to radiant heat and could be seriously damaged 4 All horizontal venting sections must slope away from the heater at...

Страница 10: ...ed through the roof be sure to carefully review the roof option installa tion portion of this section Ensure that the selected mounting site will satisfy the measurement param eters vent length not to...

Страница 11: ...ets The tube ends extend through the flanges to help with alignment 3 Using the four long and four short nuts from the bolt kit 02876 secure the tube set to the burner box As shown in the diagram use...

Страница 12: ...1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway that is l...

Страница 13: ...of the National Fuel Gas Code or the authority having jurisdiction In regions of the country where prevailing winds are consistently higher than 40 mph it may be necessary to terminate the vent system...

Страница 14: ...to be constructed of galvanized sheet metal or other approved noncombustible corrosion resistant material as indicated by state and or local codes 2 For horizontal venting the vent lengths may be as f...

Страница 15: ...flue is a problem the flue length should be shortened or insulated g For vent specifications all of the following conditions must be met The maximum equivalent length of vent pipe should be carefully...

Страница 16: ...ded below the heater for each 1 000 Btu hr of heater input When outside air is used the opening below the heater shall be one square inch of free area for each 4 000 Btu hr of heater input In contamin...

Страница 17: ...lectrical Code ANSI NFPA 70 or Canadian Electrical Code CSA 22 1 if an external electrical source is utilized Gas Service Installation Install Gas Supply Lines A gas supply connection is required as s...

Страница 18: ...burrs 3 Use LP resistant joint compound on all threads 4 Check the pipe and tube connections for leaks before placing heating equipment into service When checking for gas leaks use a soap and water so...

Страница 19: ...hen occur 8 Periodic visual check of burner flame while unit is in operation through sight glass in bottom of unit Section 6 MAINTENANCE Pre Season Maintenance Heater area to be kept clear and free fo...

Страница 20: ...h does not operate Igniter spark gap incorrect Try This Unplug heater power cord from the electrical outlet wait for a minimum of five seconds Plug heater cord back into outlet Unplug heater power cor...

Страница 21: ...essure requirements contact the gas company Check for 24V across valve terminals Check Shutoff On Valve IF NO Check wiring between the ignition module and the valve Repair replace wires as required If...

Страница 22: ...keyed to the associated parts list I B A C J F H G D E ITEM PART NUMBER DESCRIPTION HST 35 HST 45 A 02808 Spark Electrode 1 1 B 02837 Ignition Wire 1 1 C 05735 Orifice HST35 NG 1 05795 Orifice HST 45...

Страница 23: ...er Box for F108847 F102850 HST 45NG Burner Box for F108850 F102851 HST 45LP Burner Box for F108851 B F106000 HST 35 Tube Set Short F106250 HST45 Tube Set Long C 06014 Hanger D 06016 Hanger Clamp E 060...

Страница 24: ...lso supply us with the purchase date and the name and address of the dealer from whom you purchased our product The foregoing is the full extent of the responsibility of the Company There are no other...

Отзывы: