MAINTENANCE

39

FAILURES WITH ERROR MESSAGE

Some system failure modes can be recognised by the solar differential 

temperature controller and will be indicated by an error message on the 

controller display. Refer to the table below for details of possible errors 

and suggested measures to rectify.

NOTE: 

These error messages wil automatically reset when the fault has 

been rectified. In the case of the circulation error this may take a few 

minutes to clear once normal flow has resumed.

FAILURES WITHOUT ERROR MESSAGES

For faults and malfunctions that cannot be displayed, you can use 

the following table to identify them, plus evaluate the possible causes 

and sources of such erors. If you cannot rectify the fault by using the 

description below, you will need to contact your supplier or installer.

IMPORTANT:

 Any faults involving the 230V/AC mains power supply must 

only be rectified by a technician.

Resistance table PT1000.
The correct function of temperature sensros can be checked on the basis 

of the following temperature resistance table with a resistance measuring 

instrument:

Error displayed

on-screen

Possible 

causes

Actions to take

Disruption to 

sensor cable

Check cable

Sensor defective Check sensor resistance, 

replace sensor if necessary

Short-circuit in 

sensor cable

Check cable

Sensor defective Check sensor resistance 

replace if necessary

Circulation fault:

no flow-through

Fault in pump 

connection

Check cabling

Pump defective

Replace pump

Air in the system Vent system
Flow meter 

defective

If visible, check whether the 

flywheel of the meter moves 

when the system is running

Also displayed 

with energy yield 

measurement:

Grundfos sensor 

defective

Check VFS sensor. 

Measured voltage at 

terminal should be 

between 0.5 and 3.5V DC

Connection 

to flow meter 

defective

Check cable

Disruption to 

sensor cable

Check cable

Sensor defective Check sensor resistance, 

replace sensor if necessary

Error display

Possible causes

Actions to take

No possible 

display

230V mains power 

supply unavailable

Switch on or connect up 

control unit
Check fuses for building 

power supply

Fuse inside unit 

defective

Check fuse*, replace if 

necessary with new 2A 

(T) fuse.
Check 230V compo-

nents for short-circuits

Unit defective

Contact your supplier

Outputs are not 

switched on

Unit is in manual 

operation mode

Exit “Manual Operation” 

menu

Switch-on condition 

not yet achieve

Wait until switch-on 

condition achieved

“Pump” icon 

turns, but pump 

is not on

Disruption to pump 

connection

Check cable to pump

Pump has seized up

Ensure pump can run 

smoothly

Switched output has 

no current

Contact your supplier

Temperature 

display fluctuates 

strongly at short 

intervals

Sensor cabling has 

been laid near to 

230V cables

Reposition sensor 

cabling, shield sensor 

leads

Long sensor cables 

extended using 

unshielded leads

Shield sensor leads

Unit defective

Contact your supplier

!

!

!

!

X

flashing

flashing

X

!

+

flashing

X

Temperature 

in ºC

Resistance in 

Ohm

-30

882

-20

921

-10

960

0

1000

10

1039

20

1077

30

1116

40

1155

50

1194

Temperature 

in ºC

Resistance in 

Ohm

60

1232

70

1271

80

1309

90

1347

100

1385

120

1461

140

1535

200

1758

Fault finding:

Содержание Megaflo Eco SolaReady

Страница 1: ...ot Water Cylinders Megaflo Eco SolaReady Unvented Important Please read understand all these instructions before commencing installation Please leave this manual with the customer for future reference...

Страница 2: ...Direct model 17 Indirect model 18 Installation of solar differential temperature controller 21 East West Array Kit 22 Commissioning 23 Commissioning of solar primary system 24 Commissioning of hydraul...

Страница 3: ...nels its temperature is raised The heated fluid is circulated through a heat exchanger coil in the base of the Megaflo Eco SolaReady solar storage cylinder transferring the heat gained to the stored w...

Страница 4: ...L CAPABILITIES OR LACK OF EXPERIENCE AND KNOWLEDGE IF THEY HAVE BEEN GIVEN SUPERVISION OR INSTRUCTION CONCERNING USE OF THE APPLIANCE IN A SAFE WAY AND UNDERSTAND THE HAZARDS INVOLVED CHILDREN SHALL N...

Страница 5: ...team heating plant unless additional and appropriate safety devices are installed Ascending spray type bidets or any other Class 5 back syphonage risk requiring that a Type AA AB AD or AG air gap be e...

Страница 6: ...ELECTRICIAN AND BE IN ACCORDANCE WITH THE LATEST I E E WIRING REGULATIONS ENSURE THE ELECTRICAL SUPPLY IS SWITCHED OFF BEFORE MAKING ANY CONNECTIONS TO THE MEGAFLO ECO SOLAREADY The Environment This p...

