COMMISSIONING
30
“Basic Setup” menu
Display
Meaning
Value
range
Factory
setting
Line Value
11
240
Controller response time in s
30-480
240
12
1
Primary storage tank selection
1-2
1
1. RPM CONTROL
The A1 and A2 outputs can be operated using RPM control. For the
following control types:
• 230V block modulation
• Analogue signal
• PWM signal
The value set limits the minimum control value. The minimum pump RPM
can be configured in a range between 30% and 100%. If the value of
100% is set, then RPM control is switched off.
“Programming” menu
Display
Meaning
Value
range
Factory
setting
min
100
Set minimum pump capacity using
RPM control
100% = RPM control off
30%-
100%
100%
2.1 STANDARD 230V AC PUMPS
• 230V block modulation
RPM control for switched output A1 and switched output A2 (if not reser-
ved for valve).
“Basic Setup” menu
Display
Meaning
Value range
Factory
setting
Line Value
19
0
Type of pump
control
0= Standard pump: A1
RPM-controlled - 230V
block modulation
0
20
0
Type of pump
control
0= Standard pump: A2
RPM-controlled - 230V
block modulation
1
2.2 HE PUMPS
The temperature difference controller in the solar circuit controls the so-
lar pump RPM in a range between 30% and 100%. The minimum pump
RPM can be configured in a range between 30% and 100%. If a value of
100% is set, then RPM control is switched off. The pump RPM given by
the controller is indicated as “nSoll” in the curves shown overleaf.
• Control of the solar circuit pump via PWM signal
The controller emits a PWM signal at connection O1 for the control of
PWM pumps (jumper position PWM). Base frequency = 2 kHz, approx.
12 V, approx. 5 mA.
• Non-inverse PWM control
Non-inverse PWM control: Target RPM 0-100% equates to PWM 0-100%.
Used for solar applications.
2
“Basic Setup” menu
Display
Meaning
Value range
Factory
setting
Line Value
19
0
Type of pump
control
1 = HE pump: Analogue or
non-inverse PWM control
0
20
0
Type of pump
control
1 = HE pump: Analogue or
non-inverse PWM control
0
Control output
A1
O1
O1
A2
O2
O2
230V AC
Analogue Type A
0
2
4
6
8
10
0
50
100
150
nSoll in %
U
in
V
ol
t
bei nmin = 30 %
0
20
40
60
80
100
0
25
50
75
100
nSoll in %
PW
M
in
%
bei nmin = 30 %
PWM Type A
0
2
4
6
8
10
0
50
100
150
nSoll in %
U
in
V
ol
t
bei nmin = 30 %
0
20
40
60
80
100
0
25
50
75
100
nSoll in %
PW
M
in
%
bei nmin = 30 %
A1 and A2 no RPM control, only switched operation on/off. Minimum
switch-on time 5 sec
“Basic Setup” menu
Display
Meaning
Value range
Factory
setting
Line
Value
3
2
Collector protection
function
0 = Off
1 = On
2 = Drainback
0 = Off
4
120ºC
Collector protection
temperature
80-150ºC
120ºC
5
180
Fill time for drain-back
function
15-360 sec
180 sec
2. INDEPENDENT CONTROLLER
This function is set to output 3 and can be configured for the following
functionality.
• Cooling
• Heating
• Difference regulator
The temperature sensor for the temperature source can be selected as
desired.
• Cooling
If the temperature measured exceeds the target value, then output A3 is acti-
vated until the temperature measured drops below the target value hysteresis.
Commissioning of solar differential temperature controller