3.6 ELECTRICAL
WARNING: THIS APPLIANCE MUST BE EARTHED. IT IS SUITABLE FOR
A.C. SUPPLY ONLY.
ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY A COMPETENT
ELECTRICIAN AND BE IN ACCORDANCE WITH THE LATEST I.E.E. WIRING
REGULATIONS.
ENSURE THE ELECTRICAL SUPPLY IS SWITCHED OFF BEFORE MAKING
ANY CONNECTIONS TO THE STREAMLINE.
Connect the Streamline to a 230V or 240V a.c. earthed supply only.
1.
A double pole isolating switch having a contact separation of at least 3mm
2.
in each pole must be incorporated in the supply.
The Streamline must be fitted with a 3 core 1.5mm
3.
2
flexible cable. The
cable must be fitted through the cable gland and connections made to
the internal terminal block as follows:
BROWN or RED to terminal marked “L”
BLUE or BLACK to terminal marked “N”
GREEN/YELLOW or GREEN wire to terminal marked
FIGURE 08: SPOUT FRONT
SPOUT FRONT
SPOUT BODY
GREEN&YELLOW
BROWN/RED
BLUE/BLACK
ELEMENT
EARTH POST
LIVE (RED)
NEUTRAL (BLACK)
CUT-OUT BULB
THERMOSTAT BULB
COMBINED THERMOSTAT
AND CUT OUT
TO ELEMENT
TERMINAL BLOCK
CUT OUT
RESET
A
B
1
2
FIGURE 09 - WIRING DIAGRAM