Страница 7: ...to 40 C 260 248 300 Weight empty kg 60 7 69 1 75 4 Weight full kg 320 312 369 Volume Litres 259 243 294 Dedicated solar volume Litres 91 4 83 4 118 0 Max mains pressure 1 6 MPa 16 Bar Max design press...

Страница 8: ...s no requirement to site it close to the unit it can be located at a point where the mains supply enters the premises if this is more convenient but you must install a non return valve just after the...

Страница 9: ...e plumbed to the inlet connection of the Megaflo Eco SolaReady unit No other valve should be fitted between the Pressure Relief Expansion Valve and the cylinder inlet Outlet to Megaflo eco Solar Mains...

Страница 10: ...atmosphere see page 14 Discharge Pipework Isolating Regulating Valves as required Temperature Pressure Relief Valve HWS supply Balanced HWS and MCWS to bathrooms showers cloakrooms etc DOC DOC DOC DO...

Страница 11: ...f a secondary circulation system is required it is recommended that it be connected to the Megaflo Eco SolaReady as shown in Figure 7 To achieve this the 1 2 BSP Sensor Pocket must be removed The seco...

Страница 12: ...he discharge pipe should not be blocked or used for any other purpose The discharge connections from the Pressure Relief Expansion Valve and the Temperature Pressure Relief Valve must not be used for...

Страница 13: ...ter for prolonged periods should be used Worked example of discharge pipe sizing This example is for a G temperature relief valve with a discharge pipe D2 having 4 No elbows and length of 7m from the...

Страница 14: ...l outlet size of the safety device between 18 and 27m at least 3 sizes larger and so on bends must be taken into account in calculating the flow resistance See Diagram 1 Table 1 and the worked example...

Страница 15: ...s of up to 150 C The solar collectors panels or evacuated tubes must be installed according to the instructions supplied with those selected We can only guarantee the system performance if installed i...

Страница 16: ...water expansion vessel or boiler sealed system vessel The charge pressure of the solar expansion vessel must be adjusted when the fluid circuit is empty or de pressurised to a pressure equal to the st...

Страница 17: ...the event of a thermostat failure The thermal cut out reset button position is indicated on Figure 13 DO NOT BYPASS THE THERMAL CUT OUT IN ANY CIRCUMSTANCES The lower immersion heater can be operated...

Страница 18: ...mostat and thermal cut out MUST NOT be disconnected or bypassed To do so would invalidate the product approvals and warranty and it would not comply with Building Regulations Should this method of con...

Страница 19: ...4 N N 1 2 GY BL BR GR OR L N Room stat CH 2 port valve CH pump Solar pump 11 12 A1 N 11 12 E Solar pump 1 L1 NOTE For boilers with pump over run CH pump live supply should be connected to terminal 5...

Страница 20: ...d N 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Link Link Link 9 12 N 12 1 1 2 3 GY BL BR GR OR Cylinder auxiliary controls DHW 2 port valve N 7 8 N 8 11 5 4 N N 1 2 GY BL WH GR OR L N Room stat 3 port mid...

Страница 21: ...N Switched Output 2 Neutral A3 Switched Output Live 3 For Auxiliary Heat Control N Switched Output 3 Neutral PE Earth Connection T1 M1 Temperature Sensor Collector 1 Tc1 T2 M2 Temperature Sensor Stora...

Страница 22: ...n is on the East facing circuit The common return pipe from the solar pump station should be connected to the comman Port In the default position the valve is open to Port B When power is applied to t...

Страница 23: ...ct Units Switch on the electrical supply to the immersion heater s and allow the unit to heat up Check that the thermostat operates correctly A storage temperature of approx 60 C is recommended If nec...

Страница 24: ...drain valve on the safety group Fig 19 Item 1 Close right hand isolating valve dot on thermometer bezel at 9 o clock position Flush solar primary pipework and collector via the fill and drain valve o...

Страница 25: ...lot of the adjusting screw Fig 19 Item 3 back to the horizontal position Commissioning of hydraulic station Ensure the solar primary system is free from air Switch on the power supply to the solar dif...

Страница 26: ...e button is pressed and held the value increments continuously Scroll left Exit Cancel Scroll left in main menu Exit a menu Exit a menu item Cancel a value changed without saving it Access Down Access...

Страница 27: ...erature measuring point T6 only shown if connected No 1234 h Operating hours for charging storage tank Can be reset to 0h Yes 927 kWh Energy yield for storage tank Can be reset to 0h Yes Inclination e...

Страница 28: ...selection 0 Normal 230V pump 1 1 HE pump with non inverse PWM Alternatively DC control 2 2 HE pump with inverse PWM Alternatively DC control Energy yield measurement glycol type selection 0 Anro 6 Ty...

Страница 29: ...Kelvin h Operating hours kWh Productivity indication in kWh OVERVIEW OF DISPLAY AND OPERATING ELEMENTS Graphic symbol Description Indication in operation Measuring points assignment Temperature measur...

Страница 30: ...ircuit pump via PWM signal The controller emits a PWM signal at connection O1 for the control of PWM pumps jumper position PWM Base frequency 2 kHz approx 12 V approx 5 mA Non inverse PWM control Non...

Страница 31: ...erature limits possible If the difference between both measurement points exceeds the hystere sis set then A3 is activated In addition one may also define a maximum temperature for the energy consumer...

Страница 32: ...eze If the temperature at the anti freeze sensor line 12 drops below the set value the solar circuit pump is activated and heats the solar circuit using the heat exchanger in the storage tank Basic Se...

Страница 33: ...k dTmax is kept constant as much as possible At lower deviation of Storage tank dTmax the pump is operated with the lowest power till the switch off wave is reached 11 14 Thermostat heating 1 The ther...

Страница 34: ...rmal insulation Fig 26 Item 2 against the rear thermal insulation section Fig 26 Item 3 until it clips into place Benchmark Log Book On completion of the installation and commissioning procedures deta...

Страница 35: ...aximum storage temperature 65 C Storage tank 1 Switch on difference dTon 7 K Storage tank 1 Switch off difference dToff 3 K Storage tank 2 Maximum storage temperature 90 C Storage tank 2 Switch on dif...

Страница 36: ...ate Check solar expansion vessel charge pressure bar bar bar bar bar bar bar bar bar bar bar bar bar Check solar primary system pressure cold bar bar bar bar bar bar bar bar bar bar bar bar bar Check...

Страница 37: ...ly to the immersion heater s and shut down the boiler on indirect units Turn off the mains water supply to the Megaflo Eco SolaReady unit Attach a hosepipe to the drain cock having sufficient length t...

Страница 38: ...r The collector or the collector array must be checked serviced annually to check for any damage leaks or contamination In areas where there may be a build up of dirt on the collector only non abrasiv...

Страница 39: ...p Air in the system Vent system Flow meter defective If visible check whether the flywheel of the meter moves when the system is running Also displayed with energy yield measurement Grundfos sensor de...

Страница 40: ...t in event insufficient solar gain Check If tripped reset by pressing button Check Set to a CH programme Check Switch on supply to immersion heater Check boiler operation If faulty contact boiler manu...

Страница 41: ...termittent Is the discharge continuous and very hot YES YES NO NO Heating fault water may have cooled Blending valves set too low Thermostat settings too low Water from hot taps is lukewarm Contact an...

Страница 42: ...y sensor connections Are sensor cables laid alongside mains voltage cables Have sensor cables been lengthened with unshielded cable Do sensors give correct temperature v resistance readings Are temper...

Страница 43: ...mersion Heater Backnut 95 607 940 Immersion Heater Gasket 70 351 65 Immersion Heater Key 95 607 861 Immersion Heater Blanking Plug 95 605 881 Titanium Immersion Heater Upper 95 606 989 Titanium Immers...

Страница 44: ...3 Bar Inlet Control Valve 3 Bar Pressure Reducing Valve Complete Expansion Relief Cartridge 8 Bar Pressure Relief Valve Complete 95 605 893 Figure 19 Exploded View of 8 Bar Pressure Relief Valve Figu...

Страница 45: ...07 932 E Titanium Immersion Heater Upper 95 606 989 Direct Combined Thermostat and Thermal Cut Out 95 612 717 Gasket 95 611 822 Backnut 95 607 940 Terminal cover 95 614 119 See Figure 21 for Solar Con...

Страница 46: ...ket 95 611 822 Backnut 95 607 940 Terminal cover 95 614 119 C 1 2 BSP Sensor Pocket Assembly Short 95 607 938 A D E C Direct Combined Thermostat and Thermal Cut Out 95 612 717 A Mounting Plate Direct...

Страница 47: ...hermometer 0 120 Blue 5 7225264 Venting circuit DN25 6 720688701 Flow meter 2 15 l min 7 7225266 Pump PWM connector FCI Connector 2m 8 7225265 Pump power supply connector TE Superseal 2m 9 7222382 Gru...

Страница 48: ...ecial Product Division Units 9 10 Hexagon Business Centre Springfield Road Hayes Middlesex UB40 0TY Tel 0208 5730574 Parts Center Network 65 Business Park Bentley Wood Way Burnley Lancashire BB11 5ST...

Страница 49: ...SERVICING 49...

Страница 50: ...ansfer fluid details What type make of heat transfer fluid used System volume litres What is the fluid mix Water Glycol Frost protection provided to C Is the installation in a hard water area above 20...

Страница 51: ...SERVICING 51...

Страница 52: ...pply products that meet or exceed appropriate standards and building and water regulations To provide pre and post sales technical support To provide clear and concise warranty details to customers 36...

Отзывы: