2.4.6. Filter warning
The controller of the ventilation unit uses a counter to
keep track of when the filters need to be cleaned or
replaced. If it detects that a filter is dirty, an LED (4) on
the ventilation unit starts blinking orange.
1
2
3
4
5
6
AWW
ON
ON
VKK
COM
Key
1
Balance supply setting
2
Potentiometer for high speed setting
3
Potentiometer for low speed setting
4
Status LED / Dirty filter indication
5
Communication port
6
DIP switch settings (VKK & AWW)
Note
It is advisable to check the LED on the ventilation unit
on a regular basis.
ä
Caution!
If a dirty filter is detected, a signal is also sent to the
resident by suddenly reversing the operation of the
control: when the
Low Speed
button on the remote
device is pressed, the ventilation unit starts running at
high speed
, and when the
High Speed
button is
pressed the ventilation unit starts running at
low
speed
. When this happens, check the LED on the
ventilation unit. If it is blinking orange, the filter needs
to be cleaned or replaced.
2.4.7. Status LED
The appliance is equipped with a status LED on the
control panel. The status LED can display the following
messages:
Pattern
Function
Green
Orange
Blinks 1x/s
Blinks 1x/s
Identification
Blinks 1x/s
Pairing mode
Lit 6 s
Blinks 1x/s
Frost mode
Lit 5 s
Blinks 2x/s
Bypass mode
Lit
Normal operation
Pattern
Function
Red
Orange
Blinks 1x/s
Blinks 1x/s
Exhaust fan fault
Blinks 1x/s
Blinks 2x/s
Supply fan fault
Blinks 2x/s
Blinks 2x/s
Exhaust temperature
sensor fault
Blinks 2x/s
Blinks 3x/s
Supply temperature
sensor fault
Blinks 3x/s
Blinks 1x/s
Sensor fault
Blinks 1x/s
Filter dirty
2.5. Grilles
The quantity of air that must be extracted is legally
regulated, and the quantity of air supplied must stand in
proportion to this. This means that the same amount of
air must be supplied as is extracted. The minimum air
quantity per room is also legally regulated. The quantities
have been selected to ensure that no unnecessary energy
is wasted whilst still achieving an optimal indoor climate.
This is why the air extraction and supply valves differ in
size between rooms. Each of the extraction and supply
grilles therefore has a specific fixed position and setting.
Note
It is very important that you do not adjust the grilles
in any way, to ensure proper operation of the entire
ventilation system. Grilles and air valves should not
be swapped around.
2.6. Applications with new housing
developments
High levels of moisture is found in building materials for
new housing – about 4,000 litres per house on average.
This moisture originates from wet building materials such
as concrete, cement, plaster and adhesives. Materials can
also become wet from rain during the construction
period. The best way to eliminate this moisture is to
10
Содержание HRU ECO 4
Страница 1: ...HRU ECO 4 User manual...
Страница 2: ...Translation of the original document